The YTZ-150 provides a mechanical pressure reading at the equipment and a resistance signal for a remote indicator or controller. Its built-in slide-wire transmitter follows the pressure mechanism, allowing a compatible receiving instrument to monitor pressure away from the measurement point.
The 150mm dial suits pump rooms, constant-pressure water supply equipment and industrial monitoring panels. The remote circuit can work with a compatible VFD or secondary instrument that accepts a potentiometer input. Select liquids, steam or gases that do not corrode the copper-alloy wetted components.
| Parameter | Specification |
|---|---|
| Model | YTZ-150 |
| Dial diameter | 150mm |
| Accuracy class | 1.6 |
| Process connection | M20×1.5 |
| Mounting | Radial / bottom connection; install vertically |
| Case / connection material | Iron case / brass connection |
| Approximate weight | 585.4g |
| External terminal voltage | <6V |
| Initial transmitter resistance | 3–20Ω |
| Full-scale resistance | 310–400Ω; match the actual endpoints to the receiving input |
| Operating temperature | -5°C to 55°C |
| Relative humidity | ≤80% |
| Temperature influence | Additional deviation ≤0.4% per 10°C departure from 20±5°C |
Pressure-span examples include 0–0.6MPa, 0–1MPa and 0–1.6MPa, with other ranges selected for the application. Choose the calibrated span marked on the supplied dial.
| Wire color | Function |
|---|---|
| Red | Fixed end at the low-resistance side |
| Yellow | Sliding contact / variable resistance output |
| Green | Opposite fixed end of the resistance element |
The mechanical dial operates without electrical power. The remote circuit uses excitation from the receiving instrument within the terminal-voltage limit. Match the resistance endpoints and wiring to that instrument before commissioning. The English manual includes the translated wiring diagram.
Install the gauge vertically and, where practical, at the same elevation as the measurement point. Account for liquid-head error if the elevations differ. Avoid vibration transmitted through the installation and use suitable isolation or damping where the process requires it.
Keep steady pressure between one-third and two-thirds of full scale. For fluctuating pressure, use between one-third and one-half of full scale. Verify the gauge at least every three months and arrange repair promptly if an indication or resistance-output fault develops.