CJY/M Cylindrical Inductive Sensors with M12 Connectors

Description

CNTD CJY/M cylindrical inductive proximity sensors use a direct male M12 four-pin A-coded connector for metal-position detection. Sensing housings in M12, M18 and M30 sizes cover 2–15mm nominal distances with flush or nonflush installation. Nickel-plated brass bodies, red operating LEDs and IP65 protection support ordinary industrial sensing within the specified environmental limits.

Transistor Output Models

All transistor models use 10–30VDC. DNA/DNB are NPN NO/NC; DPA/DPB are PNP NO/NC; DNC/DPC provide NO+NC outputs. The single-output connector drawing does not define both conductors of a combined-output version.

Head / nominal distanceNPN choicesPNP choices
M12 / 2mm, flushCJY12-02DNA/M
CJY12-02DNB/M
CJY12-02DNC/M
CJY12-02DPA/M
CJY12-02DPB/M
CJY12-02DPC/M
M12 / 4mm, nonflushCJY12-04DNA/M
CJY12-04DNB/M
CJY12-04DNC/M
CJY12-04DPA/M
CJY12-04DPB/M
CJY12-04DPC/M
M18 / 5mm, flushCJY18-05DNA/M
CJY18-05DNB/M
CJY18-05DNC/M
CJY18-05DPA/M
CJY18-05DPB/M
CJY18-05DPC/M
M18 / 8mm, nonflushCJY18-08DNA/M
CJY18-08DNB/M
CJY18-08DNC/M
CJY18-08DPA/M
CJY18-08DPB/M
CJY18-08DPC/M
M30 / 10mm, flushCJY30-10DNA/M
CJY30-10DNB/M
CJY30-10DNC/M
CJY30-10DPA/M
CJY30-10DPB/M
CJY30-10DPC/M
M30 / 15mm, nonflushCJY30-15DNA/M
CJY30-15DNB/M
CJY30-15DNC/M
CJY30-15DPA/M
CJY30-15DPB/M
CJY30-15DPC/M

Two-Wire Model Selection

Housing / distanceDC two-wire NO / NCAC two-wire NO / NC
M12 / 2mmCJY12-02DLA/M
CJY12-02DLB/M
No model listed
M12 / 4mmCJY12-04DLA/M
CJY12-04DLB/M
CJY12-04AKA/M
CJY12-04AKB/M
M18 / 5mmCJY18-05DLA/M
CJY18-05DLB/M
CJY18-05AKA/M
CJY18-05AKB/M
M18 / 8mmCJY18-08DLA/M
CJY18-08DLB/M
CJY18-08AKA/M
CJY18-08AKB/M
M30 / 10mmCJY30-10DLA/M
CJY30-10DLB/M
CJY30-10AKA/M
CJY30-10AKB/M
M30 / 15mmCJY30-15DLA/M
CJY30-15DLB/M
CJY30-15AKA/M
CJY30-15AKB/M

Sensing Performance

Model groupSetting rangeStandard iron targetTransistor frequencyDC two-wire frequency
CJY12-02/M, 2mm nominal0–1.4mm12×12×1mm1000Hz1000Hz
CJY12-04/M, 4mm nominal0–2.8mm500Hz500Hz
CJY18-05/M, 5mm nominal0–3.5mm18×18×1mm500Hz500Hz
CJY18-08/M, 8mm nominal0–5.6mm25×25×1mm350Hz350Hz
CJY30-10/M, 10mm nominal0–7mm30×30×1mm400Hz standard; 350Hz premium version350Hz
CJY30-15/M, 15mm nominal0–10.5mm45×45×1mm200Hz200Hz

All AC two-wire models are 20Hz. Frequencies are average values using the specified standard target, an interval between successive targets equal to twice the target width, and a target-to-sensor gap equal to half the nominal detection distance. Use the setting range to choose the operating gap.

Electrical Ratings

ParameterNPN / PNPDC two-wireAC two-wire
Operating voltage10–30VDC90–250VAC
Maximum output current200mA
Leakage current≤10mA≤0.6mA≤10mA
Residual voltage≤1V≤3.5V≤10V
Protection circuitSurge, reverse-polarity and overcurrent protectionSurge protection
Hysteresis≤10% of nominal sensing distance
Temperature influenceWithin ±10% of the sensing distance at 20°C over −25 to +70°C

Connector Wiring

Standard and IEC DC two-wire pinouts are different. Match the sensor variant to the cable assembly. Use the connector-face drawings in the attachment for pin numbering and orientation; the same M12 housing does not guarantee the same circuit assignment.

ConfigurationActive connectionsOther pinsLoad connection
Standard DC two-wire, NO or NCPin 4: brown / positive side; pin 3: blue / 0V sidePins 1 and 2 unusedLoad and sensor in series; load can be placed in either lead
IEC DC two-wire, NOPin 1: brown / positive side; pin 4: blue / 0V sidePins 2 and 3 unused
IEC DC two-wire, NCPin 1: brown / positive side; pin 2: blue / 0V sidePins 3 and 4 unused
Single-output NPNPin 1: brown / +V; pin 3: blue / 0V; pin 4: black / outputPin 2 not assigned in the single-output diagramBetween +V and pin 4
Single-output PNPPin 1: brown / +V; pin 3: blue / 0V; pin 4: black / outputPin 2 not assigned in the single-output diagramBetween pin 4 and 0V
AC two-wire, NO or NCBrown and blue are the two sides of the switching circuitPins 1 and 4 internally connected; pins 2 and 3 internally connectedSeries load on 90–250VAC; load may be in either lead

When a conventional DC three-wire cordset is used with the standard DC two-wire configuration, its black conductor on pin 4 is the positive-side connection and blue on pin 3 is 0V; brown on pin 1 is unused. The connector tightening torque is 0.39–0.49N·m. Secure the cable and connection with tape where vibration occurs, as described in the installation instructions. Complete output circuits and NO/NC timing charts remain in the attachment.

Ordering Code

Ten numbered positions in a CJY/M connector inductive sensor ordering code
CJY/M model layout with a direct M12 connector suffix.
PositionCode fieldMeaning
1CJInductive sensing
2Housing shapeY=cylindrical metal; YG=cylindrical stainless steel; YS=cylindrical plastic. Full models above use Y; the other guide choices do not add unlisted full model combinations.
3Size12=M12, 18=M18, 30=M30 for the listed models. The general guide also identifies 08=M8 without a corresponding full model here.
4Product typeBlank=standard
5Thread lengthBlank=standard; L=long thread. Dimensions below apply to the illustrated standard bodies.
6Detection distance02=2mm; 04=4mm; 05=5mm; 08=8mm; 10=10mm; 15=15mm
7VoltageA=90–250VAC; D=10–30VDC. E=20–60VDC and J=5–10VDC appear as general guide choices, without additional full models in these selection tables.
8Output circuitN=NPN; P=PNP; K=AC two-wire; L=DC two-wire
9StateA=NO; B=NC; C=NO+NC
10MStraight male M12 four-pin A-coded connector, after the slash in the full model

Housing Dimensions

Model / installationSensing threadOverall axial referenceThread-length referenceFront projectionNut reference
CJY12-02/M, flushM12×165mm50mmFlushØ21mm, 17mm across flats, 4mm thick
CJY12-04/M, nonflush60mm45mm7mm
CJY18-05/M, flushM18×165mm50mmFlushØ29mm, 24mm across flats, 4mm thick
CJY18-08/M, nonflush60mm45mm10mm
CJY30-10/M, flushM30×1.565mm50mmFlushØ41mm, 36mm across flats, 5mm thick
CJY30-15/M, nonflush60mm45mm11mmØ41mm, 35mm across flats as drawn, 5mm thick

Every illustrated rear connector has an M12×1 thread. Axial references follow the endpoints in the attachment and include the illustrated connector body, without a separate cordset. Indicator locations and mounting-nut geometry are retained in the dimension drawings.

Installation Spacing and Surrounding Metal

The values below are millimeters. A is face-to-face spacing and B is parallel spacing as drawn. n is the head-exposure reference; Ød is the surrounding-metal opening diameter; ℓ and m use the axial and surrounding-metal endpoints in the installation drawing.

GroupABnØdℓm
CJY12-02/M1224012618
CJY12-04/M243611361236
CJY18-05/M30360181527
CJY18-08/M485414542454
CJY30-10/M60600303045
CJY30-15/M909015904590

Environmental and Mechanical Specifications

ItemSpecification
Protection / indicationIP65; red operating LED
Operating / storage temperature−25 to +70°C / −30 to +80°C, without icing
Humidity35–95%RH without condensation
Insulation resistance≥50MΩ at 500VDC
Dielectric strength1500VAC at 50/60Hz for 1min
Vibration1mm amplitude, 10–55Hz in a 1min sweep, 2h per X/Y/Z direction
Shock500m/s², approximately 50G, three times per X/Y/Z direction
Materials of the listed Y modelsNickel-plated brass case and nuts, nickel-plated iron washers, PBT sensing face
Referenced standardsCCC: GB/T14048.10; TÜV and CE: EN60947-5-2. Supporting certification documents are not supplied in the guide.
Utilization-category referencesDC-13: 10–30VDC, 200mA; AC-140: 24–250VAC, 200mA. Individual model operating-voltage ratings remain those in the electrical table.

Application Conditions

Use for ordinary industrial metal-position detection within the stated target, gap, circuit and mounting conditions. Regional specifications can differ. The manufacturer excludes personnel-safety functions, exceptionally high-reliability nuclear, gas and power systems, severe outdoor or contaminated conditions, fire or explosion hazards, strong acids or alkalis, and military or aerospace applications unless specifically designed and confirmed for that use.