Digital output module selection
UE20 digital output modules control 24VDC loads through NPN sinking or PNP sourcing outputs. Choose the output polarity and channel count for the connected actuators, relays, contactors or solenoid valves. Each module uses screwless spring terminals and occupies 12mm on a 35mm DIN rail. Select a coupler and expansion arrangement for the UE20 platform.
| Model | Channels | Output type | Active electrical level | Process data | Bus current at 5VDC |
| UE20-8DO-N | 8 | NPN sinking | Low | 1 byte | 66mA typical |
| UE20-8DO-P | PNP sourcing | High |
| UE20-16DO-N | 16 | NPN sinking | Low | 2 bytes | 106mA typical |
| UE20-16DO-P | PNP sourcing | High |
Supply and signal states
| Parameter | All four models |
| Internal bus input | 5VDC nominal; 4.75-5.25VDC |
| Working-voltage specification | 24VDC, +20%/−15% |
| Output-circuit voltage grade | 24VDC ±10%; 21.6-26.4VDC |
| System-side electrical isolation | 500VAC |
| Isolation method | Optical isolation |
| Reverse-polarity protection | Supported |
| Output protection | Short-circuit and overcurrent protection |
| Module fault diagnosis | Provided; individual output-channel diagnostic functions are listed separately below |
| Output type | Inactive state, 0/OFF | Active state, 1/ON |
| NPN: UE20-8DO-N and UE20-16DO-N | 24VDC, ±25% | Nominal 0VDC; ±3% tolerance with unspecified reference quantity |
| PNP: UE20-8DO-P and UE20-16DO-P | Nominal 0VDC; ±3% tolerance with unspecified reference quantity | 24VDC, ±25% |
The percentage reference for the low-level ±3% tolerance is unspecified, so it does not establish an absolute low-level voltage limit. Signal-state voltage, working supply voltage and output-circuit voltage grade describe separate conditions.
Output load limits
Apply both the per-channel and per-module limits. The 16-channel NPN and PNP models have different total resistive and inductive load ratings.
| Models | Load type | Per-channel limit | Per-module limit | Switching frequency |
| UE20-8DO-N and UE20-8DO-P | Resistive | 0.5A | 2A | 100Hz |
| Inductive | 7.2W | 7.2W | 0.5Hz |
| Lamp | 5W | 5W | 10Hz |
| UE20-16DO-N | Resistive | 0.5A | 4A | 100Hz |
| Inductive | 7.2W | 24W | 0.5Hz |
| Lamp | 5W | 18W | 10Hz |
| UE20-16DO-P | Resistive | 0.5A | 2A | 100Hz |
| Inductive | 7.2W | 12W | 0.5Hz |
| Lamp | 5W | 18W | 10Hz |
| Models | Operation at 55°C | All outputs active |
| Both 8-channel models | 50% output derating; combined simultaneously active output current no more than 0.5A | Apply a 10°C temperature derating |
| Both 16-channel models | 50% output derating; combined simultaneously active output current no more than 1A |
Connections and mechanical installation
| Models | Conductor cross-section | Separate AWG specification | Strip length |
| UE20-8DO-N and UE20-8DO-P | 0.2-2.5mm² | 28-14AWG | 8-9mm |
| UE20-16DO-N and UE20-16DO-P | 0.2-1.5mm² | 28-16AWG |
The metric and AWG entries are separate declared ranges, not point-for-point conversions. Spring terminals permit direct insertion of solid conductors.
| Property | All models |
| Connection arrangement | 1-line, screwless spring terminals |
| Height × width × depth | 100 × 12 × 68mm |
| Mounting | 35mm DIN rail |
| Protection rating | IP20 |
| Hardware feature | Function |
| Grounding spring contact | Ground connection through the 35mm DIN rail |
| Field-power contacts | Two metal clips supply the field loads |
| Latch | Secures the module to the DIN rail |
| Signal terminals | Connect the output signals |
| Internal bus connection | Carries bus power and signals |
| Channel indicators | Show the state of each output |
| Module label | Identifies the I/O module function |
Terminal assignment and load wiring
For NPN models, connect each load between the positive field supply and its output terminal. For PNP models, connect each load between its output terminal and the 0VDC return. Terminals are numbered from 1, while process-data channel numbers start at 0.
| Applies to | Left signal | Left terminal | Right terminal | Right signal |
| All models | Output 1 | 1 | 2 | Output 2 |
| Output 3 | 3 | 4 | Output 4 |
| Output 5 | 5 | 6 | Output 6 |
| Output 7 | 7 | 8 | Output 8 |
| 16-channel models only | Output 9 | 9 | 10 | Output 10 |
| Output 11 | 11 | 12 | Output 12 |
| Output 13 | 13 | 14 | Output 14 |
| Output 15 | 15 | 16 | Output 16 |
| Insulated ferrule | Conductor cross-section | Ferrule length L |
| E0310 | 0.3mm² | 10mm |
| E0510 | 0.5mm² |
| E7510 | 0.75mm² |
| E1010 | 1.0mm² |
| E1510 | 1.5mm² |
Indicators and process data
| Models | Indicator labels | Colour and state | Meaning |
| 8-channel models | 1-8 | Green on / off | Corresponding output active / inactive |
| 16-channel models | 1-16 |
| Output data | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
| Byte 0, all models | Channel 7 | Channel 6 | Channel 5 | Channel 4 | Channel 3 | Channel 2 | Channel 1 | Channel 0 |
| Byte 1, 16-channel models only | Channel 15 | Channel 14 | Channel 13 | Channel 12 | Channel 11 | Channel 10 | Channel 9 | Channel 8 |
Bit value 1 activates the corresponding output: low electrical level for NPN or high electrical level for PNP. Bit value 0 makes the output inactive.
| Software function | Behaviour |
| Fault-stop output state | Retain the current value |
| Output-port abnormality detection and indication | Not provided |
| Configurable output logic level | Not supported |
| Independent channel-enable configuration | Not supported |
| Configurable diagnostic reporting | Not supported |
| Stopped mode | Follow the fault-stop state mode and preset value; no further refresh |
| I/O mapping access | Bit, byte and word access |
Environment and immunity
| Parameter | All models |
| Operating temperature | -20°C to +60°C, subject to output derating |
| Storage temperature | -20°C to +60°C |
| Operating humidity | <95%RH, non-condensing |
| Storage humidity | <90%RH, non-condensing |
| Atmosphere | No corrosive gases |
| Altitude | Below 2000m; 80kPa reference |
| Pollution degree | 2 |
| Overvoltage category | II |
| Power-line immunity | 2kV, IEC 61000-4-4 |
| EMC environment | Zone B, IEC 61131-2 |
| Vibration | IEC 60068-2-6: 5-8.4Hz at 3.5mm amplitude; 8.4-150Hz at 9.8m/s²; X, Y and Z axes, 100 minutes per axis in ten 10-minute cycles |
| Shock | IEC 60068-2-27: 9.8m/s², 11ms; three shocks in each of six directions across the X, Y and Z axes |
Additional rating information
| UL use group | Rated current | Rated voltage | Rated cross-section |
| B | Not specified | Not specified | Not specified |
| C |
| D |