HQ-007/0 and HQ-012/0 crimp inserts provide 10A circuits in H3A hoods and housings. Choose seven or twelve contacts plus protective earth, then select the male or female version. Main contacts use crimp connections; the PE connection differs between the two contact counts.
Model and PE connection selection
| Male insert | Female insert | Contacts | PE connection | PE conductor range |
|---|
| SO-HQ-007/0-MC | SO-HQ-007/0-FC | 7+PE | Screw terminal | 2.5mm², 14AWG |
| SO-HQ-012/0-MC | SO-HQ-012/0-FC | 12+PE | Quick Lock termination | 0.5-2.5mm², 20-14AWG |
Electrical ratings
| Pollution degree | Rated current | Rated voltage | Rated impulse voltage |
|---|
| 3 | 10A | 400V | 6kV |
| 2 | 10A | 400V conductor-to-earth / 690V conductor-to-conductor | 6kV |
The rated voltage according to UL/CSA is 600V for both contact counts.
Crimp connections and insert specifications
| Property | Specification |
|---|
| Main-contact conductor range | 0.14-2.5mm², 26-14AWG |
|---|
| Contact material | Copper alloy |
|---|
| Contact finish options | Hard-silver plated or hard-gold plated |
|---|
| Contact resistance | ≤3mΩ |
|---|
| Insulation resistance | ≥1010Ω |
|---|
| Insert material and colour | Polycarbonate, RAL 7032 light grey |
|---|
| Temperature range | -40°C to +125°C |
|---|
| Flammability according to UL 94 | V0 |
|---|
| Mechanical life | ≥500 mating cycles |
|---|
| SO-HQ-012/0-MC tooling | TL02G crimp tool; TL00 contact-removal tool |
|---|
H3A enclosure options
| Enclosure | Material | Protection when coupled, according to IEC 60529 |
|---|
| Plastic hood or housing | Polycarbonate, UL 94 V0 | IP67 |
| Metal hood or housing | Die-cast zinc | IP44; IP67 with a sealing screw |
Contact arrangement and outline drawings
Four individual drawings cover the male and female versions of both contact counts. Use the selected model drawing to check numbered contact positions, PE location and installation depth; the seven-contact and twelve-contact mating faces differ.