CDT6-X Digital Display Multifunction Time Relays

Series Part Number

Part Number: CDT6 - X 1 10 W
Explanation:

Product Family

CDT6 - DIN rail time relay

Series

X - Digital display multifunction time relay with 20 operating modes

Contact Arrangement

1 - One changeover contact
2 - Two changeover contacts

Contact Current Rating

10 - 10A contacts; AC-15 operational current 2.5A at 250VAC
16 - 16A contacts; AC-15 operational current 5A at 250VAC

Power Supply

W - 12–240VAC/DC; 50–60Hz for AC
A–Z letter combinations - Custom voltage; specify the exact code for the required version

Description

CDT6-X Digital Multifunction Time Relays

CDT6-X combines a digital display and button settings with 20 operating modes: five supply-controlled modes, thirteen signal-controlled modes and continuous ON/OFF modes. The timing range extends from 0.1s to 99 days. One- and two-contact versions use an 18mm-wide housing for 35mm DIN rail mounting.

Select the contact count and 10A or 16A version with the required supply. The four common complete models use the W wide-range 12–240VAC/DC supply. Front-panel MD and arrow buttons provide the documented button-setting interface, with green power and red relay-output indication.

Series Part Number Guide

CDT6-X model code diagram with digital timer series, contact arrangement, contact rating and supply fields
Example CDT6-X110W: digital multifunction timer, one changeover contact, 10A contact version and W supply.
FieldCodes and meaning
FamilyCDT6: DIN rail time relay
SeriesX: digital display multifunction time relay
Contact arrangement1: one changeover; 2: two changeovers
Contact rating10: 10A; 16: 16A
Supply in ordering guideW: 12–240VAC/DC; A–Z letter combinations: custom voltage

Common Complete Models

ModelChangeover contactsContact Ith / IeSupply
CDT6-X110W110A / 2.5A12–240VAC/DC; 50–60Hz for AC
CDT6-X210W210A / 2.5A
CDT6-X116W116A / 5A
CDT6-X216W216A / 5A

The web labels CDT6-X1 and CDT6-X2 identify the one- and two-contact arrangements. The technical table additionally describes an M 220VAC supply version; the ordering guide and common full-model table specify W and custom supply selections. Confirm the complete code when requesting another supply configuration.

Twenty Operating Modes

ModeFunction and chart relationship
01Power-on delay: supply starts t, then the output closes.
02Timed disconnection: the output closes at power-on, then opens after t.
03Repeating cycle, OFF first: OFF interval t1 alternates with ON interval t2 while supplied.
04Repeating cycle, ON first: ON interval t2 alternates with OFF interval t1 while supplied.
05Pulse output: after power-on delay t1, the output closes for t2.
06Externally controlled on-delay: S must remain active through t before the output closes; the chart shows a shorter input pulse producing no closure.
07Off-delay triggered by the falling edge of S; the chart preserves the effect of further control transitions.
08Timed disconnection triggered by the rising edge of S, with output interval t.
09Timed output closure triggered by the falling edge of S, with output interval t.
10On-delay and off-delay controlled by S, with separate t1 and t2 intervals.
11Pulse conversion: successive S pulses alternate the output state.
12Externally controlled repeating cycle, OFF first, using t1 and t2.
13Externally controlled repeating cycle, ON first, using t2 and t1.
14Externally controlled pulse output, with the t1 delay and t2 output interval shown in the chart.
15Externally controlled delayed start and stop, with t1 and t2 intervals tied to the control pulses.
16Externally controlled dual delayed disconnection; the chart identifies t1, t2 and the combined t1+t2 interval.
17Externally controlled delayed start, with delay t before output activation.
18Externally controlled delayed closure; use the illustrated S/R relationship and t interval.
19Continuous ON: output remains closed while supplied.
20Continuous OFF: output remains open while supplied.
Complete CDT6-X modes 01 to 20 timing diagram matrix showing supply Us, control S, relay R and t, t1, t2 intervals
All twenty timing charts are retained together so trigger edges, retrigger behavior and the separate t1/t2 intervals can be compared. Us is supply, S the external control signal and R the relay output. Follow the selected chart when commissioning the timer.

Electrical, Timing and Installation Specifications

CharacteristicCDT6-X1CDT6-X2
Functions / setting20 modes; button settings
Supply terminalsA1–A2
W supply12–240VAC/DC; 50–60Hz for AC
W power consumption0.09–3VA on AC; 0.05–1.7W on DC
M supply in technical table220VAC, 50Hz
M power consumptionMaximum 6VA / 1.3WMaximum 6VA / 1.9W
Supply tolerance−15% to +10%
Rated impulse withstand voltage2.5kV
Rated insulation voltage250V
Delay range0.1s to 99 days
Setting accuracy / repeatability2% / 0.2%
Temperature influence0.05%/°C, referenced to 20°C
10A contact versionOne changeover, 10A at 250VAC/24VDCTwo changeovers, 10A at 250VAC/24VDC
16A contact versionOne changeover, 16A at 250VAC/24VDCTwo changeovers, 16A at 250VAC/24VDC
AC-15 operational rating at 250VAC10A contact version: Ie 2.5A; 16A contact version: Ie 5A
Minimum switching power500mW
IndicationGreen power LED; red output LED
Mechanical / electrical life10,000,000 mechanical operations; 100,000 electrical operations with resistive load
Reset timeMaximum 200ms
Operating temperature−20°C to +55°C
Storage / transport temperature−35°C to +75°C
Mounting / orientation35mm DIN rail; any orientation
Protection / pollution degreeIP20 / 2
Maximum installation altitude2000m
Conductors / tightening torqueOne 2.5mm² conductor or two 1.5mm² conductors; 0.4N·m
Dimensions90mm high × 18mm wide × 65mm deep
Weight67g80g

Connections and Mounting Drawings

CDT6-X1 and X2 supply, S input and changeover contact wiring diagrams
A1/A2 supply and S control connections are shown for each version. First changeover: 15 common, 16 NC, 18 NO. Second changeover on X2: 25 common, 26 NC, 28 NO.
CDT6-X enclosure dimensions with digital display and buttons, 18mm width, 90mm height and 65mm depth
Overall enclosure dimensions are 90mm × 18mm × 65mm. Upper side-profile sections are 31mm and 19mm; the front drawing locates the display, controls and terminal rows.

The selection document lists CCC with GB/T14048.5 and CE with EN60947-5-1. Certificate document numbers are available from CNTD. Select the contact version using the applicable load duty rating.

The manufacturer requires specially designed equipment and written confirmation for high reliability energy systems, applications involving personal safety or major property risk, harsh or outdoor environments, fire or explosion risks, and military or aerospace use.