JK Intelligent Integrated Power Capacitors

Description

Integrated reactive power compensation

JK intelligent power capacitors combine a monitoring and control unit, zero-cross switching, circuit protection and low-voltage shunt capacitors in one modular assembly. They serve 0.4kV networks and can operate individually or as a coordinated compensation system for local, individual or centralized reactive power correction.

Simultaneous three-phase compensation uses delta-connected capacitor sections; separate-phase compensation supports individual phase switching for unbalanced loads. Single-loop and dual-loop configurations are distinguished in the model code. The control and capacitor portions use upper and lower modular sections.

Single and dual capacitor integrated compensation assemblies
Integrated controller and capacitor configurations with different capacitor-section arrangements.

Electrical and environmental data

ParameterSpecification
Operating supply380VAC for simultaneous compensation; 220VAC for separate-phase compensation
Frequency50Hz±5%
Voltage deviation±20%
Control-unit consumption<2W
Control methodMultiple-parameter fuzzy control
Sampling signal0-2VAC
Voltage measurement accuracy≤0.5%
Current measurement accuracy≤1%
Power factor measurement accuracy≤1.5%
Temperature measurement accuracy≤1°C
Ambient temperature-25°C to +55°C
Relative humidity20-90%
Altitude≤2000m
Example weight7kg for the 20+20kvar configuration
Design referencesDL/T842-2003; JB/T7117-1993; GB/T15576-2008

Model identification

For example, JK-8CS/450-40(20+20) identifies the JK series, design code 8, dual-loop C construction, simultaneous three-phase compensation S, 450V capacitor rating and 40kvar total output comprising two 20kvar loops. The capacitor rating is distinct from the 380V system operating supply.

Code fieldMeaning
C / DC: dual loop; D: single loop
S / FS: simultaneous three-phase compensation; F: separate-phase compensation
Special requirement fieldOmitted for the standard type; 1-9 or A-Z identify special requirements
Voltage and outputCapacitor rated voltage in V, total output in kvar and, where shown, individual loop outputs in parentheses
JK integrated power capacitor model coding diagram
Design, loop configuration, compensation mode and capacitor rating fields.

Model heights

ModelHeight H (mm)
JK-8CS/450-60335
JK-8CS/450-50
JK-8CS/450-40280
JK-8CS/450-30
JK-8CS/450-20235
JK-8CS/450-10
JK-8CS/450-7.5
JK-8CF/250-20355
JK-8CF/250-15
JK-8CF/250-10280
JK-8CF/250-5
JK-8DS/450-20335
JK-8DS/450-15280
JK-8DS/450-10
JK-8DS/450-5
JK-8DF/250-10335
JK-8DF/250-5280

Outline and fixing arrangements

Use the model-specific H value with the corresponding enclosure drawing. The illustrated mounting alternatives include four Ø6mm holes and 6×10mm slots. Check the support arrangement and terminal clearance for the selected single- or dual-loop assembly.

Integrated capacitor enclosure outlines and fixing patterns
Front, side and fixing-pattern views; H is supplied by the model-height table.