| Part Number: | URE | 2 | 24 | DLT |
|---|---|---|---|---|
| Explanation: |
Series URE - Plug-in relay body |
Contacts 1 - One changeover contact (1CO) |
Coil Voltage 06 - 6V; DLT or ALT |
Supply Version DLT - Listed DC coil version |
URE relays provide one or two changeover contact sets. Choose the exact coil supply and contact arrangement from the model table. Dimensions are 35.2mm × 29mm × 13mm in H × L × W order.
| Rated coil voltage | 1CO model | 2CO model | Coil resistance, ±10% | Rated coil power |
|---|---|---|---|---|
| 6VDC | URE106DLT | URE206DLT | 68Ω | 0.53W |
| 12VDC | URE112DLT | URE212DLT | 272Ω | |
| 24VDC | URE124DLT | URE224DLT | 1087Ω | |
| 48VDC | URE148DLT | URE248DLT | 4347Ω | |
| 110VDC | URE1110DLT | URE2110DLT | 22830Ω | |
| 6VAC | URE106ALT | URE206ALT | 15.8Ω | 0.8VA |
| 12VAC | URE112ALT | URE212ALT | 63Ω | |
| 24VAC | URE124ALT | URE224ALT | 252Ω | |
| 48VAC | URE148ALT | URE248ALT | 1008Ω | |
| 110VAC | URE1110ALT | URE2110ALT | 5294Ω | |
| 220VAC | URE1220ALT | URE2220ALT | 23144Ω |
| Parameter | DC coil | AC coil |
|---|---|---|
| Pickup voltage | ≤75% of rated voltage | ≤80% of rated voltage |
| Release voltage | ≥10% of rated voltage | ≥30% of rated voltage |
| Maximum operating voltage | 110% of rated voltage | |
| Pickup time | <20ms | |
| Release time | <10ms | |
| Parameter | 1CO | 2CO |
|---|---|---|
| Resistive load | 12A at 277VAC or 30VDC | 8A at 277VAC or 30VDC |
| Maximum switching power | 3324VA / 360W | 2216VA / 240W |
| Motor load | 1/2HP at 250VAC | 1/3HP at 250VAC |
| Maximum switching voltage | 277VAC / 30VDC | |
| Maximum switching current | 15A | |
| Minimum switching load | 24V / 10mA | |
| Contact resistance | ≤100mΩ at 6VDC, 1A | |
| Contact material | AgSnO alloy | |
| Electrical life | More than 100000 operations at 900 operations/hour | |
| Mechanical life | More than 10000000 operations at 300 cycles/minute, equivalent to 18000 operations/hour | |
Maximum switching current is a separate limit from the rated resistive load. Apply voltage, current, power and load-type limits together.
| Parameter | Specification |
|---|---|
| Insulation resistance | 1000MΩ |
| Dielectric withstand, between contacts of the same pole | 1000VAC for 1 minute |
| Dielectric withstand, between poles on 2CO models | 1000VAC for 1 minute |
| Dielectric withstand, coil to contacts | 5000VAC for 1 minute |
| Impact resistance | 10g, half-sine pulse of 11ms |
| Vibration resistance | 10-55Hz, double amplitude of 1.5mm |
| Ambient temperature | -40°C to +85°C |
| Ambient humidity | 45-85%RH |
| Dimensions, H × L × W | 35.2mm × 29mm × 13mm |
| Weight | 25g |