| Part Number: | ULO | - | MC | - | 1515F | - | B | - | 20A |
|---|---|---|---|---|---|---|---|---|---|
| Explanation: |
Brand |
Series |
Fuse Version 1515F - Fixed 1500V photovoltaic inline fuse connector version |
End Configuration A - Connector interfaces at both ends |
Rated Current 10A - 10A |
MC1515F connectors integrate a photovoltaic fuse into an inline housing. A, B, C and D identify different end configurations; each has four current-rated models at 1500V.
| Configuration | Depicted end arrangement |
|---|---|
| A | Connector interfaces at both ends |
| B | Projecting connector end and cable-entry end |
| C | Recessed connector end and cable-entry end |
| D | Cable-entry ends on both sides |
All models below have a rated voltage of 1500V. The complete model code specifies both the end configuration and current rating.
| Configuration | 10A | 15A | 20A | 30A |
|---|---|---|---|---|
| A | ULO-MC-1515F-A-10A | ULO-MC-1515F-A-15A | ULO-MC-1515F-A-20A | ULO-MC-1515F-A-30A |
| B | ULO-MC-1515F-B-10A | ULO-MC-1515F-B-15A | ULO-MC-1515F-B-20A | ULO-MC-1515F-B-30A |
| C | ULO-MC-1515F-C-10A | ULO-MC-1515F-C-15A | ULO-MC-1515F-C-20A | ULO-MC-1515F-C-30A |
| D | ULO-MC-1515F-D-10A | ULO-MC-1515F-D-15A | ULO-MC-1515F-D-20A | ULO-MC-1515F-D-30A |
| Parameter | Specification |
|---|---|
| Connection system | Multipoint connection |
| Termination method | Crimping |
| Pullout force | ≥50N |
| Insertion force | ≤50N |
| Contact resistance | ≤0.35mΩ |
| Protection level | IP68 |
| DC safety class | II |
| Ambient temperature | -40°C to +90°C |
| Temperature tolerance | -40°C to +135°C |
| Insulation material / group | PPO / I |
| Flammability classification | UL94V-0 |
| Contact material / finish | Brass / tin plated |
Match the end arrangement to the wiring layout and select the fuse characteristics for the circuit. Current and voltage ratings do not specify fuse dimensions, time-current performance or breaking capacity. The ambient range and temperature tolerance are separate limits.