Modbus RTU master communication
The UE20-1MCOM-485/232 provides one serial communication channel with RS485 or RS232 interfaces. It operates as a Modbus RTU master station and supports synchronization messages and communication timeout detection.
Serial interface and baud rates
| Characteristic | UE20-1MCOM-485/232 |
|---|
| Communication channels | 1 |
|---|
| Physical interface | RS485 or RS232 |
|---|
| Protocol role | Modbus RTU master |
|---|
| Maximum RS485 network nodes | 32 |
|---|
| Selectable baud rates | 1200, 2400, 4800, 9600, 14400, 19200, 38400, 56000, 57600 and 115200baud |
|---|
| Synchronization messages | Supported |
|---|
| Communication timeout detection | Supported |
|---|
Choose the interface and baud rate to match the connected equipment. The 32-node network limit applies to RS485 operation; use RS232 for a point-to-point connection.
Supply and installation
| Characteristic | Specification |
|---|
| Operating voltage | 5V DC, ±10% |
|---|
| System supply current | 76mA |
|---|
| Connection method | Spring terminal blocks |
|---|
| Height × width × depth | 100mm × 12mm × 68mm |
|---|
| Mounting | 35mm DIN rail |
|---|
| Ingress protection | IP20 |
|---|
Environmental conditions
| Characteristic | Specification |
|---|
| Operating temperature | -10°C to +55°C |
|---|
| Storage temperature | -20°C to +85°C |
|---|
| Relative humidity | 5-95%RH, non-condensing |
|---|