| Part Number: | ULO | - | TB338 | - | UIK 16 BU |
|---|---|---|---|---|---|
| Explanation: |
Brand |
Product Code TB338 - UIK16 drawing reference |
Terminal and Color UIK 16 BU - Blue, 16mm² nominal cross-section; TB338 only |
UIK16 and UIK35 provide one row, one level, two screw connections and one electrical potential per terminal. Select the nominal conductor section, current rating and mounting dimensions for the circuit. Both models mount on U35/7.5 DIN rail and are available in gray or blue.
| Property | UIK16 | UIK35 |
|---|---|---|
| Model | ULO-TB338-UIK16 | ULO-TB339-UIK35 |
| Additional model reference | — | ULO-TB140-UIK35 |
| Nominal cross section | 16mm² | 35mm² |
| Nominal current | 76A | 125A |
| Maximum load current | 101A | 125A |
| Rated voltage, category III / pollution degree 3 | 400V | 800V |
| Rated impulse voltage, category III / pollution degree 3 | 6kV | 8kV |
| Voltage and impulse ratings, III / 2 and II / 2 | Not specified | |
| Connection property | UIK16 | UIK35 |
|---|---|---|
| Solid conductor | 2.5–25mm²; 12–4AWG | 0.75–35mm²; 18–2AWG |
| Flexible conductor | 4–16mm²; 10–6AWG | 0.75–35mm²; 18–2AWG |
| Flexible conductor with ferrule | 1.5–16mm² | 0.75–35mm² |
| Screw / tightening torque | M4 / 1.2N·m | |
| Stripping length | 11mm | 16mm |
| Model | Use group B | Use group C | Use group D | Conductor range |
|---|---|---|---|---|
| UIK16 | 85A / 300V | 5A / 600V | 12–4AWG | |
| UIK35 | 115A / 600V | Not specified | 18–2AWG | |
| Property | Both models |
|---|---|
| Insulation | PA66; material group I |
| Flammability | UL94V-0 |
| Contacts | Tin-plated copper alloy |
| Protection | IP20 |
| Operating temperature | -40°C to +105°C |
| Housing colors | Gray; blue with BU suffix |
| Dimension | UIK16 | UIK35 |
|---|---|---|
| Width × length × overall height | 12.05×42.52×45.9mm | 15×54.93×49.8mm |
| Top to rail-seat datum | 39.6mm | 43.5mm |
| Rail centerline to right end | 21.25mm | 33.65mm |
| Half rail width | 17.5mm | |


| Dimension range | Total pitch tolerance | Nominal dimension tolerance |
|---|---|---|
| 0–30mm | ±0.18mm | ±0.20mm |
| >30–53mm | ±0.20mm | ±0.25mm |
| >53–70mm | ±0.25mm | ±0.30mm |
| >70–90mm | ±0.30mm | ±0.35mm |
| >90–115mm | ±0.35mm | ±0.44mm |
| >115–150mm | ±0.44mm | ±0.55mm |
| >150–200mm | ±0.55mm | ±0.70mm |
| >200–250mm | ±0.70mm | ±0.80mm |
| >250–320mm | ±0.75mm | ±0.90mm |
| Geometric tolerance | Applicable dimension | Value |
|---|---|---|
| Perpendicularity | Up to 10mm | 0.2mm |
| Over 10mm | 0.3mm | |
| Symmetry | General | 0.3mm |
| Straightness | Up to 100mm | 0.2mm |
| Parallelism | 100–150mm | 0.3mm |
| Over 150mm | 0.5mm |
| Accessory | UIK16 reference | UIK35 reference |
|---|---|---|
| End cover | D-UK4/10 | D-UK16 |
| Partition plate | ATP-UK | Not specified |
| Grouping partition plate | TS-K | |
| Fixed bridge | FBIXX-12 | FBIXX-15 |
| Pluggable bridge | EBXX-12 | EBXX-15 |
| Marker strip | ZB12 | ZB15 |
| End clamp | E/UK | |
| DIN rail | U35/7.5 | |