UF20 Thermocouple Input Modules

Description

Thermocouple module selection

Choose UF20-4TC for four thermocouple inputs or UF20-8TC for eight. Both models support K, J, T, E, N, S, R, B and C sensors, two-wire connections and internal or external cold junction compensation.

ModelChannelsProcess dataSystem feed current
UF20-4TC48 bytes<70mA
UF20-8TC816 bytes<100mA

Measurement and signal handling

CharacteristicBoth models
Sensor categoryThermocouple
Sensor typesK, J, T, E, N, S, R, B, C
Sensor wiringTwo-wire
Cold junction compensationInternal and external; accuracy ≤3K
Resolution16 bits; 0.1°C per count
Precision±0.5%
Temperature coefficient≤50ppm/K
Module measuring range-100°C to +2320°C
Interference suppression frequencies10Hz, 50Hz, 60Hz and 400Hz
Reverse protectionSupported
Isolation methodMagnetic isolation
Fault diagnosticsSupported
Diagnostic conditionsSensor disconnection and parameter assignment errors

The overall module measuring range does not apply in full to every thermocouple type. Select the sensor and its usable temperature range for the measurement required.

Power, wiring and installation

CharacteristicBoth models
Operating voltage24V DC, +20%/-15%
Connection methodPush-in terminal blocks
Conductor cross-section0.34-1.5mm²
Conductor sizeAWG22-AWG16
Stripping length8-10mm
Height × width × depth75mm × 12mm × 105mm
Mounting35mm DIN rail
Ingress protectionIP20
Operating temperature-10°C to +55°C
Storage temperature-20°C to +85°C
Relative humidity5-95%RH, non-condensing