TBBZ High Voltage Automatic Compensation Assemblies

Description

Automatic compensation on 6kV and 10kV feeders

TBBZ assemblies provide automatically switched high-voltage shunt capacitor compensation on overhead distribution circuits. Applications include 6kV and 10kV feeders, small terminal substations and local compensation of high-voltage motors. The integrated assembly includes capacitor units, a capacitor-duty vacuum contactor, drop-out fuses, voltage and current transformers, zinc-oxide arresters and an automatic compensation controller.

System ratings and service limits

ParameterSpecification
Rated system voltage6kV or 10kV
Maximum operating voltage6.6kV or 11kV respectively
Frequency50Hz
Permissible steady overvoltage1.1 times rated voltage
Permissible steady overcurrent1.3 times rated current
Capacitance deviation0 to +5%
DischargeEach capacitor group below 50V within 10 minutes after disconnection
Altitude≤1000m
Ambient temperature-40°C to +45°C
Wind speed≤35m/s
Seismic intensity≤8
Solar irradiance≤0.1W/cm²
External insulation creepage≥2.5cm/kV
Installation inclination≤5°
EnvironmentNo harmful gases or vapour and no conductive or explosive dust; site harmonics must satisfy the applicable system requirements
Reference standardsJB/T7111-1993; DL/T604-1996

10kV model configurations

System voltage and capacitor-group voltage are separate selection fields. Retain both when specifying a model, because the same TBBZ output designation is used in different voltage configurations. For U/√3 capacitor configurations, the capacitance column represents the phase capacitor value; use it with the matching connection and capacitor voltage.

No.ModelSystem voltage (kV)Capacitor-group voltage (kV)Rated output (kvar)Rated current (A)Capacitance (µF)
1TBBZ-1001010.51005.52.87
2TBBZ-200200115.77
3TBBZ-30010.5/√330016.58.66
4TBBZ-36036019.810.4
5TBBZ-45045024.712.99
6TBBZ-6006003317.32
7TBBZ-90090049.425.98
8TBBZ-1200120065.934.65

6kV model configurations

No.ModelSystem voltage (kV)Capacitor-group voltage (kV)Rated output (kvar)Rated current (A)Capacitance (µF)
9TBBZ-10066.31009.28.02
10TBBZ-20020018.316.04
11TBBZ-30030027.524.06
12TBBZ-3603603328.87
13TBBZ-4506.3/√345041.236.09
14TBBZ-60060054.948.12
15TBBZ-90090082.472.18
16TBBZ-1200120011096.24

Protection functions and settings

Protection options include short circuit, overcurrent, overvoltage, undervoltage, voltage loss and phase failure. Capacitor closing is inhibited during the fixed 10-minute discharge interval. Protection thresholds and delays can otherwise be selected for the installation.

ProtectionSetting or actionDelay
Main-circuit phase-to-phase short circuitDrop-out fuse clears the faulted phase; vacuum contactor trips0.2-0.5s contactor delay
Capacitor phase-to-neutral short circuit3 times rated current
Capacitor-bank overcurrent1.4-1.5 times rated current5s
Overvoltage1.1-1.3 times rated voltage20-30s
Undervoltage0.6 times rated voltage0.2-0.5s
Voltage lossTrip on loss of supply voltage
Phase failurePhase-loss trip, selectable—
Lightning overvoltageZinc-oxide arrester—
Switching overvoltageCapacitor-duty zinc-oxide arrester—

Capacity allocation and feeder position references

The following analytical reference gives the share of total compensation assigned to the substation and feeder, with a position parameter expressed as a fraction of main-feeder length. Final selection depends on the actual load distribution, site access, environment and maintenance arrangements; these idealized loss reductions are planning values.

Reactive load distributionFeeder capacitor groupsShare of total compensationPosition parameterCalculated line-loss reduction
SubstationFeeder
Uniform11/32/32/388.90%
21/54/52/5 and 4/596%
Increasing along the feeder10.20.80.77593%
Decreasing along the feeder10.3740.6260.44286.40%
Isosceles distribution along the feeder20.2040.7960.55491.70%

Configuration and installation

High-voltage automatic compensation equipment configuration fields
Equipment, contactor, voltage, output and controller configuration fields.
Pole-mounted high-voltage compensation assembly installation dimensions
Support and clearance references for the illustrated overhead-line installation.