ECY-60X and ECY-100 controllers measure pressure, show it on an LED display and switch equipment at adjustable pressure limits. Both support high-stop/low-start and low-stop/high-start control modes, with alarm settings adjustable across the configured measuring range. Sampling at 10 readings per second provides regular pressure updates.
The stainless steel housing, reinforced rim and vibration-resistant construction suit water tanks, water-supply systems, air compressors, hydraulic equipment, oil-pressure systems, pipelines and industrial automation. Use compatible liquids or gases that do not corrode the wetted stainless steel.
| Parameter | ECY-60X | ECY-100 |
|---|---|---|
| Display | LED digital pressure display | |
| Sampling | 10 readings/s | |
| Control output | Upper/lower limit alarm and switching output | One relay output with hysteresis control |
| Contact capacity | 5A, resistive load | 10A, resistive load |
| Supply choices | 12VDC, 24VDC or 220VAC | 12VDC, 24VDC, 220VAC or 380VAC |
| Pressure reference | Gauge or absolute | |
| Nominal accuracy | ±0.5%; sensor-specific alternatives below | |
| Control modes | Stop at upper limit and start at lower limit; or stop at lower limit and start at upper limit | |
| Shared operating functions | One-button zero adjustment, saved settings after power loss, water-shortage protection, pressure-detection protection and password protection | |
| Additional functions | Switch-contact life ≥100,000 operations | Adjustable hysteresis and delay, MPa/PSI/kg/cm² unit selection, factory reset and reverse-polarity protection |
| Ambient temperature | -20°C to 50°C | |
| Process-fitting material | 304 stainless steel | |
| Process threads | M14×1.5, M20×1.5, G1/4 or G1/2; custom connections available | |
| Parameter | Ceramic | Diffused silicon | Glass microfused |
|---|---|---|---|
| Selectable pressure range | -0.1–60MPa | -0.1–100MPa | 0.5–300MPa |
| Accuracy choices | ±0.5% | ±0.2% or ±0.4% | ±0.5% |
| Overload capacity | 1.5× full scale | 2× full scale | |
| Sensor temperature range | -20°C to 80°C | -20°C to 50°C | Configuration dependent |
A high-temperature construction is available for process temperatures up to 200°C. This option does not change the -20°C to 50°C ambient limit. Select the sensing construction for the required pressure span, accuracy, overload tolerance and medium temperature.


On ECY-100, hysteresis and delay functions help control repeated start/stop operation around a switching point. One-button zero correction compensates for zero drift, while password protection limits unintended setting changes. Power-off memory retains the configured parameters after a supply interruption.
Choose the supply version and contact capacity for the application. The 5A and 10A capacities apply to resistive loads. Match the process connection and sensor range to the intended water, air, oil or hydraulic installation.