EYS-100K-2CO Digital Pressure Controllers

Description

Pressure indication, switching and transmission

The EYS-100K-2CO combines local LED pressure indication with two relay outputs and continuous signal transmission. Standard 4–20mA output connects to a receiving instrument or automation system; 0–10V and RS485 Modbus-RTU are configuration options. The 304 stainless steel housing and threaded process fitting support industrial installation.

Applications include natural-gas equipment, chemical processes, water supply and filtration, pumping systems, metallurgy, industrial machinery, hydraulics and pneumatics. Select the pressure range and sensing construction for the process. Diffused-silicon sensing configurations are available within the family.

Technical specifications

ParameterSpecification
ModelEYS-100K-2CO
Pressure-range selections0.5–300MPa; multiple spans and configurations available
Accuracy±0.5%FS
Temperature drift±0.01%FS/°C
Long-term stability±0.1%FS/year within the temperature-compensated range
Analog outputs4–20mA as standard; optional 0–10V
Switching outputsTwo relays
Communication optionRS485, Modbus-RTU
Supply24VDC; optional 220V version
Overload, -0.1–16MPa configurations2× rated pressure
Overload, 25–100MPa configurations1.5× rated pressure
MediaLiquids and gases that do not corrode the wetted components
Medium temperature-20°C to 70°C
Humidity0–95%RH
Process connectionStainless steel threaded fitting
Housing304 stainless steel
CalibrationThree-point calibration at zero, midpoint and full scale

Process and electrical integration

EYS-100K stainless steel threaded pressure fitting
The threaded fitting connects the controller to the pressure measurement point.

The front panel provides the pressure readout and local setting keys, while the rear terminal connection supports integration with the selected supply and output circuits. Two relays provide switching functions alongside the configured analog signal. Optional RS485 connects the instrument to a compatible Modbus-RTU monitoring system.

Specify the measuring span, required outputs, communication option, supply version and process connection. Apply the overload limit for the configured pressure range. Compatible water, air, oil and hydraulic media can be monitored when they meet the wetted-material and temperature requirements.