| Part Number: | URL | 4 | 24 | DLT |
|---|---|---|---|---|
| Explanation: |
Relay Series |
Contacts 2 - Two changeover contacts, 2CO |
Coil Voltage 06 - 6V |
Coil Model Suffix DLT - DC coil model; 6, 12, 24, 48, 110 or 220V |
URL relay bodies provide 2CO or 4CO switching in a transparent housing with a test lever. Choose the contact arrangement and exact coil voltage together: DLT models use DC coils and ALT models use AC coils. The selection tables below cover the available 26 combinations. Relay bodies and complete socket assemblies are separate products.
| Rated coil voltage | 2CO model | 4CO model | Coil resistance, ±10% | Rated coil power |
|---|---|---|---|---|
| 6V DC | URL206DLT | URL406DLT | 40Ω | 0.9W |
| 12V DC | URL212DLT | URL412DLT | 160Ω | |
| 24V DC | URL224DLT | URL424DLT | 640Ω | |
| 48V DC | URL248DLT | URL448DLT | 2560Ω | |
| 110V DC | URL2110DLT | URL4110DLT | 13400Ω | |
| 220V DC | URL2220DLT | URL4220DLT | 53777Ω |
| Rated coil voltage | 2CO model | 4CO model | Coil resistance, ±10% | Rated coil power |
|---|---|---|---|---|
| 6V AC | URL206ALT | URL406ALT | 10.5Ω | 1.2VA |
| 12V AC | URL212ALT | URL412ALT | 42Ω | |
| 24V AC | URL224ALT | URL424ALT | 168Ω | |
| 48V AC | URL248ALT | URL448ALT | 672Ω | |
| 110V AC | URL2110ALT | URL4110ALT | 3529Ω | |
| 220V AC | URL2220ALT | URL4220ALT | 14116Ω | |
| 380V AC | URL2380ALT | URL4380ALT | 42116Ω |
| Coil operating parameter | DC models | AC models |
|---|---|---|
| Pull-in voltage | ≤75% of rated voltage | ≤80% of rated voltage |
| Release voltage | ≥10% of rated voltage | ≥30% of rated voltage |
| Maximum operating voltage | 110% of rated voltage | |
| Operate time | <15ms | |
| Release time | <10ms | |
The maximum voltage, current and switching-capacity limits apply together. A 12A maximum current does not mean that every load can be switched at 12A at the maximum voltage. Select the relay for the actual load and check the matching socket's limits separately.
| Parameter | Specification |
|---|---|
| Contact arrangements | 2CO or 4CO, according to model |
| Contact material | AgSnO₂/Cu |
| Maximum switching voltage | 240V AC / 28V DC |
| Maximum switching current | 12A for 2CO and 4CO versions |
| Switching capacity | 2500VA / 300W |
| Minimum switching load | 24V / 10mA |
| Contact resistance | ≤100mΩ, measured at 6V DC and 1A |
| Electrical life | >100,000 operations; stated condition: 1 second on / 1 second off, 900 operations/hour |
| Mechanical life | >10,000,000 operations; 300 cycles/minute, 18,000 operations/hour |
| Parameter | Specification |
|---|---|
| Insulation resistance | 100MΩ |
| Dielectric withstand between contacts of the same pole | 1000V AC for 1 minute |
| Dielectric withstand between coil and contacts | 1500V AC for 1 minute |
| Dielectric withstand between different poles | Unspecified |
| Vibration resistance | 10-55Hz, 1.5mm double amplitude |
| Ambient temperature | -40°C to 85°C |
| Ambient humidity | 45-85%RH |
| Weight | 35g |
Use the pin and wiring diagrams in the attachment when checking the socket. The 2CO and 4CO versions have different terminal arrangements; match the contact count, coil supply and pin pattern before replacement.
| Function | 2CO pin | 4CO pin |
|---|---|---|
| First pole NC, 12 | 1 | |
| First pole COM, 11 | 5 | 9 |
| First pole NO, 14 | 3 | 5 |
| Second pole NC, 22 | 2 | |
| Second pole COM, 21 | 6 | 10 |
| Second pole NO, 24 | 4 | 6 |
| Third pole NC, 32 | Not applicable | 3 |
| Third pole COM, 31 | Not applicable | 11 |
| Third pole NO, 34 | Not applicable | 7 |
| Fourth pole NC, 42 | Not applicable | 4 |
| Fourth pole COM, 41 | Not applicable | 12 |
| Fourth pole NO, 44 | Not applicable | 8 |
| Coil A1 | 7 | 13 |
| Coil A2 | 8 | 14 |
The attached specification includes the relay outline, pin layouts, wiring diagrams and complete coil selection tables. Coil voltage identifies the control supply and is separate from the contact switching-voltage limit.