| Part Number: | UH | - | CL | - | D000 | 32 | N |
|---|---|---|---|---|---|---|---|
| Explanation: |
Platform UH - Horizontal integrated I/O module |
Protocol PN - PROFINET |
Output Model Prefix D000 - Fixed prefix of the digital-output models listed in this series |
Output Channels 32 - 32 outputs; fixed channel count in this series |
Output Polarity P - PNP sourcing outputs |
UH horizontal integrated modules combine a communication interface and 32 digital outputs in one DIN rail unit. Select the protocol and output polarity together. Each model below supports its named protocol; CC-Link and CC-Link IE Field Basic use different network interfaces.
| Protocol | PNP sourcing output | NPN sinking output | Output channels |
|---|---|---|---|
| PROFINET | UH-PN-D00032P | UH-PN-D00032N | 32 |
| EtherCAT | UH-EC-D00032P | UH-EC-D00032N | |
| EtherNet/IP | UH-EIP-D00032P | UH-EIP-D00032N | |
| CC-Link IE Field Basic | UH-CB-D00032P | UH-CB-D00032N | |
| Modbus TCP | UH-MT-D00032P | UH-MT-D00032N | |
| CC-Link | UH-CL-D00032P | UH-CL-D00032N |
| Models | Transmission rate | Communication distance | Interface data capacity | Addressing |
|---|---|---|---|---|
| UH-PN models | 10/100Mbps, full duplex | ≤100m | 1024 bytes maximum | PROFINET specification |
| UH-EC models | 100Mbps | EtherCAT specification | ||
| UH-EIP models | EtherNet/IP specification | |||
| UH-CB models | RX and RY: 64 bits each; RWr and RWw: 32 words each, per logical station | Not specified here | ||
| UH-MT models | 1024 bytes maximum | Modbus TCP specification | ||
| UH-CL models | Five selectable rates below | Rate-dependent, below | Not specified here | Not specified here |
Interface capacity is separate from the physical output count. The PROFINET output process image contains four bytes for its 32 channels.
| CC-Link transmission rate | Maximum communication distance |
|---|---|
| 10Mbps | 100m |
| 5Mbps | 160m |
| 2.5Mbps | 400m |
| 625kbps | 900m |
| 156kbps | 1200m |
| Property | Specification | Scope |
|---|---|---|
| Station type | Remote I/O station | All models |
| Station occupancy | 1 station | |
| Topology | Bus topology | |
| Network isolation | Electrical isolation | |
| Network cable | Ethernet CAT5 | PN, EC, EIP, CB and MT models |
| CC-Link special cable: three-core shielded stranded cable | CL models | |
| Periodic-data / node-search ports | 61450 / 61451 | CB models |
| Alarms | Diagnostic alarms and process alarms | PN models |
| Output polarity | ON state | OFF state |
|---|---|---|
| PNP, model suffix P | 24VDC, ±25% | Nominal 0VDC; ±3% tolerance with unspecified reference quantity |
| NPN, model suffix N | Nominal 0VDC; ±3% tolerance with unspecified reference quantity | 24VDC, ±25% |
The low-state percentage does not establish an absolute residual-voltage limit. PNP outputs drive loads returning to field 0V; NPN outputs switch loads connected to the positive field supply.
| Property | All models |
|---|---|
| Connection arrangement | 1-wire |
| Reverse-circuit protection | Provided |
| Output isolation | Optical isolation from the field layer |
| Module error diagnosis | Provided; individual port functions are specified separately for the PN models below |
| Parameter | All models |
|---|---|
| Housing dimensions | 43.7 × 100 × 100mm |
| Mounting | 35mm DIN rail |
| Protection rating | IP20 |
| Pollution degree | 2 |
| Operating temperature | -10°C to +55°C |
| Storage temperature | -20°C to +85°C |
| Relative humidity | 5-95%RH, non-condensing |
The housing has a 100 × 100mm face and a nominal 43.7mm thickness. The PROFINET mounting outline rounds the thickness to 44mm.
The following terminal, indicator, process-data and installation details apply to UH-PN-D00032P and UH-PN-D00032N.
| Property | Both PROFINET models |
|---|---|
| Working supply | 24VDC, +20%/−15% |
| System feed current | <150mA |
| Terminal technology | Push-in spring terminals; solid conductors can be inserted directly |
| Power-terminal conductor range | 0.5-1.5mm²; separately stated wire range 22-16AWG |
| Power-terminal strip length | 8-9mm |
| Output-terminal conductor range | 0.34-1.5mm²; 22-16AWG |
| Output-terminal strip length | 8-10mm |
| Power connector markings | 24V, 0V and PE |
| Bus interface | 2 × RJ45 |
| Resistive-load marking | 24VDC / 0.5A; aggregate simultaneous-output limit not specified here |
The two nominal conductor systems are stated separately; their endpoints should not be treated as exact metric conversions.
The first two terminal-group letters differ between the PNP and NPN assignment tables. Use the column for the exact model. Signal labels 00-07, 10-17, 20-27 and 30-37 each identify eight channels.
| Output signal | UH-PN-D00032P terminal | UH-PN-D00032N terminal | Output signal | UH-PN-D00032P terminal | UH-PN-D00032N terminal |
|---|---|---|---|---|---|
| Output 00 | B1 | A1 | Output 10 | A1 | B1 |
| Output 01 | B2 | A2 | Output 11 | A2 | B2 |
| Output 02 | B3 | A3 | Output 12 | A3 | B3 |
| Output 03 | B4 | A4 | Output 13 | A4 | B4 |
| Output 04 | B5 | A5 | Output 14 | A5 | B5 |
| Output 05 | B6 | A6 | Output 15 | A6 | B6 |
| Output 06 | B7 | A7 | Output 16 | A7 | B7 |
| Output 07 | B8 | A8 | Output 17 | A8 | B8 |
| Field +24V | B9 | A9 | Field +24V | A9 | B9 |
| Field 0V | B10 | A10 | Field 0V | A10 | B10 |
| Output signal | Terminal, both PN models | Terminal, both PN models | Output signal |
|---|---|---|---|
| Output 20 | C1 | D1 | Output 30 |
| Output 21 | C2 | D2 | Output 31 |
| Output 22 | C3 | D3 | Output 32 |
| Output 23 | C4 | D4 | Output 33 |
| Output 24 | C5 | D5 | Output 34 |
| Output 25 | C6 | D6 | Output 35 |
| Output 26 | C7 | D7 | Output 36 |
| Output 27 | C8 | D8 | Output 37 |
| Field +24V | C9 | D9 | Field +24V |
| Field 0V | C10 | D10 | Field 0V |
Supply the field terminals externally: Field +24V connects to positive 24VDC and Field 0V to its return.
| Insulated ferrule | Conductor cross-section | Ferrule length L |
|---|---|---|
| E0310 | 0.3mm² | 10mm |
| E0510 | 0.5mm² | |
| E7510 | 0.75mm² | |
| E1010 | 1.0mm² | |
| E1510 | 1.5mm² |
| Indicator | Colour and state | Meaning |
|---|---|---|
| PWR | Green on | Normal supply |
| Off | No supply or abnormal supply | |
| RUN | Green on | System operating normally |
| Off | Abnormal operation | |
| PORT1 | Red off | No communication data at port 1 |
| Red flashing | Communication data at port 1 | |
| PORT2 | Red off | No communication data at port 2 |
| Red flashing | Communication data at port 2 | |
| Output channels 00-07, 10-17, 20-27 and 30-37 | Green on / off | Corresponding output active / inactive |
| Output byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | DO07 | DO06 | DO05 | DO04 | DO03 | DO02 | DO01 | DO00 |
| 1 | DO17 | DO16 | DO15 | DO14 | DO13 | DO12 | DO11 | DO10 |
| 2 | DO27 | DO26 | DO25 | DO24 | DO23 | DO22 | DO21 | DO20 |
| 3 | DO37 | DO36 | DO35 | DO34 | DO33 | DO32 | DO31 | DO30 |
A bit value of 1 activates its output, at a high electrical level on UH-PN-D00032P or a low level on UH-PN-D00032N. A value of 0 deactivates the output.
| Software function | Both PROFINET models |
|---|---|
| Fault-stop output state | Retain current value |
| Output-port abnormality detection and indication | Not provided |
| Configurable output logic level | Not supported |
| Independent channel-enable configuration | Not supported |
| Configurable diagnostic reporting | Not supported |
| Stopped mode | Follow the fault-stop state mode and preset value; no further refresh |
| I/O access | Bit, byte and word access |
| Parameter | Specification |
|---|---|
| Altitude | Below 2000m; 80kPa reference |
| Overvoltage category | II |
| Power-line immunity | 2kV, IEC 61000-4-4 |
| EMC environment | Zone B, IEC 61131-2 |
| Vibration | IEC 60068-2-6: 5-8.4Hz at 3.5mm amplitude; 8.4-150Hz at 9.8m/s²; X, Y and Z axes, 100 minutes per axis in ten 10-minute cycles |
| Shock | IEC 60068-2-27: 9.8m/s², 11ms; three shocks in each of six directions across the X, Y and Z axes |
| Declared conformity | CE; supporting certificate number not specified here |
| Adjacent-module clearance | 10mm minimum |
Install with the 100 × 100mm face upright on the DIN rail in a ventilated cabinet or enclosure. Keep clear of equipment that could cause overheating. Disconnect power before fitting or removal. Engage the upper rail latch and seat the module. For removal, disconnect power and signal cables, release the latch with a flat screwdriver and reverse the mounting movement. Check for obstructions if the module resists fitting.
| UL use group | Rated current | Rated voltage | Rated cross-section |
|---|---|---|---|
| B | Not specified | Not specified | Not specified |
| C | |||
| D |