| Part Number: | ULO | - | TD2.5 | / | 8.4 | - | 2x04 | P | - | 1 | 000A |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Explanation: |
Brand |
Model TD2.5 - 2.5mm² terminal size; 7.0mm or 8.4mm pitch |
Pitch 7.0 - 7.0mm; TD2.5 |
Paired Positions 2x04–2x16 - 4 to 16 longitudinal positions, each with paired screw terminals; retain the two-digit position count |
Position Suffix |
Colour 1 - Grey |
Customer Requirements 000A - Standard suffix shown in the TD ordering diagrams |
TD terminal blocks use screw connections in a single bank of 4–16 positions. Each position has paired screw terminals, expressed as 2×(04–16)P in the ordering designation. Select the complete model by pitch, conductor size and mounting dimensions. A covered version with solder pins is also shown for TD2.5/8.4; its pin layout must be specified with that configuration.
| Model | Pitch | Positions | Paired terminal designation | Rated current | Rated voltage |
|---|---|---|---|---|---|
| TD2.5/7.0 | 7mm | 4–16 | 2×(04–16)P | 15A | 400V |
| TD2.5/8.4 | 8.4mm | 660V | |||
| TD4/10.0 | 10mm | 25A | 400/690V |
| Model | IEC overvoltage category | Pollution degree | Rated impulse voltage | Rated voltage | Rated current |
|---|---|---|---|---|---|
| TD2.5/7.0 | III | 2 | 5kV | 400V | 15A |
| TD2.5/8.4 | 6kV | 660V | |||
| TD4/10.0 | 5kV | 400/690V | 25A |
The 400/690V designation is retained for TD4/10.0 without assigning an unstated circuit arrangement. UL use-group ratings are listed separately.
| Model | UL use group | Rated current | Rated voltage | Wire range |
|---|---|---|---|---|
| TD2.5/7.0 | B | 16A | 300V | 18–14AWG |
| TD2.5/8.4 | ||||
| TD4/10.0 | Not specified | |||
| Parameter | TD2.5/7.0 | TD2.5/8.4 | TD4/10.0 |
|---|---|---|---|
| Connection | Screw connection | ||
| Solid conductor | 0.75–2.5mm² | 2.5–4mm² | |
| Flexible conductor | 0.75–2.5mm² | 2.5–4mm² | |
| Flexible conductor with ferrule | 0.75–2.5mm² | 2.5–4mm² | |
| Terminal screw | M3 | M4 | |
| Tightening torque | 0.5N·m | 1.2N·m | |
| Wire stripping length | 5–7mm | ||
| Operating temperature | -40°C to +130°C | ||
| Protection rating | IP20 | ||
| Separate mounting screw and torque | Not specified | ||
| Component or property | Specification |
|---|---|
| Housing | PC |
| Insulation material group | I |
| Flammability | UL94V-0 |
| Short and long conductors | Tin-plated brass |
| Fixed conductor | Nickel-plated brass |
| Screws and nuts | Zinc-plated steel; M3 for TD2.5 models and M4 for TD4/10.0 |
Specify the model, paired position count, colour and customer requirement suffix. For example, TD2.5/8.4 uses the model segment TD2.5/8.4 followed by 2×XXP, where XX is 04–16. The customer requirement suffix is 00A for the standard designation.
| Ordering field | Selection |
|---|---|
| Model | TD2.5/7.0, TD2.5/8.4 or TD4/10.0 |
| Paired positions | 2×04P through 2×16P |
| Colour code | 1: Grey; 2: Blue; 3: Black; 4: Green; 5: Orange; 6: Red; 7: Transparent; 8: Yellow; 9: White |
| Customer requirements | 00A standard designation; state any required configuration explicitly |
Dimensions below are in millimetres. N is the number of positions from 4 to 16 and corresponds to P in the dimension formulas. Dimension lines refer to their individual drawing datums.
| Model | Overall length | Mounting centre span | Inner longitudinal span | Overall width | Overall height |
|---|---|---|---|---|---|
| TD2.5/7.0 | 7×(N−1)+21.70 | 7×(N−1)+14.90 | 7×(N−1)+8.10 | 29.10 | 32.50 |
| TD2.5/8.4 | 8.4×(N−1)+23.80 | 8.4×(N−1)+17.00 | 8.4×(N−1)+10.20 | 31.50 | 36.50 |
| TD4/10.0 | 10×(N−1)+24.30 | 10×(N−1)+18.00 | 10×(N−1)+10.30 | 32.00 | 41.25 |



Apply the following tolerances where a dimension has no individual tolerance.
| Dimension range | Total pitch tolerance | Nominal dimension tolerance |
|---|---|---|
| Over 0mm to 30mm | ±0.18mm | ±0.20mm |
| Over 30mm to 53mm | ±0.20mm | ±0.25mm |
| Over 53mm to 70mm | ±0.25mm | ±0.30mm |
| Over 70mm to 90mm | ±0.30mm | ±0.35mm |
| Over 90mm to 115mm | ±0.35mm | ±0.44mm |
| Over 115mm to 150mm | ±0.44mm | ±0.55mm |
| Over 150mm to 200mm | ±0.55mm | ±0.70mm |
| Over 200mm to 250mm | ±0.70mm | ±0.80mm |
| Over 250mm to 320mm | ±0.75mm | ±0.90mm |
| Geometric characteristic | Applicable dimension | Tolerance |
|---|---|---|
| Perpendicularity | 0–10mm | 0.2mm |
| Over 10mm | 0.3mm | |
| Symmetry | All | 0.3mm |
| Straightness | Over 0mm to 100mm | 0.2mm |
| Parallelism | Over 100mm to 150mm | 0.3mm |
| Over 150mm | 0.5mm |
Individual drawings are attached for TD2.5/7.0, TD2.5/8.4 and TD4/10.0. Use the drawing matching the selected model for its outline, electrical values, materials and ordering designation.