URS Slim Single Changeover DC Relays

Description

Slim relay bodies with DC coils

URS relays provide one changeover contact in a slim plug-in body. The five listed models differ in nominal coil voltage, coil resistance and power consumption. These are relay bodies; select the socket separately for the wiring method and control input.

ModelNominal coil voltageCoil resistance, ±10%Coil power
URS105D5VDC145Ω0.18W
URS112D12VDC845Ω0.18W
URS124D24VDC3385Ω0.18W
URS148D48VDC5760Ω0.4W
URS160D60VDC9000Ω0.4W
Coil characteristicAll five models
Pull-in voltage≤80% of nominal coil voltage
Release voltage≥10% of nominal coil voltage
Maximum operating voltage120% of nominal coil voltage
Operate time<15ms
Release time<8ms

Contact and load characteristics

CharacteristicAll models
Contact arrangement1 changeover contact (1CO)
Contact materialSilver tin oxide alloy
Maximum switching voltage277VAC / 30VDC
Maximum switching current10A
Maximum switching power2770VA / 240W
Resistive load rating6A at 277VAC or 30VDC
Motor load rating1/3HP at 277VAC
Minimum switching load24V / 10mA
Contact resistance≤100mΩ, measured at 6VDC and 1A
Electrical life>30,000 operations, 1s ON / 1s OFF, 1800 operations per hour
Mechanical life>10,000,000 operations, 300 cycles per minute, 18,000 operations per hour

Maximum voltage, current and power are separate limits and do not define a simultaneous load point. Apply the stated 6A resistive rating or the motor rating for the actual load.

Insulation, mechanical and environmental data

CharacteristicAll models
Body dimensions28mm × 5mm × 15mm
Weight5g
Insulation resistance1000MΩ at 500VDC
Dielectric withstand between contacts of the same pole1000VAC for 1 minute
Dielectric withstand between coil and contacts5000VAC for 1 minute
Shock resistance10g, half-sine pulse, 11ms
Vibration resistance10-55Hz, 1.5mm double amplitude
Ambient temperature-40°C to +85°C
Ambient humidity35-80%RH

Matching socket inputs

USS screw and push-in sockets are selected by their input circuit as well as by relay fit. A socket with an AC/DC input can use a DC-coil relay; the socket input voltage and the relay coil voltage are separate specifications.

RelaySocket nominal inputScrew socketPush-in socket
URS105D5VDCUSS-1E-5USS-1P-5
URS112D12VDCUSS-1E-5USS-1P-5
URS124D24VDCUSS-1E-5USS-1P-5
URS124D24VAC/DCUSS-1E-1USS-1P-1
URS148D48VAC/DCUSS-1E-2USS-1P-2
URS160D60VAC/DCUSS-1E-2USS-1P-2
URS160D120VAC/DCUSS-1E-3USS-1P-3
URS160D230VAC/DCUSS-1E-4USS-1P-4