| Part Number: | ULO | - | TB110 | - | PTVME 6 | / | S BU |
|---|---|---|---|---|---|---|---|
| Explanation: |
Code Prefix |
Series Number |
Terminal Model PTVME 6 - 6mm² test-disconnect terminal; this breakdown covers PTVME6/S only |
Configuration and Color S - S configuration, gray body; omit BU |
TB120-PTME4 and TB110-PTVME6/S are side-entry push-in test-terminal configurations with two connection points in one row. Their disconnect structures are shown in the photographs. Select the complete model and verify the fitting dimensions and conductor preparation before installation.
The PTME4 model identity differs from its associated drawing, which is labeled TB110-PTVME4-HESI. Those documents are retained as reference material, but they do not establish that PTME4 and PTVME4-HESI are equivalent. Specifications from that reference drawing are kept separate below.
| Property | TB120-PTME4 listed data | TB110-PTVME6/S |
|---|---|---|
| Connection points / rows | 2 / 1 | |
| Nominal current | 24A | 30A |
| Maximum load current | Not established for this exact identity | 30A |
| Rated voltage, category III / pollution degree 3 | 500V | 1000V |
| Impulse voltage | 4kV listed; differing reference drawing is not assigned to this model | 8kV |
| Nominal conductor area | Unspecified | 6mm² |
| Solid conductor | 0.2–6mm² | 0.5–6mm² / 20–10AWG |
| Flexible conductor | 0.2–6mm² listed | 0.5–6mm² / 20–10AWG |
| Flexible with ferrule | 0.25–4mm² | 0.5–2.5mm² |
| Strip length | Unspecified for this exact identity | 10–12mm |
| Width × length × height | 6.2×70.5×48.8mm listed; exact fit unestablished | 8.15×82.01×53mm |
PTME4 values above are model-page entries and are not validated by the differently named attachment. Category III / pollution degree 2 and category II / pollution degree 2 voltage ratings are unspecified for both models. No UL use-group ratings are assigned.
| Property | Both model entries |
|---|---|
| Protection | IP20 |
| Operating temperature | -40°C to +105°C |
| Insulator | PA66, material group I |
| Flammability | UL94V-0 |
| Contact | Tin-plated copper alloy |
The retained PTVME4-HESI reference has the following data. These values must not replace PTME4's entries without an established model correspondence.
| Reference-drawing property | TB110-PTVME4-HESI value |
|---|---|
| Function / connections / rows / potentials | Test disconnect / 2 / 1 / 1 |
| Nominal voltage | 500V |
| Nominal / maximum load current | 24A / 24A |
| Impulse voltage / overvoltage category | 6kV / III |
| Nominal conductor area | 4mm² |
| Solid conductor | 0.2–6mm² / 24–10AWG |
| Flexible conductor | 0.2–4mm² / 24–12AWG |
| Strip length | 10–12mm |
| Width × length × height | 6.15×71.6×48.83mm |
| Other outline references | 41.98mm height reference, 35.3mm edge reference, 17.5mm rail reference |
| Drawing color entries | Gray; BU blue |

The PTVME6/S model-specific drawing defines the 8.15mm width, 82.01mm length and 53mm overall height. Additional outline references are 47mm from the indicated rail datum, 41.15mm from the indicated center datum to the edge, and 17.5mm at the rail feature. The drawing lists gray and BU blue variants. Its single potential does not mean the disconnect is permanently closed.

End plates, jumpers, markers and test accessories are not specified as included. Match any accessory to the exact terminal configuration; the two models are not described as interchangeable.