UV Vertical Integrated Digital Input and Output Modules

Series Part Number

Part Number: UV - EC - D16C16 P
Explanation:

Platform

UV - Vertical integrated I/O module

Protocol

PN - PROFINET
EC - EtherCAT
EIP - EtherNet/IP
CB - CC-Link IE Field Basic
MT - Modbus TCP

I/O Configuration

D16C16 - 16 digital inputs accepting NPN or PNP signals and 16 digital outputs; fixed configuration in this series

Output Polarity

P - PNP outputs
N - NPN outputs; both output types listed for each protocol

Description

Model and protocol selection

Each UV vertical integrated module combines 16 digital inputs, 16 digital outputs and a network interface in a 24mm-wide DIN rail housing. Inputs accept NPN or PNP signals; the final P or N in the model identifies the output polarity. Select the required protocol and output type together. Each listed model is a separate protocol variant.

ProtocolPNP output modelNPN output modelInputs / outputs
PROFINETUV-PN-D16C16PUV-PN-D16C16N16 / 16
EtherCATUV-EC-D16C16PUV-EC-D16C16N
EtherNet/IPUV-EIP-D16C16PUV-EIP-D16C16N
CC-Link IE Field BasicUV-CB-D16C16PUV-CB-D16C16N
Modbus TCPUV-MT-D16C16PUV-MT-D16C16N

Network specifications

ModelsTransmission rateInterface data capacityAddressing
UV-PN models10/100Mbps, full duplex1024 bytes maximumPROFINET specification
UV-EC models100MbpsEtherCAT specification
UV-EIP modelsEtherNet/IP specification
UV-CB modelsRX and RY: 64 bits each; RWr and RWw: 32 words each, per logical stationNot specified here
UV-MT models1024 bytes maximumModbus TCP specification

Interface capacity is separate from the physical channel count. The PROFINET models use separate two-byte input and two-byte output images, detailed below.

PropertySpecificationApplies to
Station type and occupancyRemote I/O station; 1 stationAll models
Communication distance≤100m
TopologyBus topology
Transmission mediumEthernet CAT5 cable
Network isolationElectrical isolation
Periodic-data / node-search ports61450 / 61451UV-CB models
PROFINET functionsRT, declared Class C conformity, MRP, automatic addressing and topology detectionUV-PN models
AlarmsDiagnostic alarms and process alarms

Digital input and output characteristics

Input characteristicSpecificationScope
Input channels16All models
Signal typesNPN and PNP
PNP input ON / OFF15-30V / -3V to +3V
NPN input ON / OFF-3V to +3V / 15-30V
Typical input current4mA at 24VUV-PN-D16C16P and UV-PN-D16C16N
3mAUV-EC, UV-EIP, UV-CB and UV-MT models listed above
Input voltage grade24VDC, ±10%UV-PN-D16C16P and UV-PN-D16C16N
Output configurationChannelsON stateOFF state
PNP sourcing, models ending in P1624VDC, ±25%Nominal 0VDC; ±3% tolerance with unspecified reference quantity
NPN sinking, models ending in NNominal 0VDC; ±3% tolerance with unspecified reference quantity24VDC, ±25%

The low-state ±3% notation does not establish an absolute residual-voltage limit because its reference quantity is unspecified. PNP outputs supply loads connected to the 0VDC return; NPN outputs switch loads connected to the positive field supply.

Connection and protectionInputsOutputs
Connection arrangement1-wire
Reverse-circuit protectionProvided
Field-layer isolationOptical isolation
Module error diagnosisProvided

Module error diagnosis is distinct from individual port abnormality detection. The PROFINET software functions are listed separately below.

Mechanical and environmental specifications

ParameterAll models
Installation envelope, depth × width × height80 × 24 × 115mm
Mounting35mm DIN rail, vertical installation
Protection / pollution degreeIP20 / 2
Operating temperature-10°C to +55°C
Storage temperature-20°C to +85°C
Relative humidity5-95%RH, non-condensing

The upright outline for the two PROFINET models gives a 110mm body height, 24mm width and 80mm depth. The 115mm installation height includes the projecting parts beyond the body dimension.

PROFINET supply and terminals

The detailed supply, wiring, indicator, process-data and installation information that follows applies to UV-PN-D16C16P and UV-PN-D16C16N.

ModelSystem feed currentWorking supply
UV-PN-D16C16P135mA24VDC, +20%/−15%
UV-PN-D16C16N115mA
Connection propertyBoth PROFINET models
Terminal technologyPush-in spring terminals; solid conductors can be inserted directly
Power, input and output conductor cross-section0.34-1.5mm²
Conductor size22-16AWG
Strip length8-10mm
Power interface3-position terminal
Rail fixingSlot and latch for 35mm DIN rail
Input signalA terminalB terminalInput signal
Input 00A1B1Input 10
Input 01A2B2Input 11
Input 02A3B3Input 12
Input 03A4B4Input 13
Input 04A5B5Input 14
Input 05A6B6Input 15
Input 06A7B7Input 16
Input 07A8B8Input 17
SS commonA9B9SS common
A10B10

The four SS terminals are internally connected. Connect SS to 0V for PNP input operation, or to +24V for NPN input operation. This is a shared input common; the terminals do not provide independently selectable common voltages for individual channels.

Output signalC terminalD terminalOutput signal
Output 00C1D1Output 10
Output 01C2D2Output 11
Output 02C3D3Output 12
Output 03C4D4Output 13
Output 04C5D5Output 14
Output 05C6D6Output 15
Output 06C7D7Output 16
Output 07C8D8Output 17
Field +24VC9D9Field +24V
Field 0VC10D10Field 0V

Supply the field terminals externally. The labels 00-07 and 10-17 each identify a group of eight channels, separately for inputs and outputs.

Insulated ferruleConductor cross-sectionFerrule length L
E03100.3mm²10mm
E05100.5mm²
E75100.75mm²
E10101.0mm²
E15101.5mm²

PROFINET indicators

IndicatorColour and stateMeaning
PWRGreen onNormal supply
OffNo supply or abnormal supply
RUNGreen onSystem operating normally
OffAbnormal operation
FlashingFactory reset after holding the button for 10 seconds
SYSRed offNo module fault
Red onModule fault; currently indicates a bus fault
ERRRed offNetwork connection normal
Red flashingNetwork connection abnormal
Channel LEDs, 00-07 and 10-17Green on / offCorresponding channel active / inactive

PROFINET process data and software

Data directionByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
Input0DI07DI06DI05DI04DI03DI02DI01DI00
1DI17DI16DI15DI14DI13DI12DI11DI10
Output0DO07DO06DO05DO04DO03DO02DO01DO00
1DO17DO16DO15DO14DO13DO12DO11DO10

Input bits are 1 for an active input and 0 for an inactive input. Output bits are 1 to activate the corresponding output and 0 to deactivate it. An active PNP output is high; an active NPN output is low. Input and output byte offsets belong to separate process images.

Software functionBoth PROFINET models
Fault-stop output stateRetain current value
Input-port abnormality detection and indicationNot provided
Output-port abnormality detection and indicationNot provided
Configurable input and output logic levelsNot supported
Independent channel-enable configurationNot supported
Configurable diagnostic reportingNot supported
Stopped modeFollow the fault-stop state mode and preset value; no further refresh
I/O accessBit, byte and word access

PROFINET environmental and installation details

ParameterSpecification
AltitudeBelow 2000m; 80kPa reference
Overvoltage categoryII
Power-line immunity2kV, IEC 61000-4-4
EMC environmentZone B, IEC 61131-2
VibrationIEC 60068-2-6: 5-8.4Hz at 3.5mm amplitude; 8.4-150Hz at 9.8m/s²; X, Y and Z axes, 100 minutes per axis in ten 10-minute cycles
ShockIEC 60068-2-27: 9.8m/s², 11ms; three shocks in each of six directions across the X, Y and Z axes
Declared conformityCE; supporting certificate number not specified here
Installation clearances10mm between modules; 45mm above and 25mm below

Install vertically in a ventilated enclosure or cabinet, away from equipment that could cause overheating. Disconnect power before fitting or removing the module. Engage the upper rail latch and seat the module on the DIN rail. For removal, disconnect power and signal cables, release the latch with a flat screwdriver and reverse the mounting movement. Check for obstructions if the module resists fitting.

Additional rating information

UL use groupRated currentRated voltageRated cross-section
BNot specifiedNot specifiedNot specified
C
D