Nickel-plated brass bodies combine with PA66 clamping components and NBR sealing elements to secure cables through enclosure plates. The glands have an IP68 protection rating. Fit the gland to the plate, pass the cable through the assembled gland and tighten the locknut to secure it.
Standard thread lengths suit internally threaded equipment or thin plates. Longer-thread versions are available for thicker plates; customization is available.
| Condition | Operating range | Short-duration limit |
|---|---|---|
| Static | -40°C to +100°C | +120°C |
| Dynamic | -20°C to +80°C | +100°C |
All dimensions and cable clamping ranges below are in mm. The thread pitch is 1.5mm. M20S, M20M and M20L provide different clamping ranges.
| Model / thread | D1 | D2 | B1 | L1 | L4 | Cable range |
|---|---|---|---|---|---|---|
| M12×1.5 | 12 | 8.3 | 6 | 7.9 | 13.3 | 3-6.5 |
| M16×1.5 | 16 | 10.9 | 9.6 | 15 | 15.8 | 5-10 |
| M20S×1.5 | 20 | 14.8 | 12.5 | 18.4 | 3-7 | |
| M20M×1.5 | 6-12 | |||||
| M20L×1.5 | 15.5 | 14.5 | 19.5 | 10-14 | ||
| M25×1.5 | 25 | 21 | 18.4 | 22.3 | 13-18 | |
| M32×1.5 | 32 | 26 | 26.2 | 24.8 | 18-25 | |
| M40×1.5 | 40 | 33 | 33.4 | 18 | 31.6 | 25-32 |
| M50×1.5 | 50 | 42.5 | 36.5 | 30-38 | ||
| M63×1.5 | 63 | 54.1 | 44 | 18.5 | 32.6 | 34-44 |