| Part Number: | UV | - | EC | - | D000 | 32 | P |
|---|---|---|---|---|---|---|---|
| Explanation: |
Platform UV - Vertical integrated I/O module |
Protocol PN - PROFINET |
Output Model Prefix D000 - Fixed prefix of the digital-output models listed in this series |
Output Channels 16 - 16 outputs |
Output Polarity P - PNP |
UV vertical integrated modules combine a network interface and digital outputs in one DIN rail unit. Each model supports the protocol shown in its row. Choose the protocol, channel count and output polarity together; protocol variants are separate products.
| Protocol | 16-channel PNP | 32-channel PNP | 16-channel NPN | 32-channel NPN |
|---|---|---|---|---|
| PROFINET | UV-PN-D00016P | UV-PN-D00032P | UV-PN-D00016N | UV-PN-D00032N |
| EtherCAT | UV-EC-D00016P | UV-EC-D00032P | UV-EC-D00016N | UV-EC-D00032N |
| EtherNet/IP | UV-EIP-D00016P | UV-EIP-D00032P | UV-EIP-D00016N | UV-EIP-D00032N |
| CC-Link IE Field Basic | UV-CB-D00016P | UV-CB-D00032P | UV-CB-D00016N | UV-CB-D00032N |
| Modbus TCP | UV-MT-D00016P | UV-MT-D00032P | UV-MT-D00016N | UV-MT-D00032N |
| Models | Transmission rate | Interface data capacity | Addressing |
|---|---|---|---|
| All UV-PN models above | 10/100Mbps, full duplex | 1024 bytes maximum | PROFINET specification |
| All UV-EC models above | 100Mbps | EtherCAT specification | |
| All UV-EIP models above | EtherNet/IP specification | ||
| UV-CB-D00016P | 10/100Mbps, full duplex | RX and RY: 64 bits each; RWr and RWw: 32 words each, per logical station | CC-Link IE Field Basic specification |
| UV-CB-D00032P, UV-CB-D00016N, UV-CB-D00032N | 100Mbps | Not specified here | |
| All UV-MT models above | 1024 bytes maximum | Modbus TCP specification |
Interface data capacities are separate from the physical output count. A 16-channel output image uses 16 output bits; a 32-channel image uses 32 output bits.
| Property | Specification | Applies to |
|---|---|---|
| Station type | Remote I/O station | All models |
| Station occupancy | 1 station | |
| Communication distance | ≤100m between stations | |
| Topology | Bus topology | |
| Transmission medium | Ethernet CAT5 cable | |
| Interface isolation | Electrical isolation from the field layer | |
| Periodic-data port | 61450 | All UV-CB models above |
| Node-search port | 61451 | |
| PROFINET features | RT, declared Class C conformity, MRP, automatic addressing and topology detection | All four UV-PN models above |
| Alarm functions | Diagnostic alarms and process alarms | All four UV-PN models above and UV-CB-D00016P |
| Output type | ON state | OFF state |
|---|---|---|
| PNP sourcing, models ending in P | 24VDC, ±25% | Nominal 0VDC; ±3% tolerance with unspecified reference quantity |
| NPN sinking, models ending in N | Nominal 0VDC; ±3% tolerance with unspecified reference quantity | 24VDC, ±25% |
The reference for the low-state ±3% tolerance is unspecified. It does not establish an absolute residual-voltage limit. PNP outputs drive loads connected to the 0VDC return; NPN outputs switch loads connected to the positive field supply.
| Output property | All models |
|---|---|
| Connection arrangement | 1-wire |
| Reverse-circuit protection | Provided |
| Isolation | Optical isolation from the field layer |
| Module error diagnosis | Provided; individual output-port functions are specified separately below |
| Parameter | All models |
|---|---|
| Installation envelope, depth × width × height | 80 × 24 × 115mm |
| Mounting | 35mm DIN rail, vertical installation |
| Protection rating | IP20 |
| Pollution degree | 2 |
| Operating temperature | -10°C to +55°C |
| Storage temperature | -20°C to +85°C |
| Relative humidity | 5-95%RH, non-condensing |
The upright body drawing for the four PROFINET models and UV-CB-D00016P specifies 110mm body height, 24mm width and 80mm depth. The 115mm installation height allows for the projecting parts shown outside the body dimension.
The following detailed supply, terminal, indicator and software specifications apply to the four UV-PN models in the selection table and UV-CB-D00016P. They are not electrical ratings for the other protocol variants.
| Model | System feed current | Working supply |
|---|---|---|
| UV-PN-D00016P | 98mA | 24VDC, +20%/−15% |
| UV-PN-D00032P | 153mA | |
| UV-PN-D00016N | 79mA | |
| UV-PN-D00032N | 113mA | |
| UV-CB-D00016P | 98mA |
| Connection property | These five models |
|---|---|
| Terminal technology | Push-in spring terminals; solid conductors can be inserted directly |
| Conductor cross-section | 0.34-1.5mm² |
| Conductor size | 22-16AWG |
| Strip length | 8-10mm |
| Power interface | 3-position terminal |
| Rail fixing | Slot and latch for 35mm DIN rail |
| Channel indication | Dedicated indicators for the corresponding output states |
Use the A/B group below for UV-PN-D00016P, UV-PN-D00016N and UV-CB-D00016P. The two 32-channel PROFINET models use both A/B and C/D groups. The output labels 00-07, 10-17, 20-27 and 30-37 identify groups of eight channels.
| Left signal | Left terminal | Right terminal | Right signal |
|---|---|---|---|
| Output 00 | A1 | B1 | Output 10 |
| Output 01 | A2 | B2 | Output 11 |
| Output 02 | A3 | B3 | Output 12 |
| Output 03 | A4 | B4 | Output 13 |
| Output 04 | A5 | B5 | Output 14 |
| Output 05 | A6 | B6 | Output 15 |
| Output 06 | A7 | B7 | Output 16 |
| Output 07 | A8 | B8 | Output 17 |
| Field +24V | A9 | B9 | Field +24V |
| Field 0V | A10 | B10 | Field 0V |
| Left signal, 32-channel PN models | Left terminal | Right terminal | Right signal |
|---|---|---|---|
| Output 20 | C1 | D1 | Output 30 |
| Output 21 | C2 | D2 | Output 31 |
| Output 22 | C3 | D3 | Output 32 |
| Output 23 | C4 | D4 | Output 33 |
| Output 24 | C5 | D5 | Output 34 |
| Output 25 | C6 | D6 | Output 35 |
| Output 26 | C7 | D7 | Output 36 |
| Output 27 | C8 | D8 | Output 37 |
| Field +24V | C9 | D9 | Field +24V |
| Field 0V | C10 | D10 | Field 0V |
Supply the field terminals externally: Field +24V connects to the positive 24VDC supply and Field 0V to its return.
| Insulated ferrule | Conductor cross-section | Ferrule length L |
|---|---|---|
| E0310 | 0.3mm² | 10mm |
| E0510 | 0.5mm² | |
| E7510 | 0.75mm² | |
| E1010 | 1.0mm² | |
| E1510 | 1.5mm² |
| Indicator | Colour and state | Meaning |
|---|---|---|
| PWR | Green on | Normal power supply |
| Off | No power or abnormal power supply | |
| RUN | Green on | System operating normally |
| Off | Abnormal operation | |
| Flashing | Factory reset after holding the button for 10 seconds | |
| SYS | Red off | No module fault |
| Red on | Module fault; currently indicates a bus fault | |
| ERR | Red off | Network connection normal |
| Red flashing | Network connection abnormal | |
| Channel LEDs | Green on / off | Output active / inactive; labels 00-07 and 10-17, plus 20-27 and 30-37 on the 32-channel models |
| Output data | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| Byte 0, all five detailed models | DO07 | DO06 | DO05 | DO04 | DO03 | DO02 | DO01 | DO00 |
| Byte 1, all five detailed models | DO17 | DO16 | DO15 | DO14 | DO13 | DO12 | DO11 | DO10 |
| Byte 2, 32-channel PN models only | DO27 | DO26 | DO25 | DO24 | DO23 | DO22 | DO21 | DO20 |
| Byte 3, 32-channel PN models only | DO37 | DO36 | DO35 | DO34 | DO33 | DO32 | DO31 | DO30 |
A bit value of 1 activates the corresponding output, at a high electrical level for PNP or a low level for NPN. A value of 0 makes that output inactive.
| Software function | Five detailed models |
|---|---|
| Fault-stop output state | Retain current value |
| Output-port abnormality detection and indication | Not provided |
| Configurable output logic level | Not supported |
| Independent channel-enable configuration | Not supported |
| Configurable diagnostic reporting | Not supported |
| Stopped mode | Follow the fault-stop state mode and preset value; no further refresh |
| I/O access | Bit, byte and word access |
| Parameter | Specification |
|---|---|
| Altitude | Below 2000m; 80kPa reference |
| Overvoltage category | II |
| Power-line immunity | 2kV, IEC 61000-4-4 |
| EMC environment | Zone B, IEC 61131-2 |
| Vibration | IEC 60068-2-6: 5-8.4Hz at 3.5mm amplitude; 8.4-150Hz at 9.8m/s²; X, Y and Z axes, 100 minutes per axis in ten 10-minute cycles |
| Shock | IEC 60068-2-27: 9.8m/s², 11ms; three shocks in each of six directions across the X, Y and Z axes |
| Declared conformity | CE; supporting certificate number not specified here |
| Installation clearances | 10mm between adjacent modules; 45mm above and 25mm below |
Install vertically in a ventilated enclosure or cabinet. Keep the module away from equipment that could cause overheating, and disconnect power before fitting or removing it. Engage the upper edge of the rail latch with the DIN rail, then seat the module. For removal, disconnect signal and power cables, release the latch with a flat screwdriver and reverse the mounting movement. Inspect for obstructions if a module resists fitting.
| UL use group | Rated current | Rated voltage | Rated cross-section |
|---|---|---|---|
| B | Not specified | Not specified | Not specified |
| C | |||
| D |