Spring-Loaded Flue and Air-Duct Thermocouple Assemblies

Description

Flue and air-duct temperature measurement

These assemblies use a drilled protective tube with a reduced measuring end and a spring-loaded sheathed sensing insert. The larger protective tube and process thread support use in flue and air-duct service. The sensing insert and protective tube are separate components, allowing replacement of the sensing element. A water-resistant aluminum connection head is provided; other head models are available.

Model and element selection

ModelElementsElement typeTemperature rangeAccuracy classNominal pressureProtective tube material
WRNR-12SingleK0-800°CI or II9.8MPa06Cr18Ni11Ti
WRNR2-12Dual
WRER-12SingleE0-700°C
WRER2-12Dual

Protective tube and connection dimensions

Reduced section dimensionsOuter sleeve dimensionsProcess thread optionsHeadSingle-element electrical entryDual-element electrical entry
28mm and 16mm diameters; 46mm length20mm diameter; 250mm lengthZG2 (2in), NPT2 (2in) or M60x3Water-resistantM20x1.5; 10mm cableM24x1.5; 16mm cable

Standard total and insertion lengths

Total lengthInsertion length
480mm230mm
680mm430mm
880mm630mm
1380mm1130mm

Other specifications can be supplied for the application. Select a total-length and insertion-length pair together.