How a Time Delay Relay Works in 10 Timing Diagrams

Omron power off-delay relay with a seconds dial beside a CNTD multifunction time relay with three blue adjustment knobs.
Table of Contents

Suppose a machine has a cooling fan that must run for 30s after the machine stops. Which event starts those 30s? The run signal might drop while the control panel stays powered. Or stopping the machine might disconnect power to the timer itself. Both requirements sound like “off-delay,” but they call for different timers.

A time delay relay switches an output according to a timing function and a preset interval. Depending on the function, the interval can postpone switching, limit how long an output stays on, or set the cadence of a repeating cycle. To read any of these functions, find the event that starts the clock, then follow the output through to the end of the interval.

How to Read On-Delay and Interval-On Timing Diagrams

Read each diagram from left to right. A vertical step marks a change of state. A high Supply line means the timer has power. A high Trigger line means a separate control input is active. A high Output line means the timed output has operated. For a changeover contact, that closes the path from common to normally open (NO) and opens the path from common to normally closed (NC). The bracket above the traces shows which two events are separated by the set time.

Take two power-start timers, both set to 5s. Apply power at 0s and remove it at 8s. The on-delay timer waits until 5s to operate, giving the load a 3s operating window before power is removed. The interval-on timer operates immediately and releases at 5s, even though it still has power. A machine that should wait before enabling its next stage needs the first sequence. A lamp that should light for the first five seconds needs the second.

Supply rises at 0s. The on-delay output rises at 5s and falls with the supply at 8s.
The interval output rises with the supply at 0s and falls at 5s while power remains on.
Follow the output at the 5s mark. The on-delay contact operates just as the interval-on contact releases.

Here, applying power starts both cycles. A timer can also offer a signal-start on-delay mode. In that case, supply is already present and the 5s begins when a separate input becomes active. Follow the start of the timing bracket down to the trace that changes there.

When Does the Countdown Start for Off-Delay and True Off-Delay?

For the cooling fan, set the stop command at 0s on the time axis. With a signal off-delay, the timer has continuous control power. The run signal operates the output immediately. When that signal disappears, the timer holds the output for another 30s before releasing it. This fits a panel where the machine can stop while the timer and fan circuit remain powered.

A true off-delay, also called a power off-delay, starts its countdown when its own supply disappears. Its contacts can stay in the operated position for the specified interval after that event. This solves the timing requirement when the timer loses supply with the machine. The fan and any contactor that must stay pulled in still need a source of power during the overrun. A closed timer contact alone cannot keep the motor turning.

With continuous supply, a restart at 20s cancels the pending release. The trigger falls again at 25s and the output releases at 55s.
The timer supply falls at 0s. The true off-delay output stays operated until 30s.
At 0s the signal off-delay timer loses its trigger and the true off-delay timer loses its supply. Only the first example receives a restart.

Two details matter in practice. First, consider a restart. In the retriggerable signal off-delay illustrated here, if the run signal returns 20s into the overrun, the pending release is canceled. If the signal goes low again at 25s, release is due at 55s. Second, for a power off-delay timer, check the minimum time it must be powered before it can perform the delay. The OMRON H3CR-H specifications list a minimum power-on time of 0.1s for the S-series and 2s for the M-series. This is a requirement before shutdown, separate from the release delay set on the dial.

A third function, on/off delay, times both edges of a separate trigger. In the example below, the trigger must stay on for 3s to operate the output. A 1s pulse therefore produces no operation. Once the output is on, the trigger must stay off for 2s before the output releases. The brief interruption from 10s to 11s ends too soon to release it.

A short trigger gives no output. A sustained trigger produces an output after 3s. The final trigger removal starts a 2s release delay.
Supply stays on throughout. The trigger rises at 4s and the output operates at 7s. The final falling edge at 13s starts the 2s delay to release.

What Happens When a Second Trigger Arrives?

Imagine a sensor pulse that should light an indicator for 5s. A second pulse arrives 3s after the first. Should the lamp go out at 5s or 8s? Both timings are available, and a diagram showing only one pulse would make them look identical.

Two trigger pulses arrive at 0s and 3s. The single-shot output runs from 0s to 5s.
With the same two trigger pulses, the second pulse restarts the timer at 3s and the output releases at 8s.
The trigger pulses are identical in both diagrams. The second rising edge moves the release time only on the retriggerable timer.

A single shot accepts the first rising edge and produces one fixed output pulse. Further triggers during that pulse are ignored, so the lamp goes out at 5s. A retriggerable single shot starts a fresh interval at each qualifying rising edge. The lamp stays on through both pulses and goes out at 8s. This second function can serve as a watchdog. If a sensor sends a pulse on every revolution of a shaft, each valid pulse renews the interval. A full interval of silence lets the output drop, which another circuit can use to indicate loss of motion.

Reading Repeating Cycles and Star–Delta Changeover

For a repeating output, first check what happens as soon as power is applied. An off-first flasher waits through its first interval before it turns on. The example below then alternates equal 2s intervals. The on-first repeat-cycle example starts immediately and uses two different settings, 3s on and 1s off. A buyer specifying an intermittent lamp or valve needs to state the starting state as well as both durations. A single shared time setting can only give the two halves equal lengths in the simple flasher shown here.

An off-first flasher waits 2s before its first on period, then alternates 2s on and 2s off.
An on-first repeat-cycle output turns on for 3s, turns off for 1s and repeats while powered.
Read the first interval at power-up, then measure one complete cycle. Both examples repeat every 4s, but they give the load different on-times.

A star–delta timer controls two separate outputs in sequence. At startup the star output operates. When the star interval expires, that output releases. Both outputs then remain off for the transfer interval before the delta output operates. On the chart, put a finger at the end of the star trace and follow the gap to the start of delta. That gap is a distinct setting on timers such as the CNTD CDT6-ST. The example values below illustrate the sequence. Actual settings depend on the motor and starter.

Star output is active from 0s to 5s. Both outputs are off for 0.5s before delta output operates.
With a 5s star interval and a 0.5s transfer interval, the delta command begins at 5.5s. These traces show the timer’s commands to the starter contactors.

Choosing a Time Delay Relay from the Required Sequence

Start with the sentence you want the controls to obey. For the original fan, one specification reads, “When the run signal disappears, keep the fan enabled for 30s. If the machine restarts during that time, keep the fan running and start a fresh 30s at the next stop.” Those words identify the trigger, the output state during timing, and the required response to a second event. Choose a signal off-delay whose diagram or operating description confirms that a fresh run signal cancels the pending release. If stopping also removes the timer’s supply, look for a power off-delay model and check its power-on requirement and the fan’s supply path.

Read the function setting along with the time dial. The IDEC RTE-B1AD24 has four selectable modes. With MODE set to A (on-delay), the output waits for the set time before it operates. With MODE set to B (interval), the output operates as soon as power is applied and releases after the set time. The other two modes provide repeating cycles that start with the output off or on. IDEC specifies a 24VAC/DC supply for this model. When sizing the output contacts, check their rating for the load they will switch.

Front of the IDEC RTE-B1AD24 timer with a numbered time dial and MODE, SCALE and RANGE selectors.
The photo shows MODE A with a 0–30 dial scale and RANGE set to minutes. The RANGE selector offers seconds, minutes, hours and 10-hour increments.

Finally, compare the required interval with the model’s time range and timing tolerance. Check the trigger type, minimum pulse width and reset time if the machine cycles quickly. Match the contact arrangement and switching rating to the actual load, including the duty of an inductive contactor coil where applicable. For the fan, trace the first stop, a restart during the overrun, and the next stop. The right relay keeps the fan enabled through that restart and releases it one full interval after the final stop.