CDT6-S Repeating Cycle DIN Rail Time Relays

Series Part Number

Part Number: CDT6 - S 1 10 M
Explanation:

Product Family

CDT6 - DIN rail time relay

Series

S - Repeating cycle timer with independently adjustable ON/OFF durations

Contact Arrangement

1 - One changeover contact
2 - Two changeover contacts

Contact Current Rating

10 - 10A contacts; AC-15 operational current 2.5A at 250VAC
16 - 16A contacts; AC-15 operational current 5A at 250VAC

Power Supply

M - 220VAC, 50–60Hz
W - 12–240VAC/DC; 50–60Hz for AC
A–Z letter combinations - Custom voltage

Description

CDT6-S Repeating Cycle DIN Rail Timers

CDT6-S time relays repeatedly switch a control circuit ON and OFF with independently adjustable ON and OFF durations. Applications include periodic circuit energization, lighting and heating control. The range covers 0.1s to 100 days in an 18mm-wide housing for 35mm DIN rail installation.

The S-to-A1 connection selects the starting sequence: leave S open for ON first, or short S to A1 for OFF first. Choose one or two changeover contacts, the 10A or 16A contact version and the required supply.

Series Part Number Guide

CDT6-S cycle timer ordering layout with contact count, current rating and supply fields
Example CDT6-S110M specifies one changeover contact, 10A contacts and 220VAC supply in the repeating-cycle series.
FieldCodes and meaning
FamilyCDT6: DIN rail time relay
SeriesS: repeating cycle time relay
Contact arrangement1: one changeover contact; 2: two changeover contacts
Contact rating10: 10A; 16: 16A
SupplyM: 220VAC; W: 12–240VAC/DC; A–Z letter combinations: custom voltage. AC frequency is 50–60Hz.

Common Complete Models

ModelChangeover contactsContact Ith / IeSupply
CDT6-S110M110A / 2.5A220VAC, 50–60Hz
CDT6-S210M210A / 2.5A220VAC, 50–60Hz
CDT6-S116W116A / 5A12–240VAC/DC; 50–60Hz for AC
CDT6-S216W216A / 5A12–240VAC/DC; 50–60Hz for AC

The web labels CDT6-S1 and CDT6-S2 identify the contact arrangements. The four common full codes additionally identify current rating and supply; other selections follow the ordering guide.

ON-First and OFF-First Sequences

CDT6-S timing charts comparing ON-first with open S and OFF-first with S shorted to A1
In this series, t1 is the ON interval and t2 the OFF interval. With S open, the sequence starts ON for t1. Shorting A1–S selects OFF first for t2. The cycle continues while supply Un is present.

Separate range/value knobs set the ON and OFF durations. The manufacturer specifies a ten-position delay range covering 0.1s to 100 days. Set each duration for the required duty cycle and use the chart corresponding to the S connection.

Electrical, Timing and Installation Specifications

CharacteristicCDT6-S1CDT6-S2
FunctionRepeating ON/OFF cycle
Supply terminalsA1–A2
W supply12–240VAC/DC; 50–60Hz for AC
W consumption0.09–3VA on AC; 0.05–1.7W on DC
M supply220VAC, 50–60Hz
M consumptionMaximum 6VA / 1.3WMaximum 6VA / 1.9W
Supply tolerance−15% to +10%
Timing range / setting0.1s to 100 days; separate front knobs for ON and OFF intervals
Setting accuracy / repeatability10% / 0.2%
Temperature influence0.05%/°C referenced to 20°C; equivalent to approximately 0.0278%/°F referenced to 68°F
10A contact versionOne changeover, 10A at 250VAC/24VDCTwo changeovers, 10A at 250VAC/24VDC
16A contact versionOne changeover, 16A at 250VAC/24VDCTwo changeovers, 16A at 250VAC/24VDC
AC-15 operational current at 250VAC10A contact version: Ie 2.5A; 16A contact version: Ie 5A
Minimum switching power500mW
Power / output indicationGreen LED / red LED
Mechanical life10,000,000 operations
Electrical life, resistive load100,000 operations
Reset timeMaximum 200ms
Operating temperature−20°C to +55°C
Storage / transport temperature−35°C to +75°C
Mounting / orientation35mm DIN rail; any orientation
Protection / pollution degreeIP20 / 2
Maximum altitude2000m
Conductors / tightening torqueOne 2.5mm² conductor or two 1.5mm² conductors; 0.4N·m
Dimensions90mm high × 18mm wide × 65mm deep
Weight67g80g

Connections and Dimensions

CDT6-S1 and S2 wiring symbols with A1/A2 supply, S sequence selection and one or two changeover contacts
Supply connects to A1/A2. S selects the starting sequence through its connection to A1. The first output uses 15 common, 16 NC and 18 NO; the second on S2 uses 25 common, 26 NC and 28 NO.
CDT6-S 18mm-wide DIN rail enclosure drawing with separate ON/OFF adjustment knobs
Overall dimensions are 90mm × 18mm × 65mm. The side profile includes 31mm and 19mm upper sections; the front drawing identifies the terminal rows and four adjustment knobs.

The selection document lists CCC with GB/T14048.5 and CE with EN60947-5-1. Certificate document numbers are available from CNTD. Apply the relevant contact duty rating for the controlled load.

The manufacturer requires specially designed equipment and written confirmation for high reliability energy systems, applications involving personal safety or major property risk, harsh or outdoor environments, fire or explosion risks, and military or aerospace use.