The ECY-80X combines pressure measurement, LED indication, upper/lower alarm control and protection functions. Separate alarm leads support automatic switching or alarm signalling at the configured pressure limits. Applications include constant-pressure water supply, pumps, compressed air, hydraulic systems, oil-pressure equipment and industrial pipelines.
The stainless steel case has a reinforced rim and a sealed electrical entry. Vibration resistance, water-shortage protection, pressure-detection protection and password protection support operation in industrial equipment. One-button zero correction and power-off memory simplify setup and preserve settings.
| Parameter | Specification |
|---|---|
| Control output | Upper- and lower-limit alarms; dual relay output |
| Sampling rate | 10 readings/s |
| Pressure reference | Gauge or absolute |
| Alarm settings | Adjustable throughout the configured measuring range |
| Indication and units | LED display; MPa, kg/cm² or psi |
| Standard supply | 220VAC |
| Supply options | 12VDC, 24VDC or 380VAC versions |
| Contact capacity | 5A, resistive load |
| Ambient temperature | -20°C to 50°C |
| High-temperature option | -20°C to 200°C process measurement |
| Housing | Stainless steel |
| Process-fitting material | 304 stainless steel |
| Measured media | Liquids or gases noncorrosive to the wetted materials, including compatible water, air and oil |
| Parameter | Ceramic | Diffused silicon | Glass microfused |
|---|---|---|---|
| Pressure range choices | -0.1–60MPa | -0.1–100MPa | 0.5–300MPa |
| Accuracy | ±0.5% | ±0.4% or ±0.2%, custom | ±0.5%, custom |
| Overload capacity | 1.5× full scale | 2× full scale | |
| Sensor temperature | -20°C to 80°C | -20°C to 50°C | Configuration dependent |
| Process threads | M20×1.5, M14×1.5, G1/2, G1/4, G3/8 or G3/4 | M20×1.5 only | |
Select the sensor for the required pressure span, accuracy and medium temperature. The high-temperature option does not increase the permitted ambient temperature. The glass-microfused construction has its own range, overload and process-thread limits.

| Cable colour | Function |
|---|---|
| Red / brown pair | Supply input |
| Yellow | Common, COM |
| Blue | Upper-limit alarm output |
| Black | Lower-limit alarm output |
| Reference dimension | Value |
|---|---|
| Front bezel diameter | Ø88.3mm |
| Main case diameter | Ø78.7mm |
| Overall depth | 48.1mm |
| Main case depth to bezel | 36.3mm |
| Main case top to thread end | 117.2mm |
| Main case top to process-hex bottom | 99.4mm |
Local settings provide pressure-unit selection, zero adjustment, bidirectional control and delay functions. The panel shows power, upper limit, lower limit and run status. Select the supply version, measuring range, thread and output requirements for the installation. The English specification sheet includes the complete sensor table and dimensional drawing.