JK intelligent power capacitors combine a monitoring and control unit, zero-cross switching, circuit protection and low-voltage shunt capacitors in one modular assembly. They serve 0.4kV networks and can operate individually or as a coordinated compensation system for local, individual or centralized reactive power correction.
Simultaneous three-phase compensation uses delta-connected capacitor sections; separate-phase compensation supports individual phase switching for unbalanced loads. Single-loop and dual-loop configurations are distinguished in the model code. The control and capacitor portions use upper and lower modular sections.

| Parameter | Specification |
|---|---|
| Operating supply | 380VAC for simultaneous compensation; 220VAC for separate-phase compensation |
| Frequency | 50Hz±5% |
| Voltage deviation | ±20% |
| Control-unit consumption | <2W |
| Control method | Multiple-parameter fuzzy control |
| Sampling signal | 0-2VAC |
| Voltage measurement accuracy | ≤0.5% |
| Current measurement accuracy | ≤1% |
| Power factor measurement accuracy | ≤1.5% |
| Temperature measurement accuracy | ≤1°C |
| Ambient temperature | -25°C to +55°C |
| Relative humidity | 20-90% |
| Altitude | ≤2000m |
| Example weight | 7kg for the 20+20kvar configuration |
| Design references | DL/T842-2003; JB/T7117-1993; GB/T15576-2008 |
For example, JK-8CS/450-40(20+20) identifies the JK series, design code 8, dual-loop C construction, simultaneous three-phase compensation S, 450V capacitor rating and 40kvar total output comprising two 20kvar loops. The capacitor rating is distinct from the 380V system operating supply.
| Code field | Meaning |
|---|---|
| C / D | C: dual loop; D: single loop |
| S / F | S: simultaneous three-phase compensation; F: separate-phase compensation |
| Special requirement field | Omitted for the standard type; 1-9 or A-Z identify special requirements |
| Voltage and output | Capacitor rated voltage in V, total output in kvar and, where shown, individual loop outputs in parentheses |

| Model | Height H (mm) |
|---|---|
| JK-8CS/450-60 | 335 |
| JK-8CS/450-50 | |
| JK-8CS/450-40 | 280 |
| JK-8CS/450-30 | |
| JK-8CS/450-20 | 235 |
| JK-8CS/450-10 | |
| JK-8CS/450-7.5 | |
| JK-8CF/250-20 | 355 |
| JK-8CF/250-15 | |
| JK-8CF/250-10 | 280 |
| JK-8CF/250-5 | |
| JK-8DS/450-20 | 335 |
| JK-8DS/450-15 | 280 |
| JK-8DS/450-10 | |
| JK-8DS/450-5 | |
| JK-8DF/250-10 | 335 |
| JK-8DF/250-5 | 280 |
Use the model-specific H value with the corresponding enclosure drawing. The illustrated mounting alternatives include four Ø6mm holes and 6×10mm slots. Check the support arrangement and terminal clearance for the selected single- or dual-loop assembly.