H2MK-001.1 axial-screw modules provide a single 200A contact with a 1900V rating. The male and female versions use Class 5 stranded conductors according to IEC 60228.
Module options
| Model | Gender | Contacts |
|---|
| SO-H2MK-001.1-M | Male | 1 |
| SO-H2MK-001.1-F | Female | 1 |
Electrical and termination specifications
| Property | Specification |
|---|
| Rated current | 200A |
|---|
| Rated voltage | 1900V |
|---|
| Rated impulse voltage | 8kV |
|---|
| Pollution degree | 3 |
|---|
| Rated voltage according to UL | 600V |
|---|
| Insulation resistance | ≥1010Ω |
|---|
| Termination | Axial screw |
|---|
| Conductor type | IEC 60228 Class 5 stranded wire |
|---|
| Metric conductor range | 25-70mm² |
|---|
| AWG conductor range | 2-0AWG |
|---|
| Hexagonal driver | SW5 × 150 |
|---|
| Stripping length | 16mm |
|---|
| Contact material and finish | Copper alloy, hard-silver plated |
|---|
| Contact resistance | ≤0.3mΩ |
|---|
Tightening torque
| Conductor cross-section | Tightening torque |
|---|
| 25mm² | 8N·m |
| 35mm² | 8N·m |
| 50mm² | 9N·m |
| 70mm² | 10N·m |
Select the torque from the metric conductor cross-section. The outline drawings show a heat-shrink tube at the cable termination; account for this insulation arrangement when preparing the assembly.
Materials and operating limits
| Property | Specification |
|---|
| Module material and colour | Polycarbonate, RAL 7032 light grey |
|---|
| Temperature range | -40°C to +125°C |
|---|
| Flammability according to UL 94 | V0 |
|---|
| Mechanical life | ≥500 mating cycles |
|---|