| Part Number: | CDM6 | - | 1 | 2 | 16 | W |
|---|---|---|---|---|---|---|
| Explanation: |
Product Family CDM6 - DIN rail electronic pulse relay |
Input Series 1 - Single-pulse input |
Output Function 1 - One changeover output |
Output Contact Rating 10 - 10A contact version |
Operating Voltage M - 220VAC, 50/60Hz; mains-voltage neon switch connection |
CDM6 electronic pulse relays change the output state in response to a control pulse at A1–S. Choose CDM6-11 for one changeover or CDM6-12 for two changeovers. The dual-output version offers separate output sequencing or simultaneous switching through the B1/B2 configuration.
| Complete model | Outputs | Contact rating | Supply |
|---|---|---|---|
| CDM6-1110M | One changeover | Ith 10A; Ie 2.5A | 220VAC, 50/60Hz |
| CDM6-1210M | Two changeovers | Ith 10A; Ie 2.5A | |
| CDM6-1116W | One changeover | Ith 16A; Ie 5A | 12–240VAC/DC; AC 50/60Hz |
| CDM6-1216W | Two changeovers | Ith 16A; Ie 5A |

| Position | Code | Meaning |
|---|---|---|
| 1: Family | CDM6 | DIN rail electronic pulse relay |
| 2: Product series | 1 | Single-pulse input |
| 3: Output function | 1 | One changeover |
| 2 | Two changeovers | |
| 4: Contact rating | 10 | 10A version |
| 16 | 16A version | |
| 5: Operating voltage | M | 220VAC, 50/60Hz |
| W | 12–240VAC/DC; AC 50/60Hz |
For CDM6-11, successive valid input pulses switch the output on and off. The minimum control pulse width is 25ms. For CDM6-12, leave B1/B2 open for the four-state sequence below, or bridge B1/B2 for the two outputs to switch together. The complete charts also show the illustrated response to a supply interruption.
| CDM6-12 connection | Sequence stage | R1: 11–14 | R2: 21–24 |
|---|---|---|---|
| B1/B2 open | Initial / fourth pulse | Off | Off |
| First pulse | On | Off | |
| Second pulse | Off | On | |
| Third pulse | On | On | |
| B1/B2 bridged | First pulse | On | On |
| Second pulse | Off | Off |

| Parameter | CDM6-11 | CDM6-12 |
|---|---|---|
| Supply terminals | A1–A2 | |
| W supply | 12–240VAC/DC; AC 50–60Hz | |
| W power consumption | AC: 0.09–3VA; DC: 0.05–1.2W | |
| M supply | 220VAC, 50–60Hz | |
| M power consumption | AC maximum 12VA / 1.3W | AC maximum 12VA / 1.9W |
| Permitted supply fluctuation | −15%, +10% | |
| Control terminals / pulse width | A1–S / minimum 25ms | |
| Output contact arrangement | 1×SPDT | 2×SPDT |
| 16A version load rating | 16A AC-1; contact switching voltage 250VAC/24VDC | |
| Minimum switching power | 500mW | |
| Indicators | Green supply LED; red output LED | |
| Reset time | Maximum 200ms | |
| Mechanical / resistive electrical life | 1×10⁷ / 1×10⁵ operations | |
| Weight, W / M version | 58g / 57g | 79g / 77g |
The contact current rating is separate from the relay supply voltage. Use the rating of the selected 10A or 16A version for the intended load.
| Parameter | Condition |
|---|---|
| Neon switch connection | M mains-voltage version, A1–S; connection quantity characterized at 230VAC |
| Maximum neon quantity | 75 at 230VAC, based on approximately 0.68mA per neon |
| Operating temperature | −20 to +55°C |
| Storage and transport temperature | −35 to +75°C |
| Mounting / orientation | 35mm DIN rail / any orientation |
| Protection / altitude / pollution degree | IP20 / ≤2000m / 2 |
| Conductors / tightening torque | 1×2.5mm² or 2×1.5mm² / 0.4N·m |
| Overall dimensions | 90×18×65mm |
| Conformity designations | 3C and CE; applicable documentation depends on the ordered model |
The single-output contacts are 11/12/14; the dual-output version adds 21/22/24. Connect momentary control switches to A1–S and configure B1/B2 on the dual-output version as required by the response chart.



These industrial relays are not intended for exceptionally high-reliability nuclear, gas or power systems; personal or property safety functions; harsh outdoor, contaminated, electromagnetic, vibration or shock environments; fire or explosion hazards; or military and aerospace applications unless specifically designed for that use and confirmed in writing.