Integrated Thermocouple and RTD Probes with 4-20mA Output

Description

Integrated temperature sensing and transmission

The SGW family combines a thermocouple or resistance temperature probe with a transmitter installed in the connection head. It converts the sensing signal into a temperature-linear two-wire 4-20mADC output. The thermocouple transmitter includes cold-junction compensation. Small or large stainless steel heads and aluminum heads are available, along with local pointer or digital display options.

Sensing element selections

Sensor categoryElement optionsConstructionSheath diametersBasic transmitter accuracy
ThermocoupleK, N, E, J, T, S, R or BSingle or dual sheathed elements3mm, 4mm, 5mm, 6mm or 8mm0.75%FS
RTDPt100, Cu50 or Cu1000.25%FS

Electrical and environmental specifications

ParameterSpecification
Output4-20mADC, linear with measured temperature; two-wire transmission
Supply12-40V; nominal 24VDC; reverse-polarity protection
Maximum load resistanceRmax=(Vs-7.5V)/0.022A, where Vs is the supply voltage
Transmitter vibration resistance4g over 2-150Hz
Open-sensor lower alarmOutput below 3.5mADC for two-wire RTD and thermocouple transmitter modules
Open-sensor upper alarmUser set; 20.5mADC is an example setting
Ingress protectionIP65
Flameproof marking optionsEx d IIB T4-T5 or Ex d IIC T1-T6
GT ambient option-20-70°C
LT ambient option-40-80°C
Relative humidity0-100%, non-condensing

Installation and signal connection

Connection structures can be selected for thermal mounting sleeves, while reinforced sleeve versions can mount directly to the equipment. Two-wire current transmission uses ordinary copper wiring. Match the output to the current input of a display, recorder, controller, PLC or computer control system. An LB830S barrier pairing is also listed as an available system option.