HCS Series intelligent dehumidifiers control humidity inside electrical cabinets and enclosed equipment spaces. HCS-15 is sized for smaller cabinet volumes, while HCS-30 provides higher dehumidification power, better measurement accuracy and RS485 communication for monitored installations.
Common Parameters
| Parameter | Specification |
|---|
| Measurement Range | Temperature -19 to 99 deg C; humidity 0 to 99%RH |
| Resolution | Temperature 1 deg C; humidity 1%RH |
| Control Mode | High-humidity control; optional low-temperature or high-temperature control |
| Temperature Output | One passive relay output, 250VAC/3A or 30VDC/3A |
| Fault Output | One passive fault output |
| Communication | RS485 communication, Modbus protocol |
| Drain Tube | High-temperature-resistant silicone tube, standard 1m length; other lengths by request |
| Operating Environment | 0 to 50 deg C, 85%RH or less, non-corrosive environment |
HCS-15
| Parameter | Specification |
|---|
| Input | One built-in temperature and humidity input module |
| Power Supply | 220VAC, 50/60Hz |
| Dehumidification Power | 15W default; other power levels by request |
| Basic Error | Temperature +/-1.5 deg C from 0 to 100 deg C; humidity +/-5%RH from 10% to 99% |
| Recommended Dehumidification Space | 0.5-1 cubic meter |
HCS-30
| Parameter | Specification |
|---|
| Power Supply | 220VAC, 50Hz; standby power consumption 5VA |
| Dehumidification Power | 30W default; other power levels by request |
| Basic Error | Temperature +/-0.5 deg C from 10 to 50 deg C, +/-1.5 deg C from 0 to 99 deg C; humidity +/-3%RH from 10% to 90%, +/-5%RH from 0% to 99% |
| Recommended Dehumidification Space | 1-2 cubic meters |