CUK Screw-type Terminal Blocks for NS32 and NS35 Rails

Description

CUK screw-type terminal blocks mount on NS32 G-section or NS35 U-section rails. The range includes feed-through, double-level, interconnection, switch and fuse arrangements. General terminals use a polyamide66 insulating housing, enclosed screw-guide holes and white marking positions at both upper ends. Gray GY is the standard color; custom colors are available.

Central and side bridges distribute potential where the particular model supports them. Double-level terminals stagger the upper and lower levels by 2.5mm for identification and screwdriver access. The /2Q configurations allow bridging at either level. Select the full model together with its rated voltage, conductor type, rail-mounted height and accessories.

Terminal Ratings and Conductor Ranges

Conductor ranges are in mm². The rigid, flexible and AWG specifications are separate references. The electrical tables identify IEC60947-7-1; this reference does not assert a separate product certification.

ModelArrangementAWGRigid conductorFlexible conductorCurrentVoltage
CUK-1.5Screw terminal26–160.14–1.50.14–1.417.5A500V
CUK-2.5B24–120.2–40.2–2.532A690V
CUK-2.524A800V
CUK-2.5/2-2Two-in two-out500V
CUK-2.5/2Double-level
CUK-2.5/2LDouble-level interconnection
CUK-2.5/2QBridging at either level
CUK-4Screw terminal24–100.2–60.2–432A800V
CUK-4KSwitch terminal24–120.2–416A
CUK-4/1-2One-in two-out32A500V
CUK-4/2-2Two-in two-out690V
CUK-4/2-2KTwo-in two-out switch16A
CUK-4/2Double-level32A500V
CUK-4/2LDouble-level interconnection
CUK-4/2QBridging at either level
CUK-6Screw terminal24–80.2–100.2–641A800V
CUK-6S20–80.5–100.5–6400V
CUK-1020–60.5–160.5–1057A800V
CUK-1612–42.5–254–1676A
CUK-3514–22.5–352.5–35125A1000V
CUK-35B800V
CUK-506–016–5025–50150A1000V
CUK-95Not specified25–9535–95232A
CUK-15035–15050–150308A

CUK-95 has a maximum load reference of 232A. CUK-150 has a separate maximum load reference of 309A with a 150mm² rigid conductor; its tabulated current is 308A. The maximum reference is distinct from the tabulated rating.

Terminal Dimensions

All dimensions are in mm. The final height is the installed height on the U-section rail, distinct from the body height.

ModelThicknessWidthBody heightU-rail height
CUK-1.54.242.54249.5
CUK-2.5B6.2
CUK-2.55.24754.5
CUK-2.5/2-263.5 (inferred)
CUK-2.5/2566269.5
CUK-2.5/2L
CUK-2.5/2Q67
CUK-46.242.54754.5
CUK-4K5158.566
CUK-4/1-250.54754.5
CUK-4/2-263.5
CUK-4/2-2K
CUK-4/2566269.5
CUK-4/2L
CUK-4/2Q67
CUK-68.242.54754.5
CUK-6S7251.559
CUK-1010.242.54754.5
CUK-1612.25461.5
CUK-3515.2506269.5
CUK-35B565259.5
CUK-5020.271.377.284.7
CUK-952683.691.699.1
CUK-15031.6101112.5120

Contact and Housing Arrangements

CUK 1.5 and 2.5 terminal contact arrangements
CUK-1.5 and CUK-2.5 configurations, including separate double-level, interconnection and either-level bridging arrangements.
CUK 4 switch and multi-level terminal arrangements
CUK-4 feed-through, switch, one-in two-out, two-in two-out and double-level configurations.
CUK 6 to 35 terminal internal structures
CUK-6, CUK-6S, CUK-10, CUK-16 and CUK-35 contact and housing structures.
CUK large terminal housings and fuse structures
CUK-35B, CUK-50, CUK-95 and CUK-150 housings, followed by CUK-4RD and CUK-10RD fuse structures.

End Plates and Bridging Accessories

“Not specified” preserves an unassigned accessory position. It does not establish that an accessory from a neighboring model fits.

ModelEnd plateCentral bridgeSide bridgeInsulating spacerGroup / compensation partsMarker barMarking / end fixing
CUK-1.5D-CUK-2.5BCFB2-4
CFB3-4
CFB10-4
CEB2-4
CEB3-4
CEB10-4
Not specifiedAPZB4KLM-A; E/UK
CUK-2.5BCFB2-6
CFB3-6
CFB10-6
CEB2-6
CEB3-6
CEB10-6
S-KK3ZB6
CUK-2.5D-CUK-2.5/10CFB2-5
CFB3-5
CFB10-5
CEB2-5
CEB3-5
CEB10-5
S-KZB5
CUK-2.5/2-2D-CUK-4/2-2CEBL2-5
CEBL3-5
CEBL10-5
CUK-2.5/2D-CUK-2.5/2-4/2CFB2-5
CFB3-5
CFB5-5
CFB10-5
S-KK3DG-CUK-2.5/2-4/2; DP-CUK-2.5/2-4/2Not specified
CUK-2.5/2L
CUK-2.5/2QD-CUK-2.5/2Q-4/2QDG-CUK-2.5/2Q-4/2Q; DP-CUK-2.5/2Q-4/2Q
CUK-4D-CUK-2.5/10CFB2-6
CFB3-6
CFB10-6
CEB2-6
CEB3-6
CEB10-6
S-KAPZB6KLM-A; E/UK
CUK-4KNot specifiedNot specifiedNot specifiedNot specifiedNot specified
CUK-4/1-2D-CUK-4/1-2CFB2-6
CFB3-6
CFB10-6
S-KNot specified
CUK-4/2-2D-CUK-4/2-2S-KK3
CUK-4/2-2KNot specifiedNot specified
CUK-4/2D-CUK-2.5/2-4/2CFB2-6
CFB3-6
CFB10-6
S-KK3DG-CUK-2.5/2-4/2; DP-CUK-2.5/2-4/2
CUK-4/2L
CUK-4/2QD-CUK-2.5/2Q-4/2QDG-CUK-2.5/2Q-4/2Q; DP-CUK-2.5/2Q-4/2Q
CUK-6D-CUK-2.5/10CFB2-8
CFB3-8
CFB10-8
CEB2-8
CEB3-8
CEB10-8
S-KAPZB8KLM-A; E/UK
CUK-6SD-CUK-6SCFB10-6S/S short; CFB10-6S/L longNot specifiedNot specifiedE/UK
CUK-10D-CUK-2.5/10CFB2-10
CFB3-10
CFB10-10
CEB2-10
CEB3-10
CEB10-10
SKAPZB10KLM-A; E/UK
CUK-16D-CUK-16CFB2-12
CFB3-12
CFB10-12
CEB2-12
CEB3-12
CEB10-12
ZB12
CUK-35Not required: closed housingCFB2-15CEB2-15Not specifiedZB16
CUK-35BNot specifiedCFB2-15
CFB3-15
CEB2-15
CEB3-15
Not specifiedNot specifiedZB15CUK-B1; E/UK
CUK-50CFB2-20
CFB3-20
Not specifiedZB10
CUK-95Not specifiedZB22
CUK-150

Fuse Terminal Selection

CUK-4RD and CUK-10RD accept G-type 5×25mm fuses. CUK-4RD uses an opening fuse bracket in a closed housing; CUK-10RD uses a screw-cap fuse arrangement. Circuit current depends on the installed fuse. Indicator versions signal fuse continuity; their applicable voltage and small indicator current are distinct from the terminal body's 800VAC reference.

Fuse modelAWGRigid / flexible conductor in mm²Dimensions in mm: thickness / width / body / U-rail heightIndicator voltageIndicator currentColor
CUK-4RD24–120.2–4 /0.2–48.2 /72.5 /56.5 /64None specifiedNot applicableBlack BK or gray GY
CUK-4RD/LED2415–30VAC/DC3.5–8.1mA
CUK-4RD/LA250110–250VAC/DC0.5–1mA
CUK-10RD20–60.5–16 /0.5–1012 /62 /59 /66.5None specifiedNot applicableBlack BK or gray GY
CUK-10RD/LED2415–30VAC/DC1–2.5mA
CUK-10RD/LA250110–250VAC/DC0.5–1mABlack BK
Fuse familySide bridgeCentral bridgeMarker bar
CUK-4RD, CUK-4RD/LED24, CUK-4RD/LA250CEBS2-8
CEBS3-8
CEBS10-8
Not specifiedZB8
CUK-10RD, CUK-10RD/LED24, CUK-10RD/LA250CEB2-12
CEB3-12
CEB10-12
CFB2-12
CFB3-12
CFB10-12

Accessory Functions

Insulating spacers separate neighboring bridges electrically, can be inserted afterward and do not occupy extra rail length. AP spacers separate terminal groups visually and electrically. DG and DP compensation plates align neighboring ordinary and double-level terminals and are 2.5mm thick. ZB bars provide horizontal or vertical characters in 10-position arrangements. KLM-A clips have adjustable height and a 44×7mm writing area; CUK-B1 marking terminals fit either rail profile and have a 44×17mm writing area. E/UK end fixings secure the end of a row and accept marking parts.

On CUK-35B and CUK-50, the central bridge has an insulated screw head and requires opening the housing's separating section before bridging. The CUK-35B side bridge inserts into the clamping frame and engages the insulating housing. Use the exact accessory references in the tables for the applicable terminal.

CUK accessory profiles
Accessory profiles, from top to bottom: end plate, central bridge, side bridge, insulating spacers, group spacer, marker bar, marking clip and end fixing.