HMK 40A crimp modules offer two-contact, three-contact and four-contact layouts for modular power connections. Voltage ratings and conductor ranges vary with the layout; select these together with the mating gender.
| Property | Two contacts | Three contacts | Four contacts |
|---|---|---|---|
| Male model | SO-HMK-002-MC | SO-HMK-003-MC | SO-HMK-004-MC |
| Female model | SO-HMK-002-FC | SO-HMK-003-FC | SO-HMK-004-FC |
| Rated current | 40A | 40A | 40A |
| Rated voltage | 1000V | 500V | 830V |
| Rated impulse voltage | 8kV | 6kV | 8kV |
| Pollution degree | 3 | 3 | 3 |
| Wire range | 1.5-10mm², 16-8AWG | 1.5-10mm², 16-8AWG | 1.5-6mm², 16-10AWG |
| Additional rating condition | Not specified | 32A and 600V according to UL/CSA | 600V according to UL |
| Property | Specification |
|---|---|
| Termination | Crimp |
| Contact material and surface | Copper alloy, hard-silver plated |
| Contact resistance | ≤1mΩ |
| Insulation resistance | ≥1010Ω |
| Module material and colour | Polycarbonate, RAL 7032 light grey |
| Temperature range | -40°C to +125°C |
| Flammability according to UL 94 | V0 |
| Mechanical life | ≥500 mating cycles |
Individual drawings show the outline, contact numbering and mating geometry of each male and female module. Choose crimp contacts for the selected module and conductor cross-section, and use the corresponding contact preparation requirements for termination.