CJX2 Three Phase Motor Contactors

Description

CJX2 contactors provide remote switching and frequent starting or stopping of three-phase AC motors. The family operates on 50/60Hz circuits up to 660V. The selection tables below cover 19 models from 9A to 620A at 380V in AC-3 duty; current ratings at 660V and in AC-4 duty must be selected separately.

A compatible thermal overload relay or electronic protective device can be combined with the contactor to form a magnetic starter. Stackable auxiliary contacts, pneumatic delay contacts and mechanical interlocks support delayed switching, interlocked contactor assemblies and star-delta starters. Screw fixing and 35mm or 75mm rail mounting depend on the frame and accessory arrangement.

Operating Current and Thermal Current

AC-3 and AC-4 are different utilization categories. Use the rating for the actual supply voltage and switching duty. Conventional thermal current is a separate heating limit and does not replace the applicable motor-switching current.

Model380V current (A)660V current (A)Conventional thermal current (A)
AC-3AC-4AC-3AC-4
CJX2-0993.56.61.525
CJX2-121258.9225
CJX2-18187.7123.832
CJX2-25258.5184.440
CJX2-323212217.550
CJX2-404018.534960
CJX2-505024391280
CJX2-656528421480
CJX2-8080374917.3125
CJX2-9595445521.3125
CJX2D115115528649250
CJX2D1501506010761250
CJX2D1701707511069250
CJX2D2052058513080275
CJX2D24524510517090315
CJX2D300300117225118400
CJX2D410410138305135500
CJX2D475475147355145700
CJX2D6206201804601701000

Three-Phase Motor Power

These power ratings apply to three-phase squirrel-cage motors in AC-3 duty. Match both the motor voltage and its current to the selected contactor.

Model220V motor (kW)380V motor (kW)660V motor (kW)
CJX2-092.245.5
CJX2-1235.57.5
CJX2-1847.510
CJX2-255.51115
CJX2-327.51518.5
CJX2-401118.530
CJX2-50152233
CJX2-6518.53037
CJX2-80223745
CJX2-95254555
CJX2D115305580
CJX2D1504075100
CJX2D1705590110
CJX2D20563110129
CJX2D24575132160
CJX2D300100160220
CJX2D410110220280
CJX2D475147265335
CJX2D620200335450

Switching Frequency, Endurance and Fuses

Frequency limits are operations per hour. Endurance figures in the next table are multiples of 10,000 operations: for example, 100 means 1,000,000 operations. The mechanical frequency and endurance relate to operation without switching the motor load. A dash means that the selection table gives no fuse model for that frame.

ModelMaximum operating frequency (operations/h)Endurance (×10⁴operations)Listed fuse
AC-3AC-4MechanicalAC-3 electricalAC-4 electricalMechanical
CJX2-0912003003600100201000RT00-16
CJX2-1212003003600100201000RT00-20
CJX2-1812003003600100201000RT00-25
CJX2-2512003003600100201000RT00-32
CJX2-3260030036008020800RT00-50
CJX2-4060030036008015800RT00-63
CJX2-5060030036008015800RT00-80
CJX2-6560030036008015800RT00-100
CJX2-8060030036006010600RT00-125
CJX2-9560030036006010600RT16-160
CJX2D11560015024006015600RT16-250
CJX2D15060015024006015600RT16-315
CJX2D17060015024006015600RT16-400
CJX2D20560015024005015600RT16-500
CJX2D24560015024005015600RT16-630
CJX2D30060015024005015600RT16-630
CJX2D41030015024005015600—
CJX2D4753001502400308500—
CJX2D6203001502400205500—

The family specification references IEC60947-4-1 and GB14048.4. Select the overload relay, short-circuit protection and control coil for the complete starter circuit; a frame designation alone does not specify the coil supply.

Outline and Accessory Clearances

Dimensions below are in millimetres. Cmax is the contactor depth, C1 is the depth with an F4 auxiliary block, and C2 is the depth with an SK2-2/3 accessory. The D115/D150/D170 drawing uses the same symbols as the smaller frames; retain the exact assembly clearance required by the selected accessory.

Drawing model groupamax (mm)Cmax (mm)C1 (mm)C2 (mm)
CJX2-09 / CJX2-124782115134
CJX2-184787120139
CJX2-255997130149
CJX2-3259102135154
CJX2-40 / CJX2-50 / CJX2-6579116149168
CJX2-80 / CJX2-9587127160179
CJX2-D115 / CJX2-D150 / CJX2-D170120132155168
CJX2 contactor outlines, fixing holes and accessory depths
Frame-specific mounting drawings for CJX2-09 through CJX2-95 and CJX2-D115/D150/D170. The drawings also show rail and fixing-hole details; no larger-frame outline is specified here.