UV Vertical Integrated Digital Output Modules

Series Part Number

Part Number: UV - EC - D000 32 P
Explanation:

Platform

UV - Vertical integrated I/O module

Protocol

PN - PROFINET
EC - EtherCAT
EIP - EtherNet/IP
CB - CC-Link IE Field Basic
MT - Modbus TCP; separate models for each protocol

Output Model Prefix

D000 - Fixed prefix of the digital-output models listed in this series

Output Channels

16 - 16 outputs
32 - 32 outputs; both counts listed for all five protocols

Output Polarity

P - PNP
N - NPN; both polarities listed at each protocol and channel count

Description

Protocol and output selection

UV vertical integrated modules combine a network interface and digital outputs in one DIN rail unit. Each model supports the protocol shown in its row. Choose the protocol, channel count and output polarity together; protocol variants are separate products.

Protocol16-channel PNP32-channel PNP16-channel NPN32-channel NPN
PROFINETUV-PN-D00016PUV-PN-D00032PUV-PN-D00016NUV-PN-D00032N
EtherCATUV-EC-D00016PUV-EC-D00032PUV-EC-D00016NUV-EC-D00032N
EtherNet/IPUV-EIP-D00016PUV-EIP-D00032PUV-EIP-D00016NUV-EIP-D00032N
CC-Link IE Field BasicUV-CB-D00016PUV-CB-D00032PUV-CB-D00016NUV-CB-D00032N
Modbus TCPUV-MT-D00016PUV-MT-D00032PUV-MT-D00016NUV-MT-D00032N

Network specifications

ModelsTransmission rateInterface data capacityAddressing
All UV-PN models above10/100Mbps, full duplex1024 bytes maximumPROFINET specification
All UV-EC models above100MbpsEtherCAT specification
All UV-EIP models aboveEtherNet/IP specification
UV-CB-D00016P10/100Mbps, full duplexRX and RY: 64 bits each; RWr and RWw: 32 words each, per logical stationCC-Link IE Field Basic specification
UV-CB-D00032P, UV-CB-D00016N, UV-CB-D00032N100MbpsNot specified here
All UV-MT models above1024 bytes maximumModbus TCP specification

Interface data capacities are separate from the physical output count. A 16-channel output image uses 16 output bits; a 32-channel image uses 32 output bits.

PropertySpecificationApplies to
Station typeRemote I/O stationAll models
Station occupancy1 station
Communication distance≤100m between stations
TopologyBus topology
Transmission mediumEthernet CAT5 cable
Interface isolationElectrical isolation from the field layer
Periodic-data port61450All UV-CB models above
Node-search port61451
PROFINET featuresRT, declared Class C conformity, MRP, automatic addressing and topology detectionAll four UV-PN models above
Alarm functionsDiagnostic alarms and process alarmsAll four UV-PN models above and UV-CB-D00016P

Output polarity and protection

Output typeON stateOFF state
PNP sourcing, models ending in P24VDC, ±25%Nominal 0VDC; ±3% tolerance with unspecified reference quantity
NPN sinking, models ending in NNominal 0VDC; ±3% tolerance with unspecified reference quantity24VDC, ±25%

The reference for the low-state ±3% tolerance is unspecified. It does not establish an absolute residual-voltage limit. PNP outputs drive loads connected to the 0VDC return; NPN outputs switch loads connected to the positive field supply.

Output propertyAll models
Connection arrangement1-wire
Reverse-circuit protectionProvided
IsolationOptical isolation from the field layer
Module error diagnosisProvided; individual output-port functions are specified separately below

Mechanical and environmental specifications

ParameterAll models
Installation envelope, depth × width × height80 × 24 × 115mm
Mounting35mm DIN rail, vertical installation
Protection ratingIP20
Pollution degree2
Operating temperature-10°C to +55°C
Storage temperature-20°C to +85°C
Relative humidity5-95%RH, non-condensing

The upright body drawing for the four PROFINET models and UV-CB-D00016P specifies 110mm body height, 24mm width and 80mm depth. The 115mm installation height allows for the projecting parts shown outside the body dimension.

Power and wiring for the PROFINET models and UV-CB-D00016P

The following detailed supply, terminal, indicator and software specifications apply to the four UV-PN models in the selection table and UV-CB-D00016P. They are not electrical ratings for the other protocol variants.

ModelSystem feed currentWorking supply
UV-PN-D00016P98mA24VDC, +20%/−15%
UV-PN-D00032P153mA
UV-PN-D00016N79mA
UV-PN-D00032N113mA
UV-CB-D00016P98mA
Connection propertyThese five models
Terminal technologyPush-in spring terminals; solid conductors can be inserted directly
Conductor cross-section0.34-1.5mm²
Conductor size22-16AWG
Strip length8-10mm
Power interface3-position terminal
Rail fixingSlot and latch for 35mm DIN rail
Channel indicationDedicated indicators for the corresponding output states

Terminal assignment

Use the A/B group below for UV-PN-D00016P, UV-PN-D00016N and UV-CB-D00016P. The two 32-channel PROFINET models use both A/B and C/D groups. The output labels 00-07, 10-17, 20-27 and 30-37 identify groups of eight channels.

Left signalLeft terminalRight terminalRight signal
Output 00A1B1Output 10
Output 01A2B2Output 11
Output 02A3B3Output 12
Output 03A4B4Output 13
Output 04A5B5Output 14
Output 05A6B6Output 15
Output 06A7B7Output 16
Output 07A8B8Output 17
Field +24VA9B9Field +24V
Field 0VA10B10Field 0V
Left signal, 32-channel PN modelsLeft terminalRight terminalRight signal
Output 20C1D1Output 30
Output 21C2D2Output 31
Output 22C3D3Output 32
Output 23C4D4Output 33
Output 24C5D5Output 34
Output 25C6D6Output 35
Output 26C7D7Output 36
Output 27C8D8Output 37
Field +24VC9D9Field +24V
Field 0VC10D10Field 0V

Supply the field terminals externally: Field +24V connects to the positive 24VDC supply and Field 0V to its return.

Insulated ferruleConductor cross-sectionFerrule length L
E03100.3mm²10mm
E05100.5mm²
E75100.75mm²
E10101.0mm²
E15101.5mm²

Indicators for the five detailed models

IndicatorColour and stateMeaning
PWRGreen onNormal power supply
OffNo power or abnormal power supply
RUNGreen onSystem operating normally
OffAbnormal operation
FlashingFactory reset after holding the button for 10 seconds
SYSRed offNo module fault
Red onModule fault; currently indicates a bus fault
ERRRed offNetwork connection normal
Red flashingNetwork connection abnormal
Channel LEDsGreen on / offOutput active / inactive; labels 00-07 and 10-17, plus 20-27 and 30-37 on the 32-channel models

Process data and software behaviour

Output dataBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
Byte 0, all five detailed modelsDO07DO06DO05DO04DO03DO02DO01DO00
Byte 1, all five detailed modelsDO17DO16DO15DO14DO13DO12DO11DO10
Byte 2, 32-channel PN models onlyDO27DO26DO25DO24DO23DO22DO21DO20
Byte 3, 32-channel PN models onlyDO37DO36DO35DO34DO33DO32DO31DO30

A bit value of 1 activates the corresponding output, at a high electrical level for PNP or a low level for NPN. A value of 0 makes that output inactive.

Software functionFive detailed models
Fault-stop output stateRetain current value
Output-port abnormality detection and indicationNot provided
Configurable output logic levelNot supported
Independent channel-enable configurationNot supported
Configurable diagnostic reportingNot supported
Stopped modeFollow the fault-stop state mode and preset value; no further refresh
I/O accessBit, byte and word access

Environmental and installation details for the five documented models

ParameterSpecification
AltitudeBelow 2000m; 80kPa reference
Overvoltage categoryII
Power-line immunity2kV, IEC 61000-4-4
EMC environmentZone B, IEC 61131-2
VibrationIEC 60068-2-6: 5-8.4Hz at 3.5mm amplitude; 8.4-150Hz at 9.8m/s²; X, Y and Z axes, 100 minutes per axis in ten 10-minute cycles
ShockIEC 60068-2-27: 9.8m/s², 11ms; three shocks in each of six directions across the X, Y and Z axes
Declared conformityCE; supporting certificate number not specified here
Installation clearances10mm between adjacent modules; 45mm above and 25mm below

Install vertically in a ventilated enclosure or cabinet. Keep the module away from equipment that could cause overheating, and disconnect power before fitting or removing it. Engage the upper edge of the rail latch with the DIN rail, then seat the module. For removal, disconnect signal and power cables, release the latch with a flat screwdriver and reverse the mounting movement. Inspect for obstructions if a module resists fitting.

Additional rating information

UL use groupRated currentRated voltageRated cross-section
BNot specifiedNot specifiedNot specified
C
D