Reduced-Tip Sheathed Thermocouples with Threaded Mounting

Description

Narrow sensing tip for confined positions

The measuring end of this sheathed thermocouple is reduced to 3mm or another required size. The sensing element contacts the measured medium directly. A threaded fixing and reinforced connecting tube join the probe to a small aluminum alloy waterproof head for installation at specific equipment locations.

Sensor type Element Sheath material Sheath diameter Range Class I tolerance Class II tolerance
WRNK
Nickel-chromium / nickel-silicon
K 06Cr18Ni11Ti 3mm, 4mm, 5mm or 6mm 0-800°C ±1.5°C or ±0.4%t ±2.5°C or ±0.75%t
GH3030 3mm, 4mm or 5mm 0-900°C
6mm 0-1100°C
WREK
Nickel-chromium / copper-nickel
E 06Cr18Ni11Ti 3mm, 4mm, 5mm or 6mm 0-700°C
WRFK
Iron / copper-nickel
J 3mm 0-400°C
4mm, 5mm or 6mm 0-600°C
WRCK
Copper / copper-nickel
T 3mm, 4mm, 5mm or 6mm -200-300°C ±0.5°C or ±0.4%t ±1°C or ±0.75%t

The table retains the available ranges and tolerances. The body sheath diameter and reduced measuring-tip dimension are separate specifications.

Threaded fixing and insertion

Sheath diameter Fixing Thread choices Insertion Head Electrical entry
3mm, 4mm, 5mm or 6mm Fixed screw thread M27×2, M33×2 or NPT1/2 50-150mm or user-specified Small aluminum alloy waterproof head M20×1.5