PV1-F cables have one stranded conductor; PV2-F cables have two conductors in a paired cable profile. Each range includes nominal conductor cross-sections of 2.5mm², 4mm² and 6mm².
| Model | Cores | Nominal cross-section per core | Rated voltage | External dimensions |
|---|---|---|---|---|
| ULO-PV1-F (1*2.5mm²) | 1 | 2.5mm² | 1000V | Diameter: 5.3±0.1mm |
| ULO-PV1-F (1*4mm²) | 4mm² | Diameter: 5.8±0.1mm | ||
| ULO-PV1-F (1*6mm²) | 6mm² | Diameter: 6.6±0.1mm | ||
| ULO-PV2-F (2*2.5mm²) | 2 | 2.5mm² | 11.5mm × (5.3±0.2mm) | |
| ULO-PV2-F (2*4mm²) | 4mm² | 13mm × (5.8±0.2mm) | ||
| ULO-PV2-F (2*6mm²) | 6mm² | 1500V | 15mm × (7.0±0.2mm) |
Strand count and conductor resistance below apply to each core. Twin-core cables contain two of the corresponding conductor constructions.
| Nominal cross-section per core | Strands per core | Individual strand diameter | Minimum insulation thickness | Minimum sheath thickness | Conductor resistance at 20°C |
|---|---|---|---|---|---|
| 2.5mm² | 36 | 0.285mm | 0.65mm | 0.65mm | ≤8.21Ω/km |
| 4mm² | 56 | 0.75mm | 0.7mm | ≤5.09Ω/km | |
| 6mm² | 84 | 0.8mm | 0.75mm | ≤3.39Ω/km |
| Parameter | Specification |
|---|---|
| Conductor | Stranded copper |
| Insulation material | XLPO |
| Insulation material group | I |
| Flammability classification | UL94V-0 |
| Rated temperature | -40°C to +90°C |
| Completed-cable voltage test | 6.5kV for 5 minutes; no breakdown |
Select by core count, nominal conductor size and the exact model voltage. The 1500V rating applies specifically to the 2×6mm² twin-core model. Current-carrying capacity depends on the installation and is not specified in these cable data.