| Part Number: | CDT6 | - | EC | 1 | 10 | M |
|---|---|---|---|---|---|---|
| Explanation: |
Product Family CDT6 - DIN rail time relay |
Series EC - Dual-function timer: power-on delay or timed disconnection after power-on |
Contact Arrangement 1 - One changeover contact |
Contact Current Rating 10 - 10A contact version; AC-15 operational current 2.5A at 250VAC |
Power Supply M - 220VAC, 50–60Hz |
CDT6-EC provides two selectable timing functions in an 18mm-wide housing: power-on delay and timed disconnection after power-on. DIP switches select the function and timing band, while the front knob adjusts the delay. The 0.1s to 10-day range suits industrial control circuits for lighting, heating, motors and fans.
The documented common model CDT6-EC110M has one 10A changeover contact and a 220VAC rated supply. The family overview also identifies 24VDC operation; specify the required supply and obtain the applicable terminal assignment for that configuration.

| Field | Code | Meaning |
|---|---|---|
| Family | CDT6 | DIN rail time relay |
| Series | EC | Dual-function timer: power-on delay or timed disconnection |
| Contact arrangement | 1 | One changeover contact |
| Contact rating | 10 | 10A contact version |
| Supply | M | 220VAC |
| A–Z letter combinations | Custom voltage; use the exact code for the specified configuration |
| Common full model | Functions | Output | Supply |
|---|---|---|---|
| CDT6-EC110M | Power-on delay; timed disconnection after power-on | One changeover; Ith 10A, Ie 2.5A | 220VAC, 50–60Hz |
| Selection | Sequence |
|---|---|
| A: power-on delay | Applying supply Un starts delay t. The output closes when t expires. Removing Un opens the output. |
| B: timed disconnection | Applying Un closes the output immediately and starts t. The output opens after t; removing Un before t expires also opens the output. |


| Timing characteristic | Value |
|---|---|
| Setting method | DIP switches plus front knob |
| Overall delay range | 0.1s to 10 days |
| Setting accuracy | 5%, as specified in the dedicated selection document |
| Repeatability | 0.2% |
| Temperature influence | 0.05%/°C, referenced to 20°C |
| Reset time | Maximum 200ms |
| Characteristic | Specified value |
|---|---|
| Rated supply, M version | 220VAC, 50–60Hz |
| Supply terminals in M specification | A1–A2 |
| Power consumption | 3VA / 0.5W on AC |
| Supply tolerance | −15% to +10% |
| Output contact | One 10A changeover at 250VAC/24VDC |
| AC-15 operational rating | Ie 2.5A at 250VAC for the 10A contact version |
| Minimum switching power | 500mW |
| Power / output indication | Green LED / red LED |
| Mechanical life | 10,000,000 operations |
| Electrical life, resistive load | 100,000 operations |
| Operating temperature | −20°C to +55°C |
| Storage / transport temperature | −35°C to +75°C |
| Mounting / orientation | 35mm DIN rail; any orientation |
| Protection / pollution degree | IP20 / 2 |
| Maximum altitude | 2000m |
| Conductors / tightening torque | One 2.5mm² conductor or two 1.5mm² conductors; 0.4N·m |
| Dimensions | 90mm high × 18mm wide × 65mm deep |
| Weight | 67g |


The dedicated selection document lists CCC with GB/T14048.5 and CE with EN60947-5-1. Request certificate document numbers from CNTD when needed for procurement.
The manufacturer requires specially designed equipment and written confirmation for high reliability energy systems, applications involving personal safety or major property risk, harsh or outdoor environments, fire or explosion risks, and military or aerospace use.