HME 5- and 6-Contact Quick-Connection Modules

Description

HME quick-connection modules use spring terminals for modular electrical connections. Choose the five-contact or six-contact layout by voltage rating and wire preparation requirements, then select the mating gender.

Models and electrical ratings

PropertyFive-contact modulesSix-contact modules
Male modelSO-HME-005-MQSO-HME-006-MQ
Female modelSO-HME-005-FQSO-HME-006-FQ
Contacts56
Rated current16A16A
Rated voltage400V500V
Rated impulse voltage6kV6kV
Pollution degree33
Additional rated-voltage condition600V according to UL600V according to UL/CSA

Spring-terminal wiring

PropertyHME-005-MQ and HME-005-FQHME-006-MQ and HME-006-FQ
Wire range0.14-2.5mm², 26-14AWG0.5-4mm², 20-12AWG
Separate range for crimped ferrulesNo separate range specified0.14-2.5mm², 26-14AWG
Stripping length7-9mm10±0.5mm

Common materials and operating limits

PropertySpecification
Contact material and finishCopper alloy, hard-silver plated
Contact resistance≤3mΩ
Insulation resistance≥1010Ω
Module material and colourPolycarbonate, RAL 7032 light grey
Temperature range-40°C to +125°C
Flammability according to UL 94V0
Mechanical life≥500 mating cycles

The attachments provide individual male and female outline drawings for both contact counts. Match the drawing to the complete model code when checking module dimensions and mating geometry.