CJY-S Long Range Cylindrical Inductive Proximity Sensors

Description

CNTD CJY-S long range cylindrical inductive proximity sensors detect metal at 2–25mm nominal distances in M8, M12, M18 and M30 housings. Flush and nonflush heads combine nickel-plated brass bodies, red operating LEDs and IP67 protection. The manufacturer describes nominal sensing distances approximately 1.5–2 times those of its existing standard models; choose the actual operating gap from the model-specific setting range below.

Model and Output Selection

The listed models use 10–30VDC transistor circuits. DNA/DNB are NPN NO/NC; DPA/DPB are PNP NO/NC. DNC/DPC provide complementary NO+NC outputs and require four conductors. M8 models list single outputs only.

Housing and sensing distanceNPN modelsPNP models
M8 / 2mm, flushCJY08S-02DNA
CJY08S-02DNB
CJY08S-02DPA
CJY08S-02DPB
M8 / 4mm, nonflushCJY08S-04DNA
CJY08S-04DNB
CJY08S-04DPA
CJY08S-04DPB
M12 / 4mm, flushCJY12S-04DNA
CJY12S-04DNB
CJY12S-04DNC
CJY12S-04DPA
CJY12S-04DPB
CJY12S-04DPC
M12 / 8mm, nonflushCJY12S-08DNA
CJY12S-08DNB
CJY12S-08DNC
CJY12S-08DPA
CJY12S-08DPB
CJY12S-08DPC
M18 / 10mm, flushCJY18S-10DNA
CJY18S-10DNB
CJY18S-10DNC
CJY18S-10DPA
CJY18S-10DPB
CJY18S-10DPC
M18 / 16mm, nonflushCJY18S-16DNA
CJY18S-16DNB
CJY18S-16DNC
CJY18S-16DPA
CJY18S-16DPB
CJY18S-16DPC
M30 / 20mm, flushCJY30S-20DNA
CJY30S-20DNB
CJY30S-20DNC
CJY30S-20DPA
CJY30S-20DPB
CJY30S-20DPC
M30 / 25mm, nonflushCJY30S-25DNA
CJY30S-25DNB
CJY30S-25DNC
CJY30S-25DPA
CJY30S-25DPB
CJY30S-25DPC

Operating Gap and Response

GroupNominal distanceSetting distanceStandard iron targetAverage response frequency
CJY08S-022mm0–1.05mm8×8×1mm450Hz
CJY08S-044mm0–2.1mm400Hz
CJY12S-044mm0–2.8mm12×12×1mm
CJY12S-088mm0–4.9mm25×25×1mm300Hz
CJY18S-1010mm0–7mm20×20×1mm
CJY18S-1616mm0–10.5mm40×40×1mm200Hz
CJY30S-2020mm0–11.9mm45×45×1mm100Hz
CJY30S-2525mm0–17.5mm75×75×1mm

Use the stated setting range directly; it is not a single fixed percentage of nominal distance across this family. Response frequency is an average measured with the specified standard target, spacing between successive targets equal to twice the target width, and a sensing gap of half the nominal distance.

Electrical and Environmental Ratings

ItemSpecification for listed NPN / PNP models
Operating voltage / control output10–30VDC; 200mA maximum
Leakage current / residual voltage≤10mA / ≤1V
Hysteresis≤10% of nominal sensing distance
Temperature influenceWithin ±10% of the sensing distance at 20°C over −25 to +70°C
Protection circuitSurge, reverse-polarity and overcurrent protection
Enclosure protection / indicatorIP67; red operating LED
Operating / storage temperature−25 to +70°C / −30 to +80°C, without icing
Humidity35–95%RH, without condensation
Insulation resistance≥50MΩ at 500VDC
Dielectric strength1500VAC, 50/60Hz, 1min
Vibration1mm amplitude, 10–55Hz swept over 1min, 2h per X/Y/Z direction
Shock500m/s², approximately 50G, three times per X/Y/Z direction
MaterialsNickel-plated brass case and nuts; nickel-plated iron washers; PBT sensing face

Cable Specification

HousingOutside diameterLengthConductorsStrands per conductor
M82.8mm2m3P22
M123.8mm3P for single NO/NC; 4P for NO+NC25
M18 / M304.8mm30

The cable specification identifies AWG22, 0.1mm individual strand diameter and 1.25mm conductor insulation outside diameter. The 22/25/30 figures are strand counts within each conductor. Standard cable is gray PVC; black oil-resistant PVC is also described.

Ordering Code Layout

Twelve numbered positions in a CJY-S long range inductive sensor ordering code
CJY-S ordering layout with the S long range designation and cable options.
PositionFieldKnown choices
1CJInductive sensing
2Shape / housingY=cylindrical metal. The guide additionally labels RG as cylindrical stainless steel and RS as cylindrical plastic; full models in this selection use Y.
3Size08=M8; 12=M12; 18=M18; 30=M30
4SLong range type
5Thread lengthBlank=standard; L=long thread. Illustrated dimensions apply to the standard bodies.
6Detection distance02=2mm; 04=4mm; 08=8mm; 10=10mm; 16=16mm; 20=20mm; 25=25mm
7SupplyD=10–30VDC for all listed models. A=90–250VAC and E=20–60VDC are general guide options, without corresponding full models in these tables.
8OutputN=NPN; P=PNP. K=AC two-wire and L=DC two-wire are described in the general guide, without full two-wire models in this selection.
9StateA=NO; B=NC; C=NO+NC, with C limited to the groups that list it
10ConnectionBlank=free-ended cable; M=straight male M12 four-pin A-coded connector. M-type, DT, AMP and SM connector configurations also appear with undefined individual subcodes.
11Cable materialBlank=PVC; U=PUR; VP=shielded PVC; UP=shielded PUR
12Lead lengthBlank is shown for a direct M-type connector body; L1–L5 are lead-length choices, with L1=1m and lengths not restricted to L5. Standard prewired models have 2m cable.

Housing Dimensions

Group / mountingThreadOverall axial referenceThread referenceFront projectionNut reference
CJY08S-02, flushM8×152mm38mmFlushØ15mm; 13mm across flats; 3mm thick
CJY08S-04, nonflush47mm32mm5mm
CJY12S-04, flushM12×158mm38mmFlushØ21mm; 17mm across flats; 4mm thick
CJY12S-08, nonflush53mm32mm7mm
CJY18S-10, flushM18×166mm38mmFlushØ29mm; 24mm across flats; 4mm thick
CJY18S-16, nonflush68mm32mm10mm
CJY30S-20, flushM30×1.564mm38mmFlushØ41mm; 36mm across flats; 5mm thick
CJY30S-25, nonflush59mm32mm11mm

Dimensions follow the illustrated axial endpoints, excluding the free cable. The attachment retains complete drawings of the sensing head, cable exit, indicator and nut positions.

Installation Clearances

All values are millimeters. A is face-to-face spacing; B is parallel spacing; n is the head-exposure reference; Ød is the surrounding-metal opening diameter; ℓ and m follow the axial and surrounding-metal endpoints in the attached drawing.

GroupABnØdℓm
CJY08S-02916084.512
CJY08S-041224824624
CJY12S-0424240121218
CJY12S-08483611362436
CJY18S-1042360182127
CJY18S-16845414544254
CJY30S-2090600304545
CJY30S-251509015907590

Wiring and External Input Examples

For single outputs, brown is +V, blue is 0V and black is the switching output. An NPN load connects between +V and black; a PNP load connects between black and 0V. In the optional M12 single-output connector diagram, pin 1 is brown, pin 3 is blue and pin 4 is black. The diagrams do not assign the extra conductor of NO+NC models.

External device exampleBrown / blue supply leadsBlack output lead
PA10-U input 19 (+12V) / 10 (GND)11 (IN1)
PA10-U input 213 (+12V) / 14 (GND)15 (IN2)
FX4 counter10 (+12V) / 11 (0V)8 (CP1)

The FX4 drawing has a separate 100–240VAC counter supply; the sensor receives 12VDC in that example. For a connector-terminated configuration, the installation note gives 0.39–0.49N·m tightening torque and calls for securing the cable connection with tape where vibration occurs. Circuit, connector-face and NO/NC timing diagrams remain in the attachment.

Standards and Application Conditions

The guide references CCC to GB/T14048.10 and TÜV/CE to EN60947-5-2, without supplying supporting certification documents. Utilization references are DC-13 at 10–30VDC, 200mA and AC-140 at 24–250VAC, 200mA; the AC reference does not create an AC model in the DC selection above.

Use for ordinary industrial metal-position sensing within the specified target, gap, load and mounting conditions. Regional specifications can differ. The manufacturer excludes personnel-safety functions, exceptionally high-reliability nuclear, gas and power systems, harsh outdoor or contaminated environments, fire or explosion hazards, strong acids or alkalis, and military or aerospace applications unless specifically designed and confirmed for that purpose.