| Part Number: | CDT6 | - | X | 1 | 10 | W |
|---|---|---|---|---|---|---|
| Explanation: |
Product Family CDT6 - DIN rail time relay |
Series X - Digital display multifunction time relay with 20 operating modes |
Contact Arrangement 1 - One changeover contact |
Contact Current Rating 10 - 10A contacts; AC-15 operational current 2.5A at 250VAC |
Power Supply W - 12–240VAC/DC; 50–60Hz for AC |
CDT6-X combines a digital display and button settings with 20 operating modes: five supply-controlled modes, thirteen signal-controlled modes and continuous ON/OFF modes. The timing range extends from 0.1s to 99 days. One- and two-contact versions use an 18mm-wide housing for 35mm DIN rail mounting.
Select the contact count and 10A or 16A version with the required supply. The four common complete models use the W wide-range 12–240VAC/DC supply. Front-panel MD and arrow buttons provide the documented button-setting interface, with green power and red relay-output indication.

| Field | Codes and meaning |
|---|---|
| Family | CDT6: DIN rail time relay |
| Series | X: digital display multifunction time relay |
| Contact arrangement | 1: one changeover; 2: two changeovers |
| Contact rating | 10: 10A; 16: 16A |
| Supply in ordering guide | W: 12–240VAC/DC; A–Z letter combinations: custom voltage |
| Model | Changeover contacts | Contact Ith / Ie | Supply |
|---|---|---|---|
| CDT6-X110W | 1 | 10A / 2.5A | 12–240VAC/DC; 50–60Hz for AC |
| CDT6-X210W | 2 | 10A / 2.5A | |
| CDT6-X116W | 1 | 16A / 5A | |
| CDT6-X216W | 2 | 16A / 5A |
The web labels CDT6-X1 and CDT6-X2 identify the one- and two-contact arrangements. The technical table additionally describes an M 220VAC supply version; the ordering guide and common full-model table specify W and custom supply selections. Confirm the complete code when requesting another supply configuration.
| Mode | Function and chart relationship |
|---|---|
| 01 | Power-on delay: supply starts t, then the output closes. |
| 02 | Timed disconnection: the output closes at power-on, then opens after t. |
| 03 | Repeating cycle, OFF first: OFF interval t1 alternates with ON interval t2 while supplied. |
| 04 | Repeating cycle, ON first: ON interval t2 alternates with OFF interval t1 while supplied. |
| 05 | Pulse output: after power-on delay t1, the output closes for t2. |
| 06 | Externally controlled on-delay: S must remain active through t before the output closes; the chart shows a shorter input pulse producing no closure. |
| 07 | Off-delay triggered by the falling edge of S; the chart preserves the effect of further control transitions. |
| 08 | Timed disconnection triggered by the rising edge of S, with output interval t. |
| 09 | Timed output closure triggered by the falling edge of S, with output interval t. |
| 10 | On-delay and off-delay controlled by S, with separate t1 and t2 intervals. |
| 11 | Pulse conversion: successive S pulses alternate the output state. |
| 12 | Externally controlled repeating cycle, OFF first, using t1 and t2. |
| 13 | Externally controlled repeating cycle, ON first, using t2 and t1. |
| 14 | Externally controlled pulse output, with the t1 delay and t2 output interval shown in the chart. |
| 15 | Externally controlled delayed start and stop, with t1 and t2 intervals tied to the control pulses. |
| 16 | Externally controlled dual delayed disconnection; the chart identifies t1, t2 and the combined t1+t2 interval. |
| 17 | Externally controlled delayed start, with delay t before output activation. |
| 18 | Externally controlled delayed closure; use the illustrated S/R relationship and t interval. |
| 19 | Continuous ON: output remains closed while supplied. |
| 20 | Continuous OFF: output remains open while supplied. |

| Characteristic | CDT6-X1 | CDT6-X2 |
|---|---|---|
| Functions / setting | 20 modes; button settings | |
| Supply terminals | A1–A2 | |
| W supply | 12–240VAC/DC; 50–60Hz for AC | |
| W power consumption | 0.09–3VA on AC; 0.05–1.7W on DC | |
| M supply in technical table | 220VAC, 50Hz | |
| M power consumption | Maximum 6VA / 1.3W | Maximum 6VA / 1.9W |
| Supply tolerance | −15% to +10% | |
| Rated impulse withstand voltage | 2.5kV | |
| Rated insulation voltage | 250V | |
| Delay range | 0.1s to 99 days | |
| Setting accuracy / repeatability | 2% / 0.2% | |
| Temperature influence | 0.05%/°C, referenced to 20°C | |
| 10A contact version | One changeover, 10A at 250VAC/24VDC | Two changeovers, 10A at 250VAC/24VDC |
| 16A contact version | One changeover, 16A at 250VAC/24VDC | Two changeovers, 16A at 250VAC/24VDC |
| AC-15 operational rating at 250VAC | 10A contact version: Ie 2.5A; 16A contact version: Ie 5A | |
| Minimum switching power | 500mW | |
| Indication | Green power LED; red output LED | |
| Mechanical / electrical life | 10,000,000 mechanical operations; 100,000 electrical operations with resistive load | |
| Reset time | Maximum 200ms | |
| Operating temperature | −20°C to +55°C | |
| Storage / transport temperature | −35°C to +75°C | |
| Mounting / orientation | 35mm DIN rail; any orientation | |
| Protection / pollution degree | IP20 / 2 | |
| Maximum installation altitude | 2000m | |
| Conductors / tightening torque | One 2.5mm² conductor or two 1.5mm² conductors; 0.4N·m | |
| Dimensions | 90mm high × 18mm wide × 65mm deep | |
| Weight | 67g | 80g |


The selection document lists CCC with GB/T14048.5 and CE with EN60947-5-1. Certificate document numbers are available from CNTD. Select the contact version using the applicable load duty rating.
The manufacturer requires specially designed equipment and written confirmation for high reliability energy systems, applications involving personal safety or major property risk, harsh or outdoor environments, fire or explosion risks, and military or aerospace use.