CXY Cylindrical Magnetic Sensors

Description

Magnetic Sensor Selection

These cylindrical magnetic sensors are available in M8, M12 and M18 metal housings. The listed models use either a DC NPN normally open output or an AC two-wire normally open output. They have a 10mm nominal sensing distance, 100Hz response and IP67 protection. Check the sensing arrangement with the actual magnet and mounting. A red LED indicates operation.

ModelMounting sizeOperating supplyOutput and connectionSensing distanceResponse frequency
CXY08-10DNAM810-30VDCNPN, NO, three-wire10mm100Hz
CXY08-10AKA90-250VACAC two-wire, NO
CXY12-10DNAM1210-30VDCNPN, NO, three-wire
CXY12-10AKA90-250VACAC two-wire, NO
CXY18-10DNAM1810-30VDCNPN, NO, three-wire
CXY18-10AKA90-250VACAC two-wire, NO

Electrical and Environmental Parameters

ParameterSpecification and conditions
Housing formCylindrical metal tube, normal thread
Hysteresis3-20%
Consumption currentMaximum 10mA
Residual voltageMaximum 3V
Control outputMaximum 200mA
Temperature effectWithin ±10% of sensing distance, referenced to +20°C; the stated characterization range is -25°C to +70°C. The operating-temperature rating remains -15°C to +55°C.
Insulation resistanceAt least 50MΩ at 500VDC
Dielectric strength1500VAC, 50/60Hz, for 1 minute
Vibration resistance1mm amplitude, 10-55Hz with a 1 minute frequency cycle; 2 hours in each X, Y and Z direction
Shock resistance500m/s², approximately 50G; three shocks in each X, Y and Z direction
IndicatorRed operation LED
Operating temperature-15°C to +55°C, without icing
Storage temperature-15°C to +55°C, without icing
Ambient humidity35-95%RH, without condensation
Protection circuitsSurge protection; reverse polarity protection for the DC configuration
Case and nutBrass with nickel plating
WasherIron with nickel plating
Sensing surfacePBT
Standard cableGray PVC
Oil-resistant cableBlack oil-resistant PVC; PUR and shielded cable constructions are separate options
Enclosure protectionIP67

Cable Construction

Model groupDiameter and lengthConductor countConstruction references
CXY08Ø2.8mm, 2mDC NPN: three conductors
AC two-wire: two conductors
AWG22 designation; 22 strands of Ø0.1mm per conductor; insulation outside diameter Ø1.25mm
CXY12Ø3.8mm, 2mAWG22 designation; 25 strands of Ø0.1mm per conductor; insulation outside diameter Ø1.25mm
CXY18Ø4.8mm, 2mAWG22 designation; 30 strands of Ø0.1mm per conductor; insulation outside diameter Ø1.25mm

Ordering-Code Layout and Options

Magnetic sensor ordering-code layout with twelve numbered positions
Ordering-code positions for the sensor family, housing, size, supply, output, connector and cable selections.
PositionSegmentCodeMeaning and applicability
1ClassificationCXMagnetic sensor
2ShapeYCylindrical metal housing
3Size08, 12, 18M8, M12 and M18 respectively
4Product typeOmittedStandard form
5Thread lengthOmittedNormal thread
LLong-thread option; obtain the matching dimensions
6Sensing distance1010mm nominal sensing distance
7SupplyD10-30VDC
A90-250VAC
8Output modeNNPN output
PPNP output option; select a matching model and wiring configuration
KAC two-wire output
LDC two-wire output option; distinct from the listed NPN connection
9Output stateANormally open
BNormally closed option; obtain the corresponding model
10Connection formOmittedCable with free lead end
MDirect M12 straight four-pin, A-coded connector
M plus connector-selection codeM-type cable connector configuration
D plus connector-selection codeDT-type connector configuration
A plus connector-selection codeAMP-type connector configuration
S plus connector-selection codeSM-type connector configuration
11Cable materialOmittedPVC
UPUR
VPShielded PVC
UPShielded PUR
12Lead lengthOmittedDirect M-connector body connection
L1-L51m to 5m, with L1 meaning 1m; other lengths can be specified

Specify complete connector-selection codes and use the operating voltage and wiring appropriate to the selected output mode.

Reference Standards and Ratings

Reference designationStandardDocumentation
CCCGB/T 14048.10Check documentation for the exact model and configuration.
TUVEN 60947-5-2
CE
Utilization categoryReference ratingOperating supply
AC-140200mA at 24-250VAC90-250VAC for the listed AC models
DC-13200mA at 10-30VDC10-30VDC for the listed DC models

Illustrated Cylindrical Dimensions

ModelThreadLength referencesEnd-view referencesAdditional dimensions
CXY08-10M8×145mm overall; 30mm threaded referenceØ15mm and 13mm3mm nut thickness; Ø2.8mm cable
CXY12-10M12×151mm overall; 30mm threaded referenceØ21mm and 17mm4mm nut thickness; Ø3.8mm cable
CXY18-10M18×156mm overall; 30mm threaded referenceØ29mm and 24mm4mm nut thickness; Ø4.8mm cable

Use the attachment to identify each dimension's feature and the operation-indicator position. Alternative thread and connector configurations require their matching drawings.

Application Conditions

These sensors are intended for ordinary industrial control. Nuclear, gas or power systems requiring exceptional reliability, personal-safety functions, harsh outdoor or contaminated environments, fire or explosion hazards, military use and aerospace require a specifically designed and confirmed configuration.