| Part Number: | C | H | 6 | S | - | 2P | 2 |
|---|---|---|---|---|---|---|---|
| Explanation: |
Prefix C - Fixed brand prefix |
Product Series H - Counter/timer series |
Display Digits 6 - Six-digit display, integer maximum 999999; used by the six listed models |
Front Size S - 48×48mm |
Preset Stages 1P - One-stage setting |
Supply Voltage 4 - 100–240VAC, 50/60Hz |
CH6 combines preset counting and timing in 48mm and 72mm panel instruments. Counter operation offers nine input patterns, eleven output modes, batch counting and an adjustable initial count. Timer operation offers thirteen output modes, forward/countdown timing, twelve time formats and power-off memory.
| Model | Front size | Preset stages | Supply | Display |
|---|---|---|---|---|
| CH6S-1P4 | 48×48mm | One | 100–240VAC, 50/60Hz | Six digits |
| CH6S-1P2 | One | 24VAC, 50/60Hz or 24–48VDC | ||
| CH6S-2P4 | Two | 100–240VAC, 50/60Hz | ||
| CH6S-2P2 | Two | 24VAC, 50/60Hz or 24–48VDC | ||
| CH6M-1P4 | 72×72mm | One | 100–240VAC, 50/60Hz | |
| CH6M-2P4 | Two | 100–240VAC, 50/60Hz |

| Position | Code | Meaning |
|---|---|---|
| 1: Prefix | C | Fixed brand prefix |
| 2: Series | H | Counter/timer |
| 3: Display digits | 6 | Six digits, integer display up to 999999; used by the complete models above |
| 4 | Four-digit ordering option, integer display up to 9999 | |
| 4: Front size | S | 48×48mm |
| M | 72×72mm | |
| 5: Preset stages | 1P | One-stage setting |
| 2P | Two-stage setting | |
| 6: Supply | 4 | 100–240VAC, 50/60Hz |
| 2 | 24VAC, 50/60Hz or 24–48VDC |
| Input mode | Count pattern |
|---|---|
| UP | Up-count pattern |
| UP-1 | Up-count variant 1 |
| UP-2 | Up-count variant 2 |
| dn | Down-count pattern |
| dn-1 | Down-count variant 1 |
| dn-2 | Down-count variant 2 |
| Ud-A | Up/down with direction input |
| Ud-b | Individual up/down input pulses |
| Ud-C | Phase-difference up/down inputs |
The complete INA/INB charts distinguish the gating, edge and phase relationships for each pattern. In the charts, A must be at least the minimum signal width and B at least half that width. Shorter signals can produce a count error of ±1.

| Logical state | PNP voltage input | NPN voltage-free input |
|---|---|---|
| H | 5–30VDC | Short circuit |
| L | 0–2VDC | Open circuit |
| Counting speed | Minimum signal width |
|---|---|
| 1cps | 500ms |
| 30cps | 16.7ms |
| 1kcps | 0.5ms |
| 5kcps | 0.1ms |
| 10kcps | 0.05ms |

| Output mode | Applicable input groups |
|---|---|
| F | Up / Up-1 / Up-2; Down / Down-1 / Down-2; Up/Down A / B / C |
| N | |
| C | |
| R | |
| K | |
| P | |
| Q | |
| A | |
| S | Up/Down A / B / C |
| T | |
| D |
Choose the required threshold, pulse, hold and reset behavior from the response charts. A one-stage instrument's OUT corresponds to OUT2 of a two-stage instrument. In two-stage operation, OUT1 can use one-shot or hold output. OUT1's preset can be zero in all output modes; OUT2's preset cannot be zero in C, R, P or Q.


| Code | Timing function | Power-on behavior |
|---|---|---|
| OND | Signal delay | Reset |
| OND.1 | Signal delay, variant 1 | Reset |
| OND.2 | Power-up delay | Hold |
| FLK | Flashing | Reset |
| FLK.1 | Flashing, variant 1; hold or one-shot output | Reset |
| FLK.2 | Flashing, variant 2; hold or one-shot output | Hold |
| INT | Interval | Reset |
| INT.1 | Interval, variant 1 | Reset |
| INT.2 | Interval, variant 2 | Reset |
| OFD | Signal off-delay | Reset |
| NFD | On/off delay | Reset |
| NFD.1 | On/off delay, variant 1 | Reset |
| INTG | Accumulated integration timing | Reset |
Timer settings cover 0.001s–99999.9h with twelve time-format choices, forward timing or countdown. The one-shot output duration is 0.01–99.99s in 10ms steps. Select the mode-specific response to START, INHIBIT and RESET from the complete diagrams.

| Parameter | Rating |
|---|---|
| Power consumption | ≤12VA; mains-supply wiring examples are marked 5VA |
| Counter display range | Scaled range 0.00001–99999.9, according to decimal/unit settings |
| Counter reset signal width | 1ms or 20ms selectable |
| Timer control signals | INA, RESET, INHIBIT and BATCH RESET; 2ms or 20ms selectable minimum signal width |
| Memory retention | 10 years, non-volatile semiconductor memory |
| Connection | Terminal block |
| Auxiliary supply shown in wiring | 12VDC, 100mA |
| Relay output shown in wiring | 3A at 250VAC; one or two preset-stage outputs according to model |
| Transistor outputs shown in wiring | Maximum 30VDC, 100mA; functions and terminals depend on model |
| Utilization ratings | AC-15: Ie 3A at 250VAC/380VAC; DC-13: Ie 3A at 24–48VDC |
| Operating temperature | −25 to +70°C, unfrozen |
| Storage temperature | −30 to +80°C, unfrozen |
| Humidity | 35–95%RH, non-condensing |
| Conformity references | CCC: GB/T14048.5; CE: EN60947-5-1; applicable documentation depends on the ordered model |

| Format | Front size | Shell dimensions | Panel opening |
|---|---|---|---|
| CH6S | 48×48mm | 44.3×44.3×81mm | 45×45mm |
| CH6M | 72×72mm | 67×67×81mm | 68×68mm |

These industrial instruments are not intended for exceptionally high-reliability nuclear, gas or power systems; personal or property safety functions; harsh outdoor, contaminated, electromagnetic, vibration or shock environments; fire or explosion hazards; or military and aerospace applications unless specifically designed for that use and confirmed in writing.