| Part Number: | URTEL | 4 | 24 | DLT |
|---|---|---|---|---|
| Explanation: |
Connection Family URTEL - URL complete relay set with screw connection; 2CO or 4CO |
Contacts 2 - Two changeover contacts |
Coil Reference 12 - 12V; DLT only |
Supply Version DLT - DC coil version; 12V, 24V, 48V or 110V |
URL relay sets combine a relay and socket with LED indication. Screw connections are available with 2CO or 4CO contacts, while the listed push-in sets have 2CO contacts. Select the actual set code below; CO denotes a changeover contact.
| Rated coil supply | Screw, 2CO | Screw, 4CO | Push-in, 2CO |
|---|---|---|---|
| 12VDC | URTEL212DLT | URTEL412DLT | URTPL212DLT |
| 24VDC | URTEL224DLT | URTEL424DLT | URTPL224DLT |
| 48VDC | URTEL248DLT | URTEL448DLT | URTPL248DLT |
| 110VDC | URTEL2110DLT | URTEL4110DLT | URTPL2110DLT |
| 24VAC | URTEL224ALT | URTEL424ALT | URTPL224ALT |
| 48VAC | URTEL248ALT | URTEL448ALT | URTPL248ALT |
| 110VAC | URTEL2110ALT | URTEL4110ALT | URTPL2110ALT |
| 220VAC | URTEL2230ALT | URTEL4220ALT | URTPL2220ALT |
URTEL2230ALT retains its 230 designation and uses the listed 220VAC coil specification. Its +10%/-5% supply range is 209-242VAC, which includes 230VAC.
| Family | Connection | Contacts | Dimensions, H×L×W | Nominal wire size | Wire range |
|---|---|---|---|---|---|
| URTEL2 | Screw | 2CO | 68.5×28×79mm | 1mm² | 0.5-1.5mm² |
| URTEL4 | 4CO | 68.5×45.2×79mm | 0.5-2.5mm² | ||
| URTPL2 | Push-in | 2CO | 70×26.8×92.5mm | 0.25-2.5mm² |
Supply tolerance is +10%/-5%; coil resistance tolerance is ±10%. Parameters apply to the corresponding supply row in the model table.
| Rated supply | Resistance | Consumption | Pickup voltage | Release voltage |
|---|---|---|---|---|
| 12VDC | 160Ω | 900mW | ≤9V | ≥1.2V |
| 24VDC | 640Ω | ≤18V | ≥2.4V | |
| 48VDC | 2560Ω | ≤36V | ≥4.8V | |
| 110VDC | 13400Ω | ≤82.5V | ≥11V | |
| 24VAC | 168Ω | 1.2VA | ≤19.2V | ≥7.2V |
| 48VAC | 672Ω | ≤38.4V | ≥14.4V | |
| 110VAC | 3529Ω | ≤88V | ≥33V | |
| 220VAC | 14116Ω | ≤176V | ≥66V |
Apply the current, voltage and switching-capacity limits together. A maximum current rating does not permit that current at every voltage. Motor ratings are separate from AC apparent-power and DC power limits.
| Parameter | 2CO sets | 4CO sets |
|---|---|---|
| Maximum switching voltage | 240VAC/28VDC | |
| Maximum switching current | 12A | |
| Switching capacity | 2500VA/300W | |
| Motor load | 1/3HP at 240VAC | 1/6HP at 240VAC |
| Minimum switching load | 24V/10mA | |
| Contact resistance | ≤100mΩ at 6VDC/1A | |
| Contact material | AgSnO₂/Cu | |
| Electrical life | >100,000 operations at 900 operations/hour | |
| Mechanical life | >10,000,000 operations at 300 cycles/minute (18,000 operations/hour) | |
| Pickup / release time | <15ms / <10ms | |
| Parameter | All listed sets |
|---|---|
| Rated insulation voltage | 300V |
| Creepage distance between contacts | ≥5.5mm |
| Overvoltage category / pollution degree | III / 2 |
| Status indication | LED |
| Operating temperature | -40°C to +60°C |
| Storage temperature | -40°C to +85°C |
| Relative humidity | 45-85%RH |