ECY-810 Digital Pressure Controllers

Description

Automatic pressure switching and pump protection

The ECY-810 combines digital pressure measurement, indication and relay control. Adjustable upper and lower limits allow high-stop/low-start operation; reverse mode provides low-stop/high-start operation. Delay settings help reduce repeated pump starts when line pressure fluctuates.

Water-shortage protection, automatic pressure-change checking, parameter locking and power-off memory support unattended operation. Typical applications include water supply, pump systems, compressed air, hydraulic equipment, pipelines, water engineering, food-processing equipment and industrial automation using compatible media.

Technical specifications

ParameterSpecification
Selectable spans0–0.1, 0–0.6, 0–1.6, 0–2.5, 0–10, 0–25, 0–40, 0–60 and 0–160MPa; additional spans available by configuration
Additional range choices0–0.4MPa and 0–1MPa; vacuum configurations available
Pressure referenceGauge; absolute or vacuum configurations optional
Accuracy class0.5%
Overload capacity150% of full scale
DisplayDigital pressure readout with power, upper-limit, lower-limit and run indicators
Sampling rate5 readings/s
OutputRelay switching signal
Contact/load ratings380V: 3A; 220V: 5A; 24V: 5A
Supply choices24VDC, 220VAC or 380VAC; select the required version
Operating temperature-20°C to 80°C
MediaLiquids and gases compatible with 316L stainless steel, including suitable water, air and oil
Pressure unitsMPa, PSI or kg/cm²
Process connectionsM20×1.5, G1/2 or G1/4; M14×1.5 and other custom connections available
Electrical protectionReverse-polarity and short-circuit protection
Reference dimensionsBody Ø80mm; depth 48mm; overall height 115mm; process-connection projection 35mm

Relay wiring and operation

LeadFunction
RedSupply; V+ for the DC version
BlueSupply return; V- for the DC version
BlackRelay common, COM
WhiteRelay normally closed contact, NC

In normal control, the black–white circuit opens at the upper pressure limit and closes at the lower limit. Reverse mode changes the control direction. For loads above 700W, use the contactor arrangement in the English manual with a coil voltage matching the circuit. In a 380VAC arrangement, the controller and coil use line-to-line voltage.

Settings and protection functions

FunctionOperation
h000 / h001Adjustable switching delay in seconds; h001 represents a one-second delay
P000 / P001Parameter protection prevents unintended changes
t000 / t001Normal or reverse pressure control
S000 / S001Automatic pressure check; opens the relay if pressure does not change for three minutes after closure
LuALAdjustable water-shortage pressure threshold
L000 / L001Detection time for pressure to reach the water-shortage threshold

With run mode off and the pipe unpressurized, hold ▼ for five seconds to zero the reading. Briefly press ▲ to change pressure units. SET opens the lower-limit setting, then the upper-limit setting; use ▲/▼ to adjust and SET to save. If the lower value cannot be increased enough, set the upper limit first. Press ON/OFF to start operation.

To enter advanced settings, turn run mode on, hold SET for three seconds and use SET to move through the functions. Press ON/OFF twice to exit. A value of 000 disables the corresponding function. The English manual contains the complete menu procedures, functional wiring diagrams and troubleshooting table for E--F, E--E, E--I and E--r.

Installation

Tighten at the process hex with a wrench, keeping torque off the housing. Check the supply version and wiring before energizing. Protect the sensing diaphragm from contact with hard objects and zero the instrument after installation to compensate for mounting stress.