URL Two and Four Changeover Contact Relays

Series Part Number

Part Number: URL 4 24 DLT
Explanation:

Relay Series

Contacts

2 - Two changeover contacts, 2CO
4 - Four changeover contacts, 4CO

Coil Voltage

06 - 6V
12 - 12V
24 - 24V
48 - 48V
110 - 110V
220 - 220V
380 - 380V AC only; all other voltages listed for AC and DC, with either contact count

Coil Model Suffix

DLT - DC coil model; 6, 12, 24, 48, 110 or 220V
ALT - AC coil model; 6, 12, 24, 48, 110, 220 or 380V; suffixes retained as complete codes

Description

Plug-in relays with two or four changeover contacts

URL relay bodies provide 2CO or 4CO switching in a transparent housing with a test lever. Choose the contact arrangement and exact coil voltage together: DLT models use DC coils and ALT models use AC coils. The selection tables below cover the available 26 combinations. Relay bodies and complete socket assemblies are separate products.

DC coil selection

Rated coil voltage2CO model4CO modelCoil resistance, ±10%Rated coil power
6V DCURL206DLTURL406DLT40Ω0.9W
12V DCURL212DLTURL412DLT160Ω
24V DCURL224DLTURL424DLT640Ω
48V DCURL248DLTURL448DLT2560Ω
110V DCURL2110DLTURL4110DLT13400Ω
220V DCURL2220DLTURL4220DLT53777Ω

AC coil selection

Rated coil voltage2CO model4CO modelCoil resistance, ±10%Rated coil power
6V ACURL206ALTURL406ALT10.5Ω1.2VA
12V ACURL212ALTURL412ALT42Ω
24V ACURL224ALTURL424ALT168Ω
48V ACURL248ALTURL448ALT672Ω
110V ACURL2110ALTURL4110ALT3529Ω
220V ACURL2220ALTURL4220ALT14116Ω
380V ACURL2380ALTURL4380ALT42116Ω
Coil operating parameterDC modelsAC models
Pull-in voltage≤75% of rated voltage≤80% of rated voltage
Release voltage≥10% of rated voltage≥30% of rated voltage
Maximum operating voltage110% of rated voltage
Operate time<15ms
Release time<10ms

Contact ratings

The maximum voltage, current and switching-capacity limits apply together. A 12A maximum current does not mean that every load can be switched at 12A at the maximum voltage. Select the relay for the actual load and check the matching socket's limits separately.

ParameterSpecification
Contact arrangements2CO or 4CO, according to model
Contact materialAgSnO₂/Cu
Maximum switching voltage240V AC / 28V DC
Maximum switching current12A for 2CO and 4CO versions
Switching capacity2500VA / 300W
Minimum switching load24V / 10mA
Contact resistance≤100mΩ, measured at 6V DC and 1A
Electrical life>100,000 operations; stated condition: 1 second on / 1 second off, 900 operations/hour
Mechanical life>10,000,000 operations; 300 cycles/minute, 18,000 operations/hour

Insulation and environmental specifications

ParameterSpecification
Insulation resistance100MΩ
Dielectric withstand between contacts of the same pole1000V AC for 1 minute
Dielectric withstand between coil and contacts1500V AC for 1 minute
Dielectric withstand between different polesUnspecified
Vibration resistance10-55Hz, 1.5mm double amplitude
Ambient temperature-40°C to 85°C
Ambient humidity45-85%RH
Weight35g

Pin assignments and replacement selection

Use the pin and wiring diagrams in the attachment when checking the socket. The 2CO and 4CO versions have different terminal arrangements; match the contact count, coil supply and pin pattern before replacement.

Function2CO pin4CO pin
First pole NC, 121
First pole COM, 1159
First pole NO, 1435
Second pole NC, 222
Second pole COM, 21610
Second pole NO, 2446
Third pole NC, 32Not applicable3
Third pole COM, 31Not applicable11
Third pole NO, 34Not applicable7
Fourth pole NC, 42Not applicable4
Fourth pole COM, 41Not applicable12
Fourth pole NO, 44Not applicable8
Coil A1713
Coil A2814

The attached specification includes the relay outline, pin layouts, wiring diagrams and complete coil selection tables. Coil voltage identifies the control supply and is separate from the contact switching-voltage limit.