CDP2-A Adjustable Overcurrent Protectors

Description

CDP2-A monitors load current and opens its power relay when the selected overcurrent threshold is exceeded. The single-line display shows current with 1% stated accuracy. A recovery timer and a configurable limit on consecutive overcurrent events support automatic reconnection control. Choose a 40A, 63A or 80A maximum operating-current version.

The 36mm-wide protector uses a 32-bit controller and magnetic latching relay. It operates across an 80–350V, 45–70Hz supply range at ≤1W power consumption. This is the current-protection member of the CDP2 family; the wide working-voltage range is its supply specification.

Three Models and Complete Codes

Complete modelMaximum operating currentCurrent-protection range in general tableFunction
CDP2-A/40A40A0.1–40AOvercurrent protection
CDP2-A/63A63A0.1–63A
CDP2-A/80A80A0.1–80A

In CDP2-A/63A, C is the fixed prefix, DP2 identifies the family, A selects current protection and 63A specifies the current rating. The hyphen and slash are both part of the ordering code.

Ordering fieldOptionsMeaning
PrefixCFixed brand prefix
FamilyDP2Voltage/current protector family, two-module enclosure width
FunctionAOvercurrent protection; this page's three models
VOvervoltage and undervoltage protection
VAOvervoltage, undervoltage and overcurrent protection
VAWVoltage/current protection with energy and power display
Current rating40A / 63A / 80AMaximum operating current of the complete model
CDP2 ordering diagram with A current-protection function and 40A 63A 80A ratings
Family selection guide. Select function A for overcurrent protection.

Current Threshold, Event Limit and Recovery Delay

The settings below apply to the illustrated 63A configuration. Its P1 current adjustment is 1.0–63.0A with a 63A default. The model table provides the family current-range references; use the menu limits for the selected current-rating version when configuring the device.

MenuParameterDefaultAdjustment rangePurpose
P1Overcurrent threshold63A1.0–63.0ASets the current level for overcurrent protection on the illustrated 63A unit
P2Consecutive overcurrent-event limit00–20Automatic reclosing stops after the configured number of overcurrent events is exceeded
P3Recovery delay30s1–999sSets the delay before reconnection following overcurrent protection

The family trip-delay reference is 0.1–600s. The A-version P1–P3 controls adjust the current threshold, consecutive-event limit and recovery delay, without a separate trip-delay menu item.

Display and Adjustment

The front panel has a current/menu display, output indicator, recovery indicator, overcurrent indicator, SET key, up/down keys and power button. Press SET to cycle through P1, P2 and P3, use the arrow keys to modify the selected value, and hold SET to return to the normal display. Holding an arrow key in the menu provides rapid adjustment.

CDP2-A current display and output recovery overcurrent indicators
A-version panel and four control keys.
CDP2-A sequence for current threshold consecutive event limit and recovery-delay menus
Three-setting adjustment sequence for CDP2-A.

Electrical and Environmental Data

ParameterSpecification
Working supply80–350V; 45–70Hz
Nominal operating voltage, Ue220/230VAC
Current measurement accuracy1%
Operating power consumption≤1W
Pole arrangement1P+N
Rated insulation voltage, Ui400V
Rated impulse withstand voltage, Uimp4kV
ConstructionElectronic control with magnetic latching relay
Enclosure protectionIP40
Ambient temperature−20°C to +50°C
Ambient humidity35–85%RH, non-condensing
Net weight153g
Marking and referenced standardCE; EN60947-5-1

Connections, Conductor Areas and Dimensions

The housing occupies two module widths, with an electrical pole arrangement of 1P+N. The drawings show two connection arrangements: supply at the top with load at the bottom, or supply at the bottom with load at the top. N is on the left and L on the right; use the corresponding IN/OUT terminal markings.

Wiring-guide current referenceConductor cross-sectional area
32A6mm²
40A10mm²
50A10mm²
63A16mm²
80A25mm²

These are conductor areas, not diameters. The 32A and 50A entries are installation-reference rows; the complete A models listed here have 40A, 63A and 80A ratings.

CDP2 line neutral and load terminals with top or bottom supply input
Supply/load wiring arrangements shared by the CDP2 family.
CDP2 87mm high 36mm wide and 66mm deep enclosure drawing
Overall dimensions: 87±0.2mm high, 36±0.2mm wide and 66±0.2mm deep.

The nine-page attachment preserves the full family selection guide, separate V/A/VA/VAW settings, drawings and use precautions. The current-protection functions and A-version menu above apply to this page. Regional specifications may differ.