| Part Number: | ULO | - | PV | - | 15MC |
|---|---|---|---|---|---|
| Explanation: |
Brand |
Product Family PV - Photovoltaic cable connector; this breakdown covers the unsuffixed MC, 15MC and 151MC models |
Model MC - 1000V model; PPO housing, UL94V-0, IP68 |
MC and 15MC connectors use a multipoint contact system, crimp termination and an embedded locking arrangement. Choose the complete model by voltage, housing material, protection level and ambient temperature.
| Model | Rated voltage | Housing | Flammability | Protection | Ambient temperature | Contact resistance |
|---|---|---|---|---|---|---|
| ULO-PV-MC-N | 1000V | PPO | UL94V-0 | IP68 | -40°C to +95°C | ≤0.5mΩ |
| ULO-PV-MC-N-R | ||||||
| ULO-PV-MC | -40°C to +90°C | |||||
| ULO-PV-MC (PC) | PC | UL94V-2 | IP67 | ≤0.35mΩ | ||
| ULO-PV-MC (PC2) | ||||||
| ULO-PV-15MC (PC) | 1500V | IP68 | -40°C to +95°C | |||
| ULO-PV-15MC | PPO | UL94V-0 | -40°C to +90°C | |||
| ULO-PV-151MC |
Current ratings depend on conductor cross-section. Standard wiring sizes are 2.5mm², 4mm² and 6mm². The electrical rating table also specifies a separate 1.5mm² condition.
| Conductor cross-section | Rated current, all listed models |
|---|---|
| 1.5mm² | 17A |
| 2.5mm² | 22.5A |
| 4-6mm² | 30A |
| Parameter | All listed models |
|---|---|
| Contact system | Multipoint connection |
| Termination | Crimp |
| Standard wiring sizes | 2.5mm², 4mm², 6mm² |
| Locking system | Embedded |
| DC safety class | II |
| Temperature tolerance | -40°C to +135°C |
| Insulation material group | I |
| Contact material / finish | Brass / tin plated |
The temperature-tolerance range is separate from the model-specific ambient operating range listed above.