CLW2-63 cam switches provide modular rotary switching with a 63A conventional thermal-current rating. Select an on/off, changeover, instrument-selector or motor-control contact program, together with its operating positions, handle, mechanical function and panel wording.
Standard detent versions support up to eight contact sections; spring-return and illuminated versions support up to seven. The mounting arrangements recommend six or fewer sections. Indexing steps are 45°, 60° and 90°. Conventional, label, illuminated, G2-handle and panel-key versions have different front plates and rear-depth requirements.
| Field | Code / choice | Meaning |
|---|---|---|
| Design family | CLW2 | Modular cam switch |
| Thermal current | 63 | Ith63A |
| Mechanical function | Omitted | Conventional version |
| D | Illuminated version | |
| P | Label version, default label arrangement | |
| G2 | G2 handle arrangement | |
| Y2 | Panel-mounted key below the operating handle | |
| Y2P | Panel-mounted key with label arrangement | |
| Position program | Example: 6KC | Indexing step, start and end positions; this example gives −60°, 0°, 60° |
| Contact program | Example: 202 | Open/closed contact states at each operating position |
| Sections | 1–8; illustrated example: 3 | Detent≤8; return/illuminated≤7; preferably≤6 for the illustrated mounting arrangements |
| Handle | AD / G2 | Select the shape for the mounting version |
| Handle color | K / C / R | Black / blue / red |
| Panel print | Example: B14; special print: P | Omission retains the contact program's standard printing |


The first character is 4 for 45°, 6 for 60° or 9 for 90°. The next two letters identify starting and ending positions clockwise on the matching circle. A is the 0° reference; O is a position letter. Unrestricted 360° rotation repeats the start letter as the end letter: eight positions at 45°, six at 60° or four at 90°. Contact logic and section count can restrict travel.
| Code | Step | Position sequence |
|---|---|---|
| 4OB | 45° | O, A, B |
| 6KE | 60° | K, A, C, E |
| 9GC | 90° | G, A, C |

Arrows below show spring-return directions. Commas separate positions without a return arrow between them. All listed programs are available.
| Return code | Angles and return directions |
|---|---|
| A2 | 0° ← 45° |
| A3 | −45° ← 45° |
| A4 | −45° ← 0° |
| A5 | 0° ← 90° |
| B2 | −45° → 0° ← 45° |
| B4 | −90°, −45°, 0°, 45° ← 90° |
| B5 | −90°, −45°, 0° ← 45° |
| B7 | −90° → −45°, 0°, 45°, 90°, 135° |
| B8 | −90° → −45°, 0°, 45°, 90° |
| B9 | −45° → 0°, 45°, 90°, 135° |
| B10 | −45° → 0°, 45°, 90°, 135°, 180° |
| B11 | −45° → 0° ← 45° ← 90° |
| BA | −90° → −45° → 0° ← 45° ← 90° |
| BA1 | −45° → 0° → 45° ← 90° ← 135° |
| BC | −45° → 0° ← 45° |
| D4 | 0° ← 45° ← 90° |
| Z1 | −135° → −90°, 0° ← 45° |
| Z2 | −45° → 0°, 90° ← 135° |
| ZA | −90° → −45°, 0°, 45° ← 90° |
| ZB | −90° → −45°, 0°, 45° |
| ZC | −45°, 0°, 45° ← 90° |
| ZD | −90°, 0° ← 45° |
| ZE | 0°, 45° ← 90° |
| ZF | −45°, 0° ← 45° |
| ZG | −45° → 0°, 45° |
| ZK | −45° → 0°, 45°, 90° |
| ZK1 | −45° → 0°, 45°, 90°, 135° |
| Group | Parameter | Value |
|---|---|---|
| Electrical and mechanical | Referenced standard | GB/T14048.5 |
| Conventional thermal current | 63A | |
| Rated insulation voltage | 690VAC | |
| Impulse withstand voltage | 4kV | |
| Frequency | 50Hz technical rating; 50/60Hz application range | |
| Mechanical life | 500000 operations | |
| Electrical life | AC300000; DC200000 operations | |
| Operating frequency | 300 operations/hour | |
| Shock resistance | 50g, 11ms, half-sine waveform | |
| Vibration resistance | 10–500Hz, 5g | |
| Operating conditions | Ambient temperature | −25°C to +55°C |
| Humidity | ≤90%RH | |
| Pollution degree | 3 | |
| Installation category | III | |
| Storage/transport temperature | −40°C to +80°C | |
| Protection | IP65 at the working face |
Application voltage limits are 380VAC and 220VDC. Use the appropriate operating-current rating when selecting a circuit; Ith63A is the thermal-current value. A DC operating-current table is not specified.
| Utilization category | 24V | 48V | 110V | 220V | 380V |
|---|---|---|---|---|---|
| AC-15 | — | — | 22A | 16A | 8A |
A dash denotes an unspecified rating.
Dimensions below are in mm; n is the number of contact sections. The block pitch is 21.5mm. All illustrated arrangements use four Ø4.5 fixing holes on a 48±0.20 square and a central Ø10 opening.
| Version | Handle / plate dimensions | Front projection | Rear depth | Panel thickness | Additional opening |
|---|---|---|---|---|---|
| CLW2-63 | AD; 64×64 | 33.5 | Detent29+21.5n; return46.5+21.5n | Not specified | None illustrated |
| CLW2-63P | AD; 64×82 label plate | 1–4 | |||
| CLW2-63D | AD; 64×82 illuminated plate | 13×5 lamp slot; center40 above handle center | |||
| CLW2-63G2 | G2; 64×64 | 43 | None illustrated | ||
| CLW2-63Y2 | AD and panel key; 64×105.75 | Not specified | Detent47+21.5n; return64.5+21.5n | Ø34 key opening; center48±0.20 below handle center | |
| CLW2-63Y2P | AD, panel key and label; 64×122.75 |


Each section adds the two pairs below. Include all rows from section 1 through the selected section count. On/off programs open all contacts at 0 and close both groups at 1. Changeover closes the first group at position 1 and the second at position 2. Center-off adds an all-open position 0.
| Sections | On/off | Independent two-position | Bridged two-position | Independent center-off | Bridged center-off | Added first-group pair | Added second-group pair |
|---|---|---|---|---|---|---|---|
| 1 | 02/1 | 11/1 | 11J/1 | 101/1 | 101J/1 | 1–2 | 3–4 |
| 2 | 04/2 | 22/2 | 22J/2 | 202/2 | 202J/2 | 5–6 | 7–8 |
| 3 | 06/3 | 33/3 | 33J/3 | 303/3 | 303J/3 | 9–10 | 11–12 |
| 4 | 08/4 | 44/4 | 44J/4 | 404/4 | 404J/4 | 13–14 | 15–16 |
| 5 | 0A/5 | 55/5 | 55J/5 | 505/5 | 505J/5 | 17–18 | 19–20 |
| 6 | 0C/6 | 66/6 | 66J/6 | 606/6 | 606J/6 | 21–22 | 23–24 |
| 7 | 0E/7 | 77/7 | 77J/7 | 707/7 | 707J/7 | 25–26 | 27–28 |
| 8 | 0G/8 | 88/8 | 88J/8 | 808/8 | 808J/8 | 29–30 | 31–32 |
Bridged programs add links between even terminals: 2–4, 6–8, 10–12 and the corresponding pair on each subsequent section.
| Complete example | Function | Angles | Panel marks |
|---|---|---|---|
| CLW2-63-4AB-06/3 | Three-section on/off | 0°, 45° | 0, 1 |
| CLW2-63-9OB-33/3 | Three-section independent changeover | −45°, 45° | 1, 2 |
| CLW2-63-6OB-33J/3 | Three-section bridged changeover | −30°, 30° | 1, 2 |
| CLW2-63-4OB-303/3 | Three-section independent center-off | −45°, 0°, 45° | 1, 0, 2 |
| CLW2-63-4OB-404J/4 | Four-section bridged center-off | −45°, 0°, 45° | 1, 0, 2 |


Use only pairs within the selected program's stated terminal range. Each pair closes at its listed position and remains open at other positions. Keep all links in the matching diagram. The ten-section five-position reference exceeds the standard eight-section mechanism limit. Its illustration specifies only the shown contacts through 31–32.
| Positions | Program | Sections | Illustrated terminal-pair range |
|---|---|---|---|
| 3 | 111J/1 | 1 | 1–2 through 3–4 |
| 212J/2 | 2 | 1–2 through 7–8 | |
| 313J/3 | 3 | 1–2 through 11–12 | |
| 414J/4 | 4 | 1–2 through 15–16 | |
| 515J/5 | 5 | 1–2 through 19–20 | |
| 616J/6 | 6 | 1–2 through 23–24 | |
| 717J/7 | 7 | 1–2 through 27–28 | |
| 818J/8 | 8 | 1–2 through 31–32 | |
| 4 | 1111J/2 | 2 | 1–2 through 7–8 |
| 2222J/4 | 4 | 1–2 through 15–16 | |
| 3333J/6 | 6 | 1–2 through 23–24 | |
| 4444J/8 | 8 | 1–2 through 31–32 | |
| 5 | 1x5J/3 | 3 | 1–2 through 11–12 |
| 2x5J/5 | 5 | 1–2 through 19–20 | |
| 3x5J/8 | 8 | 1–2 through 31–32 | |
| 4x5J/10 | 10, reference only | Shown only through 31–32 |
| Terminal pair | 3-position: closed position | 4-position: closed position | 5-position: closed position |
|---|---|---|---|
| 1–2 | 1 | 1 | 1 |
| 3–4 | 2 | 2 | 5 |
| 5–6 | 3 | 3 | 2 |
| 7–8 | 1 | 4 | 3 |
| 9–10 | 2 | 1 | 4 |
| 11–12 | 3 | 2 | 2 |
| 13–14 | 1 | 3 | 3 |
| 15–16 | 2 | 4 | 4 |
| 17–18 | 3 | 1 | 1 |
| 19–20 | 1 | 2 | 5 |
| 21–22 | 2 | 3 | 1 |
| 23–24 | 3 | 4 | 5 |
| 25–26 | 1 | 1 | 2 |
| 27–28 | 2 | 2 | 3 |
| 29–30 | 3 | 3 | 4 |
| 31–32 | 1 | 4 | 2 |

A special × suffix requires a separately defined contact diagram. It does not identify a single switching pattern by itself.
| Program | Position 1 closed pairs | Position 2 closed pairs | Position 3 closed pairs |
|---|---|---|---|
| 424/3 | 1–2, 3–4, 5–6, 7–8 | 9–10, 11–12 | 1–2, 3–4, 5–6, 7–8 |
| 424×/3, illustrated custom schedule | 1–2, 7–8, 11–12 | 5–6, 11–12 | 1–2, 3–4, 5–6, 7–8, 9–10 |
These schedules list the closed pairs at each panel position; unlisted pairs are open. Retain the corresponding internal and external connection links.
| Model | Measurement arrangement | Position, angle → closed pairs |
|---|---|---|
| CLW2-63-YH1/3 | Three phase-to-neutral voltages; N connection and off position | 0, 0° → None A, 90° → 1–2, 9–10 B, 180° → 5–6, 9–10 C, 270° → 3–4, 9–10 |
| CLW2-63-YH2/3 | Three line voltages; off position | 0, 0° → None AB, 90° → 1–2, 7–8 BC, 180° → 1–2, 11–12 CA, 270° → 5–6, 11–12 |
| CLW2-63-YH3/3 | Three line voltages; no N; off position | 0, 0° → None AB, 90° → 1–2, 7–8 BC, 180° → 5–6, 11–12 CA, 270° → 3–4, 9–10 |
| CLW2-63-YH4/2 | Three line voltages; no off position; A/B/C panel marks | A, −90° → 1–2, 7–8 B, 0° → 1–2, 3–4 C, 90° → 3–4, 5–6 |
| CLW2-63-YH12/2 | Three line voltages; no N; off position | 0, 0° → None AB, 90° → 3–4, 5–6 BC, 180° → 5–6, 7–8 CA, 270° → 1–2, 7–8 |
| CLW2-63-YH13/2 | Three phase-to-neutral voltages; N connection; no off position; panel references A72/B100 | A, 90° → 1–2, 7–8 B, 180° → 3–4, 7–8 C, 270° → 5–6, 7–8 |
| CLW2-63-YH22/3 | Three line voltages; no N; off position; panel references A75/B103 | 0, 0° → None AB, 90° → 1–2, 7–8 BC, 180° → 5–6, 11–12 CA, 270° → 3–4, 9–10 |
| CLW2-63-YH5/4 | Three line and three phase-to-neutral voltages; N connection and off position | CA, −135° → 5–6, 11–12 BC, −90° → 1–2, 15–16 AB, −45° → 3–4, 11–12 0, 0° → None AN, 45° → 7–8, 9–10 BN, 90° → 3–4, 13–14 CN, 135° → 1–2, 9–10 |
| CLW2-63-YH6/4 | Three line voltages from each of two supplies; off position | Supply 1 CA, −135° → 3–4, 11–12 Supply 1 BC, −90° → 7–8, 15–16 Supply 1 AB, −45° → 3–4, 15–16 0, 0° → None Supply 2 AB, 45° → 1–2, 9–10 Supply 2 BC, 90° → 5–6, 13–14 Supply 2 CA, 135° → 1–2, 13–14 |
| CLW2-63-YH8/4 | Three line voltages and one phase-to-neutral voltage; N connection and off position | CA, −135° → 5–6, 11–12 BC, −90° → 1–2, 15–16 AB, −45° → 3–4, 11–12 0, 0° → None AN, 45° → 7–8, 9–10 |


Keep the specified CT wiring and shorting contacts. An ammeter position marked 0 can retain closed CT shorting paths.
| Model | Arrangement | Position, angle → closed pairs |
|---|---|---|
| CLW2-63-LH1/2 | Two CTs; no N; 0/A/B/C selection | 0, 0° → 1–2, 5–6 A, 90° → 3–4, 5–6 B, 180° → 3–4, 7–8 C, 270° → 1–2, 7–8 |
| CLW2-63-LH2/4 | Three CTs and N; N/A/B/C selection | N, 0° → 1–2, 3–4, 5–6, 15–16 A, 90° → 1–2, 5–6, 7–8, 11–12 B, 180° → 1–2, 3–4, 7–8, 13–14 C, 270° → 3–4, 5–6, 7–8, 9–10 |
| CLW2-63-LH3/4 | Three CTs; no N; 0/A/B/C selection | 0, 0° → 1–2, 5–6, 7–8 A, 90° → 1–2, 7–8, 13–14 B, 180° → 5–6, 7–8, 9–10 C, 270° → 1–2, 5–6, 15–16 |

| Use code | Application |
|---|---|
| Q | Direct starting of a squirrel-cage motor |
| N | Forward/reverse starting |
| S | Two-speed motor starting and speed selection |
| XS | Star/delta starting |
The motor-use ordering fields include thermal current, use code and motor power in kW, followed by section and option fields. In these examples, 3 denotes 3kW and 1.2 denotes 1.2kW.
| Model | Application | Position, angle → closed pairs |
|---|---|---|
| CLW2-63-Q3/2 | Direct starting; switching off during operation | OFF, 0° → None ON, 45° → 1–2, 3–4, 5–6 |
| CLW2-63-N1.2/3 | Starting, reversing and reverse-current braking | 1, −45° → 3–4, 5–6, 9–10, 11–12 0, 0° → None 2, 45° → 1–2, 7–8, 9–10, 11–12 |
| CLW2-63-S3/4 | Two-speed motor starting and speed selection | 1, −45° → 1–2, 5–6, 7–8, 11–12, 13–14 0, 0° → None 2, 45° → 1–2, 3–4, 5–6, 9–10, 13–14, 15–16 |

Print codes define wording and physical layout. English equivalents below identify the labels; the drawings retain their positions and return arrows. Special printing uses P. Omission retains the contact program's standard printing. The 30° and 22.5° print references do not establish those indexing steps for a standard CLW2-63 mechanism.
| Code group | Layout angle | Content |
|---|---|---|
| A1–A22 | 30° reference | Worded operating and metering plates |
| B1–B59 | 45° | Worded operating, distribution and metering plates |
| C1–C18 | 60° | Worded operating plates |
| D1–D22 | 90° | Worded operating and metering plates |
| E1–E8 | 22.5° reference | Numeric and Auto/Stop/Manual plates |
| F1–F17 | 30° reference | Numeric plates |
| G1–G29 | 45° | Numeric plates |
| H1–H14 | 60° | Numeric plates |
| I1–I11 | 90° | Numeric plates |
| Print code | English wording / symbols |
|---|---|
| A1 / B1 | Raise / 0 / Lower |
| A2 / B2 | Start / 0 / Stop |
| A3 / B3 | Trip / Stop / Close |
| A4 / B4 | Trip / 0 / Close |
| A5 / B5 | Off / 0 / On |
| A6 / B6 | Remote / Stop / Local |
| A7 / B7 | Increase speed / 0 / Decrease speed |
| A8 / B8 | Trip / Disconnect / Close |
| A9 / B9 | Open / 0 / Close |
| A10 / B10 | Close / 0 / Trip |
| A11 / B11 | Trip / 0 / Close |
| A12 | OFF / ON |
| A13 | Trip / 0 / Close |
| A14 | Auto / 0 / Manual |
| A15 | Raise voltage / Stop / Lower voltage |
| A16 | On / Stop / Off |
| A17 | Close / 0 / Trip |
| A18 | Decrease speed / Stop / Increase speed |
| A19 | AB, BC, CA, 0, A, B, C |
| A20 | Auto / Stop / Manual / 2–6 |
| A21 | Auto / Stop / Manual / 2–8 |
| A22 | Auto / Stop / Manual / 2–10 |
| B12 | Remote / Local / Trip / Close, arranged as illustrated |
| B13 | Remote / After trip / After close / Trip / Close |
| B14 / B15 / B16 | Pre-close / After close / Close / Pre-trip / After trip / Trip; three illustrated layouts |
| B17 | Stop / Start |
| B18 | On / Off |
| B19 | Manual / Auto |
| B20 | Insert / Withdraw |
| B21 | Working / Test |
| B22 | Disconnect / Connect |
| B23 | Local / Remote |
| B24 | Switch cabinet / Operator station |
| B25 | Withdraw / Insert |
| B26 | Manual / Auto |
| B27 | Remote / Local |
| B28 | Disconnect / Connect |
| B29 | Auto / Standby |
| B30 | Stop / Start |
| B31 | Field / Remote |
| B32 | Remote / Field |
| B33 | Manual / Remote control |
| B34 | Withdraw / Insert |
| B35 | Interlock / Manual |
| B36 | On / Off |
| B37 | Test / Run |
| B38 | Disconnect / Remote |
| B39 | 1 / 2 / 3 / OFF |
| B40 | Trip / 0 / Close |
| B41 | Auto / Stop / Manual |
| B42 | Trip / 0 / Close |
| B43 | Run / Stop / Test |
| B44 | Increase excitation / Stop / Decrease excitation |
| B45 | Manual / Disconnect / Auto |
| B46 | Decrease speed / Disconnect / Increase speed |
| B47 | Raise voltage / Stop / Lower voltage |
| B48 | Local / Stop / Remote |
| B49 | Manual / Stop / Auto |
| B50 | Parallel / 0 / Separate |
| B51 | Local / 0 / Remote |
| B52 | Local / Disconnect / Remote |
| B53 | Decrease / 0 / Increase |
| B54 | Low voltage / High voltage |
| B55 | Local / 0 / Remote control |
| B56 | Parallel / 0 / Separate |
| B57 | Working / Stop / Standby |
| B58 | 0 and two sets of UAB / UBC / UCA |
| B59 | 0, UAB / UBC / UCA and UA / UB / UC |
| C1 | Manual / Auto |
| C2 | Remote / Local |
| C3 | Local / Remote |
| C4 | Trip / Close |
| C5 | Off / On |
| C6 | Auto / Manual |
| C7 | Manual / Auto |
| C8 | Parallel / Release |
| C9 | Auto / Manual |
| C10 | Local / Remote |
| C11 | Remote / Local |
| C12 | Trip / Disconnect / Close |
| C13 | Decrease speed / Disconnect / Increase speed |
| C14 | Manual / Stop / Auto |
| C15 | Auto / Stop / Manual |
| C16 | Local / Release / Remote |
| C17 | Manual / Reset / Auto |
| C18 | Remote / Local |
| D1 | Manual / Auto |
| D2 | Local / Remote |
| D3 | Auto / Manual |
| D4 | Remote / Local |
| D5 | Trip / Close |
| D6 | On / Off |
| D7 | Field / Remote |
| D8 | Close / Trip |
| D9 | Release / Parallel |
| D10 | Test / Run |
| D11 | Disabled / Enabled |
| D12 | Trip / Close |
| D13 | Field / Remote |
| D14 | Withdraw / Insert |
| D15 | Interlock / Release |
| D16 | IA / IB / IC |
| D17 | UAB / UBC / UCA |
| D18 | UA / UB / UC |
| D19 | 0, UA / UB / UC |
| D20 | 0, UAB / UBC / UCA |
| D21 | 0, IA / IB / IC |
| D22 | 0, IAB / IBC / ICA |
| E1 | 0–12 |
| E2 | 0–13 |
| E3 | Auto / Stop / Manual / 2–11 |
| E4 | Auto / Stop / Manual / 2–12 |
| E5 | Auto / Stop / Manual / 2–13 |
| E6 | Auto / Stop / Manual / 2–14 |
| E7 | 0–15 |
| E8 | 0–16 |


| Numeric print code | Printed numbers / return marks |
|---|---|
| F1 / G1 | 0 ← 1 |
| F2 / G2 | 1 ← 2 |
| F3 / G3 | 1 → 0 ← 2 |
| F4 / G4 | 1 → 2 ← 3 |
| F5 | 0, 1 |
| F6 | 1, 2 |
| F7 | 0, 1, 2 |
| F8 | 1, 0, 2 |
| F9 | 1, 2, 3 |
| F10 | 2, 1, 0, 1, 2 |
| F11 | 1–5 |
| F12 | 0–4 |
| F13 | 0–5 |
| F14 | 3, 2, 1, 0, 1, 2, 3 |
| F15 | 0–7 |
| F16 | 0–8 |
| F17 | 0–11 |
| G5 / G6 | 0, 1; distinct layouts |
| G7 | 1, 0 |
| G8 / G9 | 1, 2; distinct layouts |
| G10 | 0, 1, 2 |
| G11 | 1, 0, 2 |
| G12 / G13 | 1, 2, 3; distinct layouts |
| G14 | 1, 0, 1, 2 |
| G15 / G16 | 1–4; distinct layouts |
| G17 | 0–4 |
| G18 | 2, 1, 0, 1, 2 |
| G19 / G20 | 1–5; distinct layouts |
| G21 | 0–5 |
| G22 | 1–6 |
| G23 | 2, 1, 0, 1, 2, 3 |
| G24 | 0–6 |
| G25 | 1–7 |
| G26 | 0–7 |
| G27 | 1–8 |
| G28 | 0–7, circular layout |
| G29 | 1–8, circular layout |
| H1 | 0, 1 |
| H2 / H3 / H4 | 1, 2; distinct layouts |
| H5 | 0, 1 |
| H6 | 1, 0, 2 |
| H7 | 1, 2, 3 |
| H8 | 0, 1, 2 |
| H9 | 0–3 |
| H10 | 1–4 |
| H11 | 1–5 |
| H12 | 2, 1, 0, 1, 2 |
| H13 | 1–6 |
| H14 | 0–5 |
| I1 / I3 | 0, 1; distinct layouts |
| I2 / I4 / I5 | 1, 2; distinct layouts |
| I6 | 0, 1, 2 |
| I7 | 1, 0, 2 |
| I8 | 1, 2, 3 |
| I9 / I11 | 0–3; distinct layouts |
| I10 | 1–4 |

Specify thermal current, mechanical function, handle code, panel wording, operating directions and the contact state of every required pair at each position. The worksheet has eight sections, with pairs 1–2 through 31–32; the chosen mechanism's section limit still applies.

The standard minimum applicable load is 24VDC, 10mA. Smaller signals require an appropriate small-load contact configuration. Contacts used for general loads should not subsequently be reused for smaller signals, because surface changes can reduce low-current reliability. Use suitable CR suppression and contact protection where bounce, noise or pulse currents affect the circuit.

These switches are intended for industrial controls. High-reliability infrastructure, safety-critical transport or medical systems, severe outdoor or contaminated environments, fire or explosion hazards, military uses and large engineering projects require a specifically designed and expressly confirmed configuration.