ELE-806 Sanitary Clamp Pressure Transmitters

Description

Flush diaphragm with a quick-clamp connection

The ELE-806 uses a flush sensing face to reduce blockage when measuring viscous liquids or media containing particles. A 50.5mm sanitary clamp connection allows the instrument to be removed for cleaning or maintenance. The standard construction combines diffused-silicon sensing with a 304 stainless steel housing.

Applications include food processing, wastewater treatment, petrochemical equipment, vacuum systems and industrial automation. The family includes standard and digital versions, with high-temperature configurations identified separately. Explosion-proof, armored and glass-microfused constructions are additional customization choices.

Standard construction

ParameterSpecification
Sensor and diaphragmDiffused-silicon sensing; flush diaphragm
Housing304 stainless steel
Process connection50.5mm sanitary quick-clamp ferrule
Accuracy±0.5%FS
Overload capacity1.2× full scale for instantaneous pressure impact
Operating temperature0–50°C
Supply10–30VDC; see output-specific requirements below
Outputs4–20mA, 0–10V or RS485
MediaLiquids or gases compatible with 304 stainless steel

Model and electrical options

ParameterELE-806ELE-806SELE-806G1ELE-806SG1
VersionStandardDigitalHigh temperatureDigital, high temperature
Local LCDNoneFour digitsNoneFour digits
Temperature0–50°C0–100°C
Nominal sensing-range bands±200–800Pa; -100–900kPa; 1–100MPa±200–800Pa; -100–900kPa; 1–10MPa
Pressure referenceGauge or absolute, according to configuration
Current outputTwo-wire 4–20mA; 10–30VDC supply
Voltage output choicesThree-wire 0–5V or 0–10VDC
Supply for 0–10V12–30VDC15–30VDC12–30VDC15–30VDC
Digital outputFour-wire RS485
Accuracy options±0.2% or ±0.5%
Electrical connectionHirschmann connector
ProtectionIP65

The nominal sensing range does not define the allowable pressure of the clamp assembly. Select the sensor span together with the pressure and temperature ratings of the ferrule, clamp and seal. The 0–100°C rating applies to G1 and SG1 high-temperature constructions.

Configuration for the process

Specify the pressure range and reference, operating temperature, required output and local-display preference. For voltage versions, select the supply appropriate to the model. Use the flush diaphragm with compatible media and a correctly rated sanitary connection. The English catalogue provides the model selection tables and additional construction options.