RPCF3 Phase Selective Power Factor Controllers

Description

Phase-selective reactive power control

RPCF3 controllers sample the voltage and current of all three phases separately. They calculate capacitor switching demand from fundamental-frequency reactive power and support simultaneous, individual-phase and mixed compensation. This makes the compensation schedule selectable for balanced or unbalanced three-phase loads.

The controller displays total and fundamental power factor, together with the voltage, current, active power, reactive power and apparent power of the individual phases. Automatic and manual operation are available. Settings are entered digitally and retained through a power interruption. Overvoltage and undervoltage protection are included.

Electrical and display specifications

ParameterSpecification
Rated voltage input3×220VAC
Rated current input5A
Frequency45-65Hz
Power factor display endpoints0.001 lagging to 0.001 leading
Active power measurement0-9999kW
Reactive power measurement0-9999kvar
Apparent power measurement0-9999kVA
Power factor target adjustment0.70 lagging to 0.70 leading
Undervoltage protection180VAC
Output contact capacity220VAC, 7A
Sensitivity20mA
Current input resistance≤0.01Ω
Maximum outputs16 circuits
Output coding12 selectable codes
Compensation schedulesSix selectable schedules; the RPCF3-12S examples below show five arrangements
DisplayFour-digit red LED
Consumption10VA

RPCF3-12S compensation examples

In the mixed arrangements, the individual compensation count is per phase: nine simultaneous circuits plus one circuit per phase, six plus two per phase, or three plus three per phase use twelve outputs. The three mixed arrangements share the same application and switching logic.

Compensation arrangementLoad conditionSwitching method
All simultaneous compensationThree-phase powers are approximately balancedSwitch according to total three-phase reactive power
9 simultaneous circuits and 1 individual circuit per phaseThree-phase powers differ moderatelySelect simultaneous compensation using the phase with the lowest reactive power; add individual compensation when the remaining demand or imbalance requires it
6 simultaneous circuits and 2 individual circuits per phase
3 simultaneous circuits and 3 individual circuits per phase
All individual compensation, 4 circuits per phaseSeverely unbalanced three-phase powersSwitch according to each phase's reactive power

Panel and mounting sizes

Panel size (mm)Panel cutout (mm)
144×144138×138
122×122113×113

Mounting options include a plug-in arrangement secured by retaining screws and rail mounting. Select the panel size and the required output count together with the compensation schedule.