CLN LCD PID Temperature Controllers with Output Options

Series Part Number

Part Number: CLN 4 S - 4 3A 1 R
Explanation:

Series

CLN - LCD dual display PID temperature controller

Display Digits

4 - Four-digit, 9999 format with separate PV and SV rows

Panel Format

S - 48×48mm
V - 48×96mm
M - 72×72mm
L - 96×96mm
H - 96×48mm guide option, without a separate photograph, common-model table or detailed outline in the document. Use the actual version's mechanical drawing for installation.

Power Supply

2 - 24–48VAC/DC; AC frequency 50/60Hz
4 - 100–240VAC, 50/60Hz
A–Z combinations - Other custom supply versions; use the exact code supplied for the specified version.

Control Output

1 - Relay output
2 - SSR logic drive
3A - Analog current option, 0–20mA or 4–20mA; the complete common 43A1 models specify 4–20mA
3B - Analog voltage option, 0–5V or 1–5V
4 - SCR zero-crossing output
5 - Built-in 5A SCR
6 - Relay plus SSR drive
A–Z combinations - Custom output versions; exact code accompanies the ordered configuration.

Alarm Output

1 - One relay alarm
2 - Two relay alarms
3 - One solid-state alarm
4 - Two solid-state alarms
A–Z combinations - Custom alarm versions. Complete common models use relay alarms.

Temperature Input

Blank - Universal input without a suffix: thermocouples K, E, J, L, T, R and S, or RTDs Pt100 and Cu50
A–Z combinations - Custom input version; exact code accompanies the specified sensor configuration. The displayed common example uses the default universal input.

Retransmission Output

Blank - No separate retransmission output; omit the code
T - Retransmission output. The documented R and T model selections are separate; the displayed R example does not add an unlisted combined TR suffix.

Communication

Blank - No communication function; omit the code
R - RS485 communication

Description

CLN LCD Temperature Controllers

CLN controllers use a large segmented LCD to show the measured process value, PV, and the setpoint, SV, on separate rows. The range combines a 32-bit MCU, a 100ms sampling interval, the manufacturer's AI adjustment algorithm and automatic tuning. PID heating, PID cooling, ON/OFF heating and ON/OFF cooling are available control modes.

Four photographed panel formats cover 48×48mm, 48×96mm, 72×72mm and 96×96mm installations. Select relay, SSR drive or analog control hardware together with the required alarm and expansion functions. RS485 communication, primary analog control and separate retransmission output are distinct choices; the display and keypad alone do not identify which interfaces are installed.

Series Part Number and Configuration Choices

CLN model ordering diagram with nine configuration fields
CLN ordering layout. Default input and omitted expansion functions contribute no suffix characters.
FieldCodes and meaningSelection condition
Series / digitsCLN: LCD dual display PID controller; 4: four-digit, 9999 display formatThe display format does not specify a temperature measuring range.
Panel formatS: 48×48mm; V: 48×96mm; M: 72×72mm; L: 96×96mm; H: 96×48mmS, V, M and L have photographs, detailed drawings and complete common models. H is a wider guide option without those separate details in this document.
Supply2: 24–48VAC/DC; 4: 100–240VAC; A–Z letter combinations: other custom supply versionsAC supply frequency is 50/60Hz. The complete common models below use code 4.
Control output1: relay; 2: SSR drive; 3A: analog current, 0–20mA or 4–20mA; 3B: analog voltage, 0–5V or 1–5V; 4: SCR zero-crossing output; 5: built-in 5A SCR; 6: relay plus SSR driveThe common 43A1 selections specify 4–20mA control. Other letter combinations describe custom output versions.
Alarm output1: one relay alarm; 2: two relay alarms; 3: one solid-state alarm; 4: two solid-state alarms; letter combinations: custom alarm versionUse the actual hardware alarm arrangement; common full models use relay alarms.
Temperature inputNo code: thermocouples K, E, J, L, T, R or S; RTDs Pt100 or Cu50. Letter combinations: custom input versionThe common models use the default universal input. Configure the selected sensor type before operation.
RetransmissionNo code: absent; T: retransmission outputSeparate from the primary control output; no specific retransmission signal range is stated in this selection table.
CommunicationNo code: absent; R: RS485The full model tables document R and T variants separately.

Custom letter codes represent a specified version, rather than a freely interchangeable suffix. Order the exact code supplied for the required custom supply, output or input configuration.

44 Complete Common Models

All models in this table use 100–240VAC and universal thermocouple/RTD input. The configuration column identifies the control interface, relay alarm count and any additional output or communication function.

Configuration48×48mm48×96mm72×72mm96×96mm
Relay control; one relay alarmCLN4S-411CLN4V-411CLN4M-411CLN4L-411
Relay control; two relay alarmsCLN4S-412CLN4V-412CLN4M-412CLN4L-412
SSR drive; one relay alarmCLN4S-421CLN4V-421CLN4M-421CLN4L-421
SSR drive; two relay alarmsCLN4S-422CLN4V-422CLN4M-422CLN4L-422
Relay plus SSR drive; one relay alarmCLN4S-461CLN4V-461CLN4M-461CLN4L-461
4–20mA control; one relay alarmCLN4S-43A1CLN4V-43A1CLN4M-43A1CLN4L-43A1
Relay control; one relay alarm; RS485CLN4S-411RCLN4V-411RCLN4M-411RCLN4L-411R
SSR drive; one relay alarm; RS485CLN4S-421RCLN4V-421RCLN4M-421RCLN4L-421R
4–20mA control; one relay alarm; RS485CLN4S-43A1RCLN4V-43A1RCLN4M-43A1RCLN4L-43A1R
Relay control; one relay alarm; retransmissionCLN4S-411TCLN4V-411TCLN4M-411TCLN4L-411T
SSR drive; one relay alarm; retransmissionCLN4S-421TCLN4V-421TCLN4M-421TCLN4L-421T

Electrical and Operating Specifications

CharacteristicSpecified value
Supply100–240VAC or optional 24–48VAC/DC; AC frequency 50/60Hz
Power consumptionNo more than 5VA
Sampling / measurement accuracy100ms / ±0.5%FS
Resolution1°C or 0.1°C, adjustable
Operating environment−10°C to +60°C; 35–85%RH, without condensation
Storage environment−25°C to +65°C; avoid freezing and condensation
Memory / connectionNonvolatile memory / terminal wiring
Installation conditionsInstallation category II; pollution degree 2
Relay control output3A at 220VAC or 30VDC
SSR logic driveON: 12VDC or 24VDC according to the output version; OFF: below 0.5VDC; maximum current 30mA

SSR drive is a control signal for an external solid-state relay, rather than a heater power output. The catalog's separate contact certification entries list AC-15 at 380VAC and 250VAC, 3A, and DC-12 at 24–48VDC, 3A. Those entries do not increase the controller supply range or replace its relay output specification. CE and EN61010-1 are referenced in the catalog; obtain the applicable document from CNTD when required for a project.

Panel Cutouts and Dimensions

Dimensions are in millimeters. Cutout lower deviations are zero. Installation spacing is measured between the centers of adjacent cutouts.

Panel formatFront sizeNominal shell sizeCutoutMinimum horizontal × vertical centers
CLN4S48×4848×48×7145(+0.6/0)×45(+0.6/0)65×65
CLN4V48×9648×96×7146(+0.6/0)×92(+0.8/0)65×115
CLN4M72×7272×72×7168(+0.7/0)×68(+0.7/0)90×90
CLN4L96×9696×96×7192(+0.8/0)×92(+0.8/0)115×115

The wider guide also names H, a 96×48mm horizontal option. Its general table lists a nominal 96×48×71mm shell and a 91×45mm opening, but provides no separate full model selection, photograph or detailed H outline. Treat that entry as a guide reference and obtain the actual version's mechanical drawing before preparing its panel.

Panel formatFront / rear side-view calloutsAdditional side-view dimension
CLN4S6.5 / 67.955.3
CLN4V6 / 6591.5
CLN4M6 / 6567
CLN4L6 / 6591.5

Reserve space for the individual side-view dimensions, mounting clips, terminals and wiring. For CLN4S, check the separate 6.5mm and 67.9mm callouts rather than using the nominal 71mm shell entry alone.

LCD Indication and Key Functions

CLN LCD front panel with PV and SV rows, output and alarm indications, and four keys
LCD indication and front panel key layout, with the operating parameter reference supplied in the selection document.
Display or keyFunction
PV / SVPV shows the measured value and status prompts; SV shows the setpoint and parameter values.
OUTHeating/output indication, lit while the output is operating
AL1 / AL2High-limit / low-limit alarm indication, lit during the corresponding alarm
UpIncrease values, enter manual mode and switch menu/parameter items
DownDecrease values and switch menu/parameter items
Left shift / ATShift the selected digit and enter the tuning state
ModeEnter main/submenus, modify parameters and confirm settings

The LCD layout also shows OUT1, OUT2, AT, RSV, MAN, PGM, AL3, SV1, SV2, SV3 and °C/°F/% segments. These are display legends; their presence does not independently specify extra alarm hardware, program control or additional setpoint functions in a particular ordered model.

Control Loop and Use Conditions

The example heater loop returns the sensor signal to the controller and switches the heater through an external SSR. ON/OFF control and manual output are illustrated, including 50% and 80% output examples over a 50-cycle window. Match the sensor, output interface, power switching device and protective functions to the actual process.

The manufacturer requires specially designed equipment and written confirmation for high reliability energy systems, applications involving personal safety or major property risk, harsh or outdoor environments, fire or explosion risks, and military or aerospace use.