Four RTD measurement channels
The UF20-4RTD accepts four resistance temperature detector inputs and transfers eight bytes of process data. It supports two-, three- and four-wire sensor connections, magnetic isolation and individual upper/lower process alarms for each channel.
Temperature measurement and diagnostics
| Characteristic | UF20-4RTD |
|---|
| Sensor category | RTD, resistance temperature detector |
|---|
| Sensor types | PT100, PT200, PT500, PT1000 and Ni120 |
|---|
| Channels | 4 |
|---|
| Process data | 8 bytes |
|---|
| Sensor wiring | Two-, three- or four-wire |
|---|
| Resolution | 16 bits; 0.1°C per count |
|---|
| Precision | ±0.3% |
|---|
| Module measuring range | -200°C to +850°C |
|---|
| Isolation method | Magnetic isolation |
|---|
| Fault diagnostics | Supported |
|---|
| Diagnostic conditions | Sensor disconnection and parameter assignment errors |
|---|
| Process alarms | Upper and lower limits for each channel |
|---|
The module measuring range is an overall limit; the usable temperature range also depends on the selected RTD type and sensor.
Power and terminal connections
| Characteristic | Specification |
|---|
| Operating voltage | 24V DC, +20%/-15% |
|---|
| System feed current | <100mA |
|---|
| Connection method | Push-in terminal blocks |
|---|
| Conductor cross-section | 0.34-1.5mm² |
|---|
| Conductor size | AWG22-AWG16 |
|---|
| Stripping length | 8-10mm |
|---|
Installation and environment
| Characteristic | Specification |
|---|
| Height × width × depth | 75mm × 12mm × 105mm |
|---|
| Mounting | 35mm DIN rail |
|---|
| Ingress protection | IP20 |
|---|
| Operating temperature | -10°C to +55°C |
|---|
| Storage temperature | -20°C to +85°C |
|---|
| Relative humidity | 5-95%RH, non-condensing |
|---|