GYW3 DC Air Circuit Breaker

Description

GYW3 DC air circuit breakers are used in high-current DC distribution systems where reliable isolation, fault interruption and equipment protection are required. The series covers GYW3-2500 and GYW3-4000 frame sizes, with multi-pole DC voltage configurations and fixed or draw-out installation options.

Key Features

  • Designed for DC circuit protection and switching in high-current distribution applications.
  • Arc-extinguishing chamber and contact-system design support high breaking capacity.
  • Optimized contact structure and operating mechanism for improved electrical life and mechanical reliability.
  • High-strength insulating material is used for impact strength and insulation performance.
  • Compact phase spacing and built-in shunt help reduce complete cabinet size.
  • Safety devices include draw-out door interlock, three-position locking device, OFF-position key lock, terminal shield and closing-ready device.

Model Range

ModelRated currentPoles in seriesRated working voltage
GYW3-2500800A, 1000A, 1250A, 1600A, 2000A, 2500A2P, 3P, 4PDC500V / DC750V for 2P or 3P; DC1000V / DC1500V for 4P
GYW3-40001600A, 2000A, 2500A, 3200A, 3600A, 4000A3P, 4PDC500V / DC750V for 3P; DC1000V / DC1500V for 4P

Breaking Capacity

ModelDC voltage and pole configurationRated ultimate short-circuit breaking capacity
GYW3-2500DC500V, 2P50kA
GYW3-2500DC500V, 3P65kA
GYW3-2500DC750V, 2P40kA
GYW3-2500DC750V, 3P55kA
GYW3-2500DC1000V, 4P50kA
GYW3-2500DC1500V, 4P40kA
GYW3-4000 S/HDC500V, 3P80kA / 120kA
GYW3-4000 S/HDC750V, 3P65kA / 80kA
GYW3-4000 S/HDC1000V, 4P55kA / 75kA
GYW3-4000 S/HDC1500V, 4P50kA / 60kA

Installation And Control

  • Installation options include fixed and draw-out types.
  • Controller options listed in the technical data include NWK20Z and NWK22Z controllers.
  • Rated service short-circuit breaking capacity is listed as 100% of Icu.
  • Rated short-time withstand current for 1 second is listed as 100% of Icu.